Title: Corporate Design PowerPointBasisTemplates
1Synco livingTrain the TrainerRF
RepeaterAugust 2007
2RF RepeaterBasics
- RF repeaters are used where transmitter and
receiver - are too far apart, or where construction
materials or - appliances inside the house lead to radio signal
- attenuations.General planning rule
- If the radio path exceeds 30 meters or covers
- more than 2 concrete ceilings or floors,
- an RF repeater should be included right from
- the start
- In all other types of plant, RF repeaters are
not - normally required. Nevertheless, should
- radio control range problems occur, a repeater
- can also be fitted at a later stage
- In case of critical radio links, repeaters should
physically be installed between the transmitter
and the receiver wherever possible.
3RF RepeaterBasics
Quantity structure Per system, a maximum of 3 RF
repeaters can be operated in parallel.
1)
Repeater 1
Repeater 2
Repeater 3
1) Direct link
4RF RepeaterBasics
Device list For runtime operation, the RF
repeaters are to be configured in a way that they
only repeat the telegrams from selected devices.
For that purpose, each repeater receives its
device list from the central apartment unit.
During commissioning, the RF repeaters repeat
all telegrams.
1)
2)
Repeater 1
3)
Device list
4)
Repeater 2
5)
Repeater 3
6)
5RF RepeaterBasics
Topology A device can only be assigned to one RF
repeater.
Repeater 1
Repeater 2
Telegram re-repetition over several repeaters
(cascading) is not possible.
Repeater 1
Repeater 2
6RF RepeaterBasics
Topology An RF repeater repeats the following
telegrams sent by the central apartment unit
- Individual telegrams sent to a device on the
repeaters device list e.g. room setpoint
readjustment on room unit (applies only to
this device) - Group telegrams from groups in which at least
one device is contained on its device list
e.g. room temperature setpoint (applies to
all in a room group) - System broadcast telegrams Central unit to all
e.g. manual overriding of valves (applies to
all in the apartment system)
7RF RepeaterMounting
Mounting, basic design RF repeater type ERF910 is
powered via a power pack.
Same housing as roomsensor QAA910
Same base as roomsensor QAA910
Power packfor AC 230 V
Cable without plug
8RF RepeaterBasic Configuration
Procedure
- Activate the RF repeater
Main menu gt Commissioning gt Basic
configuration gt RF repeater gt Repeater x gt
active - Connect the RF repeater
Main menu gt Commissioning gt RF
connections gt RF repeater gt RF Repeater x gt
Connect device - Select from the device list the devices to be
repeatedMain menu gt Commissioning gt Device list
gt Device x gt RF repeater gt Repeater x
The ERF910 repeater is suited for repeating the
telegrams from both Synco 900 and GAMMA wave
devices. Hager products require their own Hager
repeaters.
9RF RepeaterBasic Configuration
The ERF910 repeater can also be used for
repeating the telegrams from devices that require
no functional connection to the central apartment
unit. These devices must be connected to the
central apartment unit, enabling the RF repeater
to obtain its respective device list from the
central apartment unit. Main menu gt
Commissioning gt RF connections gt RF repeater gt
Other RF devices gt Connect device
Handheld transmitter
Device list
Runtime operation
Binding
Commissioning
10RF RepeaterOperation
- Power up LED is lit green for about 2 s
- Non-connected state LED flashes green
- Binded state
- lt 2 hours after pressing the multifunction
button - LED flickers orange during telegram traffic
- gt2 hours after pressing the multifunction button
- No display
11RF RepeaterExercises
- Bind an RF repeater in your groups plant.
- Make the necessary settings so that the telegrams
from all devices in room 1 will be repeated.