Title: understanding EN50131
1understanding EN50131
- risk assessment installer support programme
2Introduction
- Martin Kane ECS
- Martin Halliday - ABI
3where we are now
- Convener of CENELEC working group
- Geoff Tate
4European StandardsIntruder Alarm Systems
- Majority of UK standards to be withdrawn 31st
March 2004 - Parts of BS 4737 to be retained
- Installers can continue to use withdrawn UK
standards until 1st March 2005 - By industry agreement
- EN based systems can be installed subject to
availability of - PD 6662 2004
- Compliant equipment
5BS 4743 Series EN 50131 SeriesDifferences
- Structure of standards
- System/General requirements
- Equipment requirements
- Application guidelines
- System requirements
- Technology independent
- Equipment requirements
- Tests specified
- Facilitates third party type approval
- System design
- Onus placed upon installer
- Majority of change relates to equipment
functionality
6BS 4743 Series EN 50131 SeriesMajor
Differences - General
- System grading scheme
- Equipment classification
- No restrictions on type of interconnections
- Guidance on extent of detection
- By grade
- Notification requirements specified by
- Grade
- Option
7BS 4743 Series EN 50131 SeriesMajor
Differences - Equipment
- Authorisation
- Access levels
- Prevention of setting
- Indication
- Event recording
- Tamper security
- Tamper detection
- Tamper protection
8BS 4743 Series EN 50131 SeriesMajor
Differences Equipment (cont)
- Interconnections
- Monitoring
- Power supplies
- Monitoring
- Standby periods
- Alarm Transmission Systems
- Performance requirements
9BS 4743 Series EN 50131 SeriesMajor
Differences Design
- Design parameters include
- Risk
- Contents
- Building
- Levels of supervision
- Other
- Influences inside supervised premises
- Influences outside supervised premises
- Design to determine
- Extent of detection
- Selection of components
- Grade
- Class
- System grade
10BS 4743 Series EN 50131 SeriesMajor
Differences Installation
- Planning
- System Design Proposal
- Manufactures recommendations
- Competence
- Inspection/Test/Commissioning
- Handover
- Acceptance
- Brought into service
- Certificate of Conformance
11BS 4743 Series EN 50131 SeriesMajor
Differences Maintenance
- Maintenance to be carried out at regular
intervals to agreed schedule - By competent organisation
- Repair
- Agreed response times
- Contact details
- Spares
- To be held on site
- Complex systems
12European Standards Implementation
- 1st March 2004
- UK standards conflicting with EN 50131-1 1997 to
be with drawn - BS 4737 Part 1 IAS
- BS 4737 Part 2 DOD
- BS 4737 Part 4.1 Planning Installation
- BS 4737 Part 4.2 Documentation Records
- BS 6799 Wirefree systems
- DD 244
- BS 7042 High security systems
- DD 242
13European Standards Transition BS to ENs
- Two methodologies adopted
- Scheme described in PD 6662 2004
- Industry agreement
- Installers/Specifiers/Users free to choose
- Systems installed in accordance with existing UK
standards, e.g. BS 4737 for 12 months commencing
1st March - System based on European Standards as described
in PD 6662 2004
14European Standards - Transition PD 6662 2004
- Describes the framework for the installation of
IAS using - European standards where available
- Calls up draft revision of EN 50131-1 1997
- Existing National Standards where ENs not
available - Introduces requirements for routine maintenance
15PD 6662 2004Standards Specified - Systems
- BS EN 50131-1 (Draft revision of 1997 standard)
- DD CLC/TS 50131-7 Application Guidelines
- BS EN 50136 Alarm Transmission Systems
- Part 1.1 General requirements
- Part 1.2 Requirements for dedicated path systems
- Part 1.3 Requirements for Digital Communicators
- Part 1.4 Requirements for Voice Communicators
- BS 4737 Part 4.2 Maintenance Records
- Clause 3.3 Corrective maintenance
- 3.3.1 Emergency service to be available at all
times - 3.3.2 Engineer to attend within 4 hours
- DD 243 2002
16PD 6662 2004Standards Specified - Equipment
- BS EN 50136 Power supplies
- BS EN 50136 Alarm Transmission Systems
- Part 2.1 General requirements for ATS equipment
- Part 2.2 Requirements for dedicated path systems
- Part 2.3 Requirements for Digital Communicators
- Part 2.4 Requirements for Voice Communicators
- BS 4737
- Part 3 Section 3 General requirements for
components - Part 1 clause 3.2.1 Housings (CIE)
- Part 1 clause 8 Warning devices
- Except 8.2.6 Environment
17PD 6662 2004 Equipment
- Equipment for which EN is specified
