ELECTRICAL WIRING - PowerPoint PPT Presentation

1 / 38
About This Presentation
Title:

ELECTRICAL WIRING

Description:

To accompany the Georgia Agriculture Curriculum Lesson 01422 ... UL Listed assures product meets minimum ... Lighting outlets in closets should be wall ... – PowerPoint PPT presentation

Number of Views:16973
Avg rating:3.0/5.0
Slides: 39
Provided by: bobbyj3
Category:

less

Transcript and Presenter's Notes

Title: ELECTRICAL WIRING


1
ELECTRICAL WIRING
  • WIRING BASICS

Written by Bobby Joslin
GA Ag Ed Curriculum Office To accompany the
Georgia Agriculture Curriculum Lesson
01422-6.2 July 2002
2
STANDARDS FOR SAFETY
  • National Electrical Code
  • Local Electrical Code
  • Power Company Requirements
  • Underwriters Laboratory (UL)

3
NATIONAL ELECTRICAL CODE
  • History of the National Electrical Code
  • Purpose of the NEC
  • How Often the NEC is updated
  • Scope of the NEC
  • Enforcement of the NEC
  • Using the NEC

4
LOCAL ELECTRICAL CODES
  • Local authorities may adopt NEC
  • May adopt NEC with modifications
  • Local wiring permits and inspections

5
POWER COMPANY REQUIREMENTS
6
UNDERWRITERS LABORATORY
  • UL Listed assures product meets minimum safety
    standards
  • UL Listed does not mean that product is safe for
    all installations
  • UL Listed is not an indication of quality

7
BRANCH CIRCUITS
  • Definition of circuit
  • Definition of branch circuit

8
BRANCH CIRCUITS IN A RESIDENCE
  • Individual Circuit
  • Small Appliance Circuit
  • Laundry Circuit
  • Bathroom Circuit
  • General Purpose Circuit

9
INDIVIDUAL CIRCUIT
  • Supplies only one outlet or piece of equipment
  • Motors 1/2 horsepower or larger
  • All 240 volt equipment
  • Other equipment such as furnace fan, freezer,
    television, computer

10
SMALL APPLIANCE CIRCUIT
  • Serves receptacles for small appliance loads
  • At least two required by NEC
  • Must be 20 ampere circuits
  • No lighting outlets
  • Cannot serve any other room in house

11
LAUNDRY CIRCUIT
  • Serves only receptacles in laundry room
  • At least one required by NEC
  • Must be 20 ampere circuit
  • May not have lighting outlets
  • May not serve outlets in any other room of house

12
BATHROOM CIRCUIT
  • Circuit to serve receptacles in bathroom
  • At least one required by NEC
  • Must be 20 ampere circuit
  • May not serve lighting outlets
  • May not serve any other room in house

13
GENERAL PURPOSE CIRCUITS
  • Serve all lighting outlets in home
  • Serve all receptacles not on one of the other
    types of circuits
  • May be 15 or 20 ampere (20 ampere preferred)
  • Allow at least one general purpose circuit for
    every 500 square feet of floor space in house

14
Determining the Kind, Number and Location of
Outlets and Switches in a Wiring System
15
Lighting Outlet Requirements
  • At least one wall switch controlled outlet in
    every habitable room in house
  • Stairways consisting of 6 or more steps must have
    lighting outlet that is wall switch controlled at
    both floor levels
  • Attics, underfloor space, utility room and
    basement requirements

16
RECEPTACLE OUTLET REQUIREMENTS
  • No point along the floor line in any wall space
    may be more than 6 feet from a receptacle in
    kitchen, family room, dining room, living room,
    den, sun room, bedroom, recreation room, or
    similar room
  • (Receptacles must be no farther than _____ feet
    apart.)

17
RECEPTACLE REQUIREMENTS
  • A receptacle must be installed at each kitchen
    and dining area counter space if the space is
    wider than 12 inches
  • No point along the wall line of a kitchen counter
    may be more than 24 inches from a receptacle
  • (Receptacles must be no farther than _____
    inches apart)

18
RECEPTACLE REQUIREMENTS
  • At least one receptacle is required within 36
    inches of the outside edge of each basin in
    bathrooms.
  • All receptacles in bathrooms must have ground
    fault circuit interrupter protection

19
RECEPTACLE REQUIREMENTS
  • At least one outdoor receptacle is required
  • All outdoor receptacles must have GFCI protection
  • Outdoor receptacles must be installed in
    waterproof boxes

20
RECEPTACLE REQUIREMENTS
  • At least one receptacle is required in the
    laundry area
  • At least one receptacle is required in a
    basement. All general use receptacles in an
    unfinished basement must have GFCI protection

21
RECEPTACLE REQUIREMENTS
  • At least one receptacle is required in hallways
    10 feet or more in length
  • Effective January 1, 2002, all receptacles in a
    bedroom must have arc-fault circuit interrupter
    protection

22
RECOMMENDATIONS FOR OUTLETS AND SWITCHES
  • Receptacles should generally be located
    approximately above floor line
  • Receptacles preferably should be located near the
    ends of wall space
  • Lighting outlets in closets should be wall switch
    controlled
  • Pull chain lighting outlets should be minimized,
    if used at all

23
RECOMMENDATIONS FOR OUTLETS AND SWITCHES
  • Wall switches should be generally be located
    approximately 48 inches above the floor line and
    on the latch side of doors
  • Three and four way switches should be used to
    control lights in locations such as rooms having
    more than one entrance, stairways, halls,
    basement, covered walkways between the house and
    garage, etc.

24
Determining the Number of Outlets On a General
Purpose Circuit
  • For calculation purposes, estimate a load of at
    least 1.5 amps per outlet on the circuit
  • To determine the maximum number of outlets on a
    20 amp general purpose circuit 20 amps (circuit
    rating) ? 1.5 amps 13 outlets (maximum)
    on the circuit
  • Maximum number of outlets on a 15 amp general
    purpose circuit ________?

25
SELECTING SERVICE ENTRANCE EQUIPMENT
  • Service conductors
  • Service mast
  • Entrance head or weather head
  • Meter base
  • Service entrance cable

26
Service Entrance Panel
  • Purpose
  • Factors to consider when selecting the service
    entrance panel
  • Type of panel
  • Size or ampere rating
  • Circuit capacity or number of spaces for
    connecting circuits

27
PROVIDING OVERCURRENT PROTECTION
  • Providing a means to interrupt an electrical
    circuit when the amperage in the circuit becomes
    excessive
  • Reasons for providing overcurrent protection

28
SIZE OF OVERCURRENT PROTECTION DEVICE TO USE
29
PLANNING ELECTRICAL CIRCUITS
  • Wiring symbols

30
CLASSIFICATION OF CONDUCTORS
  • Grounded conductor
  • Ungrounded conductor
  • Equipment grounding conductor
  • Grounding electrode conductor

31
Grounded Conductor
  • A current carrying conductor that is connected to
    the earth
  • Often called the neutral wire
  • Color must be white or natural gray
  • Known as identified conductor
  • Identity must be maintained throughout a circuit
    and the electrical system

32
Grounded Conductor
  • NEVER connected to a fuse, circuit breaker, or a
    switch
  • One grounded conductor must be connected to all
    120 volt outlets or equipment

33
UNGROUNDED CONDUCTOR
  • A current carrying conductor that is not
    connected to the earth
  • Often called the hot wire
  • Color should not be white, gray, or green. Color
    may be black, red, blue, etc.
  • Circuit breakers (or fuses) and switches are
    placed on the ungrounded conductor

34
UNGROUNDED CONDUCTOR
  • One ungrounded conductor must be connected to all
    120 volt outlets or equipment.
  • Two ungrounded conductors must be connected to
    all 240 volt outlets or equipment.

35
EQUIPMENT GROUNDING CONDUCTOR
  • Under normal conditions, the equipment grounding
    conductor is never a current carrying conductor.
    It serves as a path to ground if a fault occurs
    in electrical equipment or the electrical system
  • May be a bare wire or may have green or green
    with yellow stripe insulation

36
EQUIPMENT GROUNDING CONDUCTOR
  • Always connected to the grounding terminal of
    devices (receptacles, switches, etc.)
  • Always connected to non-current carrying metal
    parts of equipment and circuits (including all
    metal boxes)

37
GROUNDING ELECTRODE CONDUCTOR
  • The large bare copper wire that connects the
    electrical system to the grounding electrode
  • Size is determined by the size of service
    entrance cable being used

38
COLOR CODING OF ELECTRICAL CONNECTIONS
  • Silver or white colored terminal - attach the
    grounded conductor
  • Copper or brass colored terminal -attach the
    ungrounded conductor
  • Green colored terminal - attach the equipment
    grounding conductor
Write a Comment
User Comments (0)
About PowerShow.com