Title: CIVL 2230 Introduction to Structural Concepts
1CIVL 2230 Introduction to Structural Concepts
Design
The University of Sydney
Department of Civil Engineering
2LECTURE 2 PERMANENT AND IMPOSED ACTIONS
- A PERMANENT ACTION (G) also known as a dead load
is an action acts continuously through the design
working life and for which variations in
magnitude with time are small. Permanent actions
shall be taken to include the self-weight of the
following - (a) The structure.
- (b) All other materials in the structure (walls,
floors, roofs, suspended ceilings and other
permanent construction).
3- An IMPOSED ACTION (Q), also known as live load,
is a variable action resulting from the intended
use or occupancy of the structure. It may be
removed or replaced on a structure. -
- The magnitude of the imposed action to be applied
to a structure is specified by the Standards, and
it is mandatory for the designer to adopt it
undiminished, except for any concessions that are
listed.
4- Probably the most common imposed action is that
of uniformly distributed actions on floors and
roofs. These are always given in units of kN/m2
(kilopascal, kPa) and are listed in Table 3.1 of
AS/NZ 1170.12002 typical values are 1.5 kPa for
general areas of dwellings, 3.0 kPa for offices
in general use and public areas with tables, up
to 5.0 kPa for corridors, stairs, balconies,
dance halls etc., and 7.5 kPa for stages in
public assembly areas. - For non-trafficable roofs, the action is
generally 0.25 kPa, but full details are given in
Table 3.2 of the Standard. - A concentrated action shall also be considered in
the position giving the most adverse effect. A
typical value is 4.5 kN in factories.
5CALCULATION OF PERMANENT ACTION
- calculated from the volume and density of the
components of a structure. - the design process is cyclic, so that a
preliminary design based on assumed initial
dimensions will be re-assessed and most likely
re-calculated using the 'final' derived
dimensions.
6- In design practice for buildings, it is not
possible to calculate permanent actions
precisely, and some approximations are made. - For example, if the floors consist of reinforced
concrete slabs and beams, the self-weight of the
concrete is calculated on nominal dimensions,
using density of 2500 kg/m3 for normal weight
concrete, which also includes the weight of the
steel reinforcement. -
- The slab may be covered with a topping and/or
tiles or other covering, which add significantly
to the load. - Partition walls also add to the permanent
actions, and an allowance is normally made for
them by replacing the 'line' load of the walls by
an equivalent uniformly distributed action
typically 0.5 kPa over the entire floor area.
7Example of a RC building
8(No Transcript)
9(No Transcript)
10Permanent action for design of the slab
- Slabs normally sustain only their own
self-weight, and any directly supported load such
as topping, tiles, ceiling under, services such
as pipes, cables etc. - Of course the slab is supported on beams and/or
walls, but the slab sees only the actions
directly on its surface
11- In this case, the slab is supported by beams or
by the shear core. It is unusual for the slab
thickness to change over the extent of a floor.
A critical slab panel is rectangular in plan view
and has approximate dimensions 8m x 8m. An
initial estimate of the required slab thickness
is 175 mm. Therefore, the initial estimate of
permanent action on the slab, expressed as
kilonewtons per square metre of slab
(kiloPascals, kPa), is
12- Bare slab0.175?2,500?9.8/1,000 4.3 kPa
- Topping tiles (estimate only) 1.0 kPa
- Ceiling under services (estimate) 0.5 kPa
- Partitions (estimate) 0.5 kPa
-
- Total permanent action on slab 6.3 kPa
- Normally, the actual self-weight of the
quantities marked 'estimate' are not known
accurately at the time of the initial design, and
therefore an initial estimate must be made to
allow the design to proceed.
13Permanent action for design of the beams
14- In a square panel (e.g. 8m ? 8m), the figure
becomes 4-sided of total area 32 m2, and the
total permanent action on that beam transmitted
by the slab becomes 6.3 ? 32 201.6 kN. This
load is however not distributed uniformly over
the span of the beam, but increases linearly from
zero at the ends (Figure 5) to a maximum of 6.3?8
50.4 kN/m at midspan.
15RECTANGULAR INTERIOR PANEL
Wmax 6.3x8.1
l
l
Wmax 6.3x8.1
SQUARE PANEL
16Useful formula for replacing the 6 or 4-sided
load distribution by a uniformly distributed load
- L is the span of the beam, l is the distance from
the end supports at which the distributed loading
reaches its maximum, wmax is the maximum value of
the load distribution ( 50.4 kN/m in this
example), and w' is the equivalent load uniformly
distributed over the entire span.
17- The formula ensures that the maximum bending
moment on the beam at midspan, i.e. wL2/8, is
equal to the maximum bending moment at midspan in
the actual non-uniform load case. It is a good
exercise for the student to verify this equality.
It must be noted that the equivalent load
distribution w' does not give the correct value
of maximum shear, which must be evaluated from
first principles. - Also, fixed-end moments of wL2/12 can be subject
to a maximum error of 5 (triangular load),
reducing to zero error as the load distribution
approaches uniformity.
18- To this permanent action on the beam must be
added the self-weight of the stem of the beam
(the upper part of the beam has already been
accounted for by the slab load calculation). The
total equivalent permanent action on the beam
therefore becomes
19- The maximum moment at midspan is therefore wL2/8
41.6?82/8 333 kNm. - The student should verify that the correct
maximum shear force at the support is 132.8 kN,
including the effect of the beam stem.
20Permanent actions on columns
- Estimation of permanent actions on columns is
especially critical, as errors accumulate when
the load carried by columns in the lower levels
of buildings are estimated by summation of each
level above. There are several ways of
calculating permanent actions on columns,
depending on the accuracy required. - A full computer frame analysis is normally
warranted for the final design, but more
approximate methods are acceptable for a
preliminary design.
21(No Transcript)
22-
- If the building has a regular array of columns,
then permanent actions on interior columns may be
calculated by considering a plan tributary area
of slab around each column (Figure 6). - If for example a building has 50 stories, and
the columns are spaced 8 m apart, then an
interior column at ground level would carry a
permanent action due to the slabs (only) of
50?8?8?6.3 20,160 kN. - Add self-weight of the beam stems and of the
columns themselves.
23- Exterior columns carry lower loads than interior
columns. AS3600 allows a simplified method that
states the negative moment at the first interior
support may be taken as wL2/10, implying that the
load on the exterior columns is 20 less than the
load calculated from a tributary area. - This also implies an increase in the load on the
first interior columns. Global equilibrium of the
entire structure must of course always be
satisfied.
24CALCULATION OF IMPOSED ACTIONS
- Imposed actions (live loads) are that part of the
load that may be imposed because of the use or
purpose of the building or structure. It
includes the loads specified by the loading
standards (e.g. AS/NZS 1170.1-2002) for various
uses and occupancies of the building. - These specified imposed actions cover the
occupants, furniture, movable equipment,
fixtures, books, etc,. - Imposed actions include impact and inertia loads,
but exclude wind, snow and earthquake loads,
which are covered in other standards.
25FLOOR LOADS IN BUILDINGS
- Floors in houses 1.5 kPa
- Stairs and landings in houses 2.0 kPa
- Office buildings (office use) 3.0 kPa
- Shop floors 4.0 kPa
- Office buildings (file rooms) 5.0 kPa
- Equipment floors 5.0 kPa
- Public assembly (no fixed seating)) 5.0 kPa
- Grandstands 5.0 kPa
- Stages in public assembly areas 7.5 kPa
- Non-trafficable roof (flat or pitched,
- providing shelter from the elements only) 0.25kPa
26- A second type of action is also to be considered
by the designer it takes the form of a
concentrated action on the surface, listed
alongside the distributed load, in Table 3.1 of
AS1170.1. - Normally, the concentrated action is taken as a
point action, or distributed over the small area
of 0.01 m2. - For example, the concentrated action to be used
on ordinary office floors is 4.5 kN, located in
the most damaging location for the design of a
specific structural element (slab, beam, column
etc.). - It is rare for the concentrated action to have a
more severe effect than the distributed action.
27LIVE LOAD REDUCTION
- LIVE LOAD REDUCTION FACTOR
- ? 0.3 3/?A, not greater than 0.5
- A is the sum of all areas supported by a
structural member, in m2. - Does not apply to roof and balcony actions, to
places of assembly, and to areas on which the
imposed action exceeds 5 kPa.
28HEAVY MAINTENANCE HANGAR AT BRISBANE
AIRPORTMAINTENANCE OF 3 LARGE AIRCRAFT FOR
QANTAS AIRWAYSSTRUCTURE BEFORE LIFTCLEAR SPACE
BETWEEN FRONT COLUMN 160 m
29FRONT, SECONDARY AND DISTRIBUTION TRUSSES
30ROOF IN FINAL POSITION