- Equipment to be marked in accordance with EN
50131-1 draft revision document clause 15 - Equipment for which no EN is specified
- Equipment to comply with relevant clause of BS
4737 Section 3 and/or relevant Annex of PD - Equipment must satisfy requirements of PD
- Installer to provide evidence of suitability,
Grade Class
18PD 6662 2004 Maintenance
- Specifies requirements for
- Preventative maintenance
- Specifies inspection test requirements
- Frequency of preventative maintenance
- Grade 1 1 site inspection PA
- Grades 2 3 2 site inspections PA
- OR
- 1 site inspection 1
remote check PA - Grade 4 2 site inspections PA
- Grade 2 Option X 1 site inspection PA
- Remote system checks
19PD 6662 2004 Alarm Transmission Systems
- Specifies requirements for indication of line
faults on dual path signalling systems - Introduces additional notification option in
Grade 2 - Option to install Grade 2 system without ATS
- Must comply with all other requirements for Grade
2
20PD 6662 2004Identity Cards
- Specifies requirements additional to those
previously included in BS 4737 Part 4.1 clause
3.3 - ID cards only issued to persons screened in
accordance with BS 7858 - Cards to be carried during working hours
- Cards to be withdrawn when employment ceases
- Records of cards to be maintained to indicate
status - Invalid/obsolete cards to be destroyed
21PD 6662 2004National Forewords
- EN 50131-1 1997 System Requirements
- Existing national foreword relating to battery
standby periods retained - Applies to draft revision of EN 50131-1 1997
included in PD 6662 2004 to power supplies - DD CLC/TS 50131-7 Application Guidelines
- Requirements for qualifications not applicable in
UK for time being
22Status of Drafts for Development
- DD 243 2002 Installation configuration of IAS
designed to generate confirmed alarm conditions - Included in PD 6662 2004 scheme
- DD 245 Management of false alarms
- Not included in PD 6662 2004
- Called up in ACPO scheme alarms policy
23European StandardsSummary
- Introduction dependent upon availability of
- Equipment
- PD 6662 2004
- Dual running period until March 2005
- Use existing BS standards or scheme described in
PD 6662 - Main changes relate to equipment
- System design requirements place more
responsibility on installers - Equipment standards provide basis for third party
type approval - Grading scheme simplifies specification
24EN 50131-1an Insurance View
25Current standards are out of date!
- New standards are needed
- to keep up with new technologies.
- to improve reliability of systems.
- to help reduce false alarms.
26What will the new standard bring?
- Problems!
- Training issues for installers and insurers.
- Better designed systems.
- Systems that are graded to meet the needs of the
risk.
27Who will decide on the Grade required?
- Insurer may advise their client.
- BUT.
- The installer must carry out a risk assessment
and make a decision! - No different to BS 4737 except that is has to be
written down.
28System grades in EN 50131 - 1
- Grade 1 - Lower than BS4737
- Bells only signalling
- No tamper detection on detectors
- Unlikely to be acceptable to insurers where an
alarm system is required for insurance purposes
29System grades in EN 50131 - 1
- Grade 2 -
- Remote signalling
- Some tamper detection required,
- but not detector orientation adjustment
- Probably acceptable to insurers in low risk
situations
30Types of risk where insurers might want a grade 2
system
- Offices with low value of computers
- Stationery retailers (ex computers).
- Carpet retailers (ex oriental).
- Manicurists health / beauty shops
- Bakers, florists, fishmongers.
31System grades in EN 50131 - 1
- Grade 2X -
- Introduced in PD 6662 to allow Grade 2 systems to
be installed without remote signalling. - Probably acceptable to insurers for low domestic
risks - Unlikely to be acceptable for commercial risks.
32System grades in EN 50131 - 1
- Grade 3
- Roughly equates to existing systems in commercial
premises. - BUT includes anti-masking of detectors.
- Probably required by most insurers for all but
low commercial risks. - Possibly high net worth domestic.
33Types of risk where insurers might want a Grade 3
system
- Offices -modest computer values.
- Motor garages
- Warehouses - bulky low value items
- Public houses.
- Convenience stores (without ATMs).
- Builders merchants (? electric tools).
- Small industrial units (average cts.)
34System grades in EN 50131 - 1
- Grade 4 -
- Equates to high security systems.
- Equipment not yet available.
- For a high security system use available Grade 4
components, and Grade 3 for the remainder.
35Types of risk where insurers might want a Grade 4
system
- Very high risk premises
- Computer warehouses
- Print design (high computer values)
- Spirit and cigarette wholesalers and bonds
- Premises handling large amounts of cash
36Signalling
- Digital communicators are unlikely to be
acceptable to insurers. - For Grade 3 systems most insurers will require
dual path signalling. - Installers quoting for a Grade 2 or 3 system
should always give a dual path option! - For Grade 4 (or high risk Grade 3) always quote
for dual signalling.
37Help!
- Its good to talk!
- Talk to insurance surveyor
- Ask insurers or insurance broker.
- Consult with inspectorates and trade bodies.
38Conclusion!
- It aint difficult,... its different!
- If in doubt, ASK!
- Lets all work together to give the customer a
good system and. - Reduce false alarms!
39EN 50131-1a manufacturers view
- Presented by
- Dave Armstrong or Steve Thomas
- of Cooper Security Limited
40System Components
- Typical system components on which the new
standard will have an impact - Control Panels
- Ancillary Control Equipment
- Alarm Transmission Equipment
- Commercial Movement Detectors
41System Grades
- The manufacturers will indicate the highest grade
for which each system component is suitable. - The lowest graded component will decide the whole
system grade.
42Environmental Classes
- When choosing a system component always ensure
that it has been specified by the manufacturer to
operate in the correct environment.
43Product Marking
- Only products where the standard has been
published and are listed in PD6662 2004 will
require to have product marking. - However manufacturers should state that the
component is suitable for use in a specific grade
and environmental class.
44Product Labeling
- Each product must carry a label or a code number.
- Each label must be Legible, Durable and
Unambiguous. - Each instruction manual or guide provided with
each component shall include the following
statement - This product is suitable for use in systems
designed to comply withPD66622004 at grade x
and environmental class y.
45Typical Wiring Configurations
- Acceptable Zone Configuration
- Grade 1 Installations
Alarm Contact
Alarm Circuit
Tamper Contact
Tamper Circuit
Zone by Zone or Global Tamper
Traditional Closed Circuit Zone Wiring
46Typical Configuration
- Acceptable Zone Configuration
- For Grade 2 Option X Grade 2 Installations
47Revised Detector Operation
- For Grade 3 The Movement detectors shall have a
detector masking facility.
48Typical Configuration
- Acceptable Zone Configuration
- For Grade 3 Installations
49Typical Configuration
- Acceptable Zone Configuration
- New Generation for Grade 3 Installations
50Typical Configurations
- Zone Configuration Acceptable
- For Grade 4 Installations
- Individually addressable systems shall meet the
substitution of a system component requirements.
51Wire-free Interconnections
- Wire-free systems are defined in the
interconnections section of the standard and must
conform to the same requirements as those for
hardwired systems.
52Revised System Functionality
53Remote System Checks
- Applies to Grades 2 3 but not Grade 2 (Option X)
54Impact on Power Supplies
- The installed battery standby time should comply
with PD6662 2004. - PD6662 Grade1 Grade 2 Grade 3 Grade 4
- 12h 12h
24h 24h - The power supply design and construction must
also comply with EN 50131-6. -
55Types of ATE
- Various types of Alarm Transmission Equipment can
be used but are now grade dependent.
- More Communications Outputs -Channels will
require!
56System Event Logs
- Event recording at the CIE Control panel is
mandatory on Grades 2, 3 4 - The Event log must be protected against
accidental or deliberate deletion.
57EN50131redcare view
- Iain Jolley - National Insurance Sector Manager
always there
58The impact of EN Standards on monitored systems
59Upon the introduction of the EN Standards, all
signalling devices including digital
communicators MUST BE MONITORED either as a
single signalling path system or as part of a
DUAL PATH SIGNALLING SYSTEM.
The frequency of that monitoring will depend on
the level of European Grade ascertained from a
Risk Assessment of the premises
60 Monitoring frequency and EN requirements
To comply with Grade 2 - EN Standard The primary
path must be checked / report fault within25
hours The secondary path must be checked /
report in 25 hours
To comply with Grade 3 - EN Standard The primary
path must be checked / report fault within 5
hours The secondary path must be checked / report
in 25 hours
To comply with Grade 4 - EN Standard The primary
path must be checked / report fault within 3
minutes The secondary path must be checked /
report in 5 hours
redcares primary path reports within 45 seconds
and the secondary path reports within 3 minutes
61Alarm Transmission systems and compliance with
European Standards
62EN 50136 - 1 - 1 1998
Alarm transmission system performance
criteria The security classification of an alarm
transmission system is defined as the combination
of five parameters D transmission time
speed of delivery M maximum acceptable
transmission time T frequency of checks to
identify/report faults S substitution
security I information security Within each
of these parameters there are difference levels
of acceptance. The grade the signalling can be
used for will depend on the level achieved
63Compliance with Parameters
- Parameter D speed of delivery
redcare
- Highest level required D4 - under 10 seconds
D4 - Parameter M - maximum acceptable delivery time
- Highest level for maximum acceptable time M4
-under 20 seconds M4 - Parameter T frequency of checks to
identify/report faults - T1 (32 DAYS) to T6 (20 seconds) T5 primary
path T4 secondary path - Parameter S substitution security/detection
- S0 (no measures) to S2 (stringent measures eg.
encryption) S2 - Parameter I information protection
- I0 (no measures) to I3 (measures to prevent
unauthorised reading and modification of
information transmitted)
I3
64 EN 50136 - 1 - 3 1998 Requirements for systems
with Digital Communicators using the PSTN
Page 4 - para 5 of EN 50136 - 1 - 3 states
- Alarm transmission systems within the scope of
this standard shall comply with the requirements
in EN 50136 - 1 - 1 (There are no exclusions here
from the parameters of D,M, T,S and I, which
are the requirements of EN 50136 - 1 - 1 Digital
Communicators must therefore be monitored and be
able to report faults within the time frames
required by the appropriate grade
65Grade 4 requirements for a dual path signalling
system
primary signalling path
secondary signalling path
66redcare exceeds the highest requirements of all
the European grades from 1 to 4
redcare can be specified to protect ALL levels of
grade at no extra cost
67Why will ALL signalling providers have to now
monitor both paths ?
- To report the loss of both signalling paths To
meet the requirements for confirmation and police
response NOW - To comply with Table 3 - Fault reporting time in
EN 50136-1-11998 and Tables 10 11 of EN
50131-11997 - (Revision)
68Indication to Control Indicating Equipment (CIE)
- Revision in EN50131-1 1997 Table 8 deals with
indications and includes fault conditions (see
Table 1) as mandatory for all grades of system - Table 1- Faults - includes Alarm Transmission
System(s) if a system is required to have two
signalling paths, a fault in either path has to
be indicated - Prevention of Setting setting of an I HAS, or
part thereof shall be prevented when one or more
of the conditions shown in Table 4 is present - Table 4 Prevention of setting includes Alarm
Transmission System fault optional for grade 1
mandatory for grades 2 to 4
69 redcare has been thoroughly independently tested
against the EN Standards by the BRE and has
achieved Grade 4 status.
Transparency to industry is essential
Independent testing is the only way to verify
compliance to specific grades
70leading the way in technology
- Way ahead in continuous monitoring
- If primary path compromised, polling of secondary
path commences immediately at any time - in
both set and unset condition - Loss of secondary path reported within 3 minutes
- No additional line required to avoid disruption
of business when landline path is being polled
redcare is non dialling technology - No extra cost when either the landline or GSM
path is being polled redcare is non dialling
technology - Way ahead in indication to CIE
- Loss of either signalling path to CIE
- Configurable on basic GSM stu no extender board
required no extra cost - Way ahead in meeting the requirements of UK
Insurers
71leading the way in customer support risk
assessment programme
72leading the way in customer support
- Events like these
- Sponsors of SSAIB EN50131 training seminars -
running until December 04 designed to be the
next level of information for the installer
covering in more detail how you need to change in
order to become compliant with the new standards - redcare registered installers will qualify for a
10 discount by giving the SAAIB their user ID
and company name from redcares online services
(risk assessment, fault reporting etc) when they
register
73EN50131-1
- Ashley Carmichael
- Specialised Security Systems Ltd
74Why me
- Been in the Industry for 24 Years
- Have Installed and will give telephone support
practical training to our engineers. - Heavily involved with BSIA and NSI
- Thanks to Martin Halliday who proposed me I now
Chairman of BSI Committee GW1-2 - Currently reviewing DD243
- Optimist by nature. Arranged 5 review meetings
ending in Mid May
75Period of Dual Running12 months?
- Thanks to Geoff Tait he given you the Overall
view of the European Standards. - May aim is discuss how it will affect the Alarm
Installer, