Title: The Frustrating Realities of Cold Climate Design:
1The Frustrating Realities of Cold Climate Design
- Piercing the Skin
- Ins-U-lation versus Ins-O-lation
- Terri Meyer Boake
- University of Waterloo
Richmond City Hall, Richmond, B.C.
2From First Principles
- First Ins-U-late then Ins-O-late
- Walls are thick and have a very high (mandated)
thermal resistance - Windows are thin elements whose thermal
resistance remains a fraction of the wall - Energy efficient window (design) is costly
- If windows are improperly specified, designed and
constructed, energy losses are significant
3The Model National Energy Code of Canada for
Houses 1997
- MNECH is a stand-alone document
- Addresses environmental protection and resource
conservation only - Suggests but does not enforce its rules/ideas
- Relies heavily on CSA Standard A440.2 Energy
Performance of Windows and Other Fenestration
Systems
4MNECH Minimum Insulating Values
- Minimum RSI and R values for up to 5000C Degree
Days (9000F) for above ground opaque elements
are - Attic-type roofs 5.6 m2xoC/W or a U-value of
0.178 W/m2xoC - 31.8 hxft2xoF/Btu 0.031 Btu/hxft2xoF
- All other roofs 4.3 m2xoC/W or a U-value of
0.233 W/m2xoC - 24.4 hxft2xoF/Btu 0.041 Btu/hxft2xoF
- Walls 2.9 m2xoC/W or a U-value of 0.345
W/m2xoC - 16.5 hxft2xoF/Btu 0.061 Btu/hxft2xoF
- Floors 4.5 m2xoC/W or a U-value of 0.217
W/m2xoC - 25.5 hxft2xoF/Btu 0.039 Btu/hxft2xoF
- Windows must only have a maximum U value of 2.60
W/m2xoC (0.457 Btu/hxft2xoF). This will permit
7.5 times as much heat transmission per hour
compared to wall elements! - Skylights must only have a maximum U value of 3.4
W/m2xoC (0.599 Btu/hxft2xoF). This will permit
14.5 to 19 times as much heat loss as the roofs
they displace!
5The Energy Rating (ER) for Windows
- The MNECH uses a new Energy Rating system to
compare the overall performance of windows - Previous standards relied only on separate U, SC,
SHGC and air leakage values - The ER combines
- Solar heat gain coefficient (SHGC)
- Overall heat transmission coefficient (U-value)
- Air leakage
6Solar Heat Gain Coefficient SHGC
- Fraction of solar radiation incident on a window
that appears as solar heat gain in the building - Dimensionless, expressed as a decimal, always
less than 1.0 - Center of glass of a clear single glazed window
has a SHGC of 0.87 - Shading Coefficient (SC) is no longer used
- SC is the SHGC of window relative to the SHGC a
single glazed clear window under the same
conditions - The SC times 0.87 provides a good approximation
of the SHGC for most glazing systems if that is
the only data provided
7ER total performance
- The ER gives a single number to indicate the
combined response to solar heat gain, conductive
heat loss and air leakage in typical Canadian
(cold) climate conditions - Based on total performance, including glazing,
spacers, glass and frame (many other U-values do
not include other than center of glass values) - Developed in CSA Standard A440.2 Energy
Performance of Windows and Other Fenestration
8Understanding the ER
- Only applicable when comparing windows and
sliding glass doors in houses under specified
heating conditions - Assumes vertical installation
- Based upon AVERAGE conditions for solar radiation
on windows facing 4 cardinal directions (i.e.)
north, south, east and west - Minimum requirements are based on climate and
fuel type
9ER positive or negative
- The ER may be positive or negative
- A positive ER means that the window gains more
heat than it loses in the heating season - A negative ER means that the window has an
overall loss of heat during the heating season - Most windows have negative ER values
10ER Requirements for Houses
CSA A440.2 sets out the following ER requirements
for energy efficient windows in houses in the
calculated Energy Level Regions across Canada.
To merely meet CSA 440.2 a window need only meet
the EL1 level.
11ER Limitations
- Good for builders who in a subdivision will have
the same number of windows facing all directions - Not good for passive solar buildings that do not
have evenly oriented windows N,S,E,W (CSA A440.2
does include a calculation method to
differentiate based on solar orientation or on
cooling rather than heating design) - Not the correct number to be plugged into
simulation programs (most want U and SHGC) - Values are developed by window manufacturers
- Not presently many available for comparisons
except through www.enermodal.com, CATALOGUE
program
12Ontario Building Code Requirements for Window
Design
The OBC seems to assume that most builders will
use a minimum amount of glazing and that the
thermal integrity of such buildings will not
likely be compromised by excessive amounts of
glazing.
13Minimum OBC Energy Requirements
- For windows that meet the previous criteria, the
only energy requirements are - (a)Air infiltration shall not exceed 0.775 dm3/s
for each meter (0.5 cfm for each foot) of sash
crack when tested at a pressure differential of
75 Pa (0.011 psi)) - (b)All glazing that separates heated space from
unheated space shall have a thermal resistance of
not less than RSI0.30 m2oC/W (1.70 ft2xhxoF/Btu) - The OBC requirements are slightly more stringent
for residences with electric heating and copy the
MNECH in their requirement of an ER of not less
than 13 for operable windows and sliding glass
doors, and an ER of 0 for fixed glazing. - Additionally, the Code requires that the maximum
amount of glazing (including windows, skylights
and doors) can not exceed 20 of the floor area
of the story being served by the glazing nor
exceed 40 of the total area of the walls of that
story.
14OBC and Passive Solar Design
- The Code does allow for passive, aka Thermal
Design - This design is considered alternative to normal
thermal insulation requirements and allows for
window areas that exceed the 20/40 rule - Increases in window area allowed is proportional
to the increase in its thermal resistance value
i.e. if the Code permitted the building of 10m2
of window with a resistance value of 0.30 m2oC/W
(1.70 ft2xhxoF/Btu), if you selected a window
with an insulation value of 0.40 m2oC/W (2.27
ft2xhxoF/Btu), your ratio would be 0.30/0.40
0.75. You could actually have 13.3 m2 of windows
as when 13.3 is multiplied by 0.75, it translates
to the value of 10m2. Therefore, the higher the
thermal value for the window, the proportionally
higher amount of glazing is permitted resulting
in theoretically identical heat losses.
15OBC and South Facing Windows
- Glazing areas can also be increased where the
design is using passive solar gain principles on
south facing orientations. In such cases the
glazing area may be calculated at 50 of what is
actually being constructed, provided that - (a) the area contains clear glass or has a
shading coefficient of more than 0.70 (the MNECH
uses a value of 0.61), and - (b) faces a direction within 45o of due South,
and - (c) is unshaded in the Winter (calculating
angles based on Dec. 21 at noon), and - (d) the building is designed with a system that
is capable of distributing the solar gain from
such glazed areas throughout the building. - Where houses are designed to be cooled, window
areas cannot be increased, as outlined above,
except where the glazing is shaded in the summer
with exterior devices. The shading is to be
calculated using noon sun angles for June 21.
16CMHC Comparison of Typical Window Thermal
Efficiencies
17Unrealistic Expectations?
- From the previous charts very few windows would
meet the MNECH criteria of ER -13 for Ontario and
Quebec - No windows would meet ER criteria for Manitoba,
Yukon and NWT (severe climates) - Most call for low-e, argon fill and triple
glazing, which is beyond most housing budgets - All but one would exceed the minimum thermal
rating of the OBC of 0.30 m2oC/W (1.70
ft2xhxoF/Btu) - If codes were to mandate the new ER requirements,
we would save energy, but capital building costs
would skyrocket -- what would window
manufacturers do??
18Finding the Right Information
- A very tough job!!
- Varies from Canada (SI) to US (Imperial)
- Must rely on window manufacturers for accurate
information! - Manufacturers info usually not there at all or
inconsistently presented - Use great terms like super energy efficient
without data backup
19Sample Manufacturers Test Data
Loewen Windows Test Data
In this instance the only windows which meet the
-13ER are triple glazed wood frame units. All
others fail. All pass the thermal minimum rating
of 0.30 RSI.
20Understanding the Data
- The values achieved through Loewen testing are
comparable to the CMHC ideals in some cases but
not all - Most of the windows exceed the 0.30 RSI OBC
minimum so could be used to proportionately
increase fenestration areas - None have a SHGC that would permit increases
based on passive solar south facing glazing - Low-E coatings increase the RSI and decrease the
SHGC indicating suitability in energy efficient
thermal design but not passive solar design
21Low-E wins over Solar Gain
- In the Loewen advertising, windows with low-e
coatings are pushed for their insulating
qualities and ability to reduce solar gain - Anti-passive solar which would use differentiated
glazing on the south side to promote solar gain
and shading devices for cooling
22Insulation is better than Insolation???
- Again the advertising clearly shows that
insulating glass and protection from the suns
free heat are the most important attributes of
windows.
23Balancing Ins-U-lation vs. Ins-O-lation
- The codes (and manufacturers) clearly favor
insulation over insolation - It is possible, however more complicated to
design fenestration for passive solar design in
order to achieve reasonable heating values
through window design - It requires separate design tactics for south
facing windows, different windows than are used
on the E,W,N elevations, and additional
calculations - Simpler to use computer simulation programs to be
able to differentiate the elevations and design
for solar passive
24Balancing Insulation
Insolation Daylighting
- 1. INSULATION Calculate heat loss. Uses R/U
values and infiltration - 2. INSOLATION Calculate heat gain. Uses SHGC,
precise orientation, shading, thermal mass. - 3. DAYLIGHTING Calculate how windows reduce
electrical/lighting energy requirements.
25Selling Energy Efficient Window Design
- Most clients and builders regard Code
requirements as maximum rather than minimum
standards - Up to Architects and educators to approach window
design in more environmentally responsible manner - Need to simulate performance to show long term
energy savings over short term capital costs - i.e. Frame Plus, Energy-10, Solar 5 or Hot2000
can be used to run more accurate comprehensive
simulations for different window solutions - However, simulations are time consuming and can
be expensive to run -- most clients not willing
26In Conclusion
- Windows and skylights that simply meet the
minimum energy standards as set by the Code
account for 7.5 to 19 times the heat losses based
on the same area as a wall or roof. These losses
can be drastically reduced if energy efficient
strategies are responsibly applied. To properly
design energy efficient openings for cold climate
applications is not an easy task. It is,
however, essential. The Building Code provides
us with minimum standards. The National Model
Energy Code asks that we aim higher. Good
conscience says that this is not enough. Tools
exist which help to make this frustrating,
complex task a little bit easier. It is up to us
to use them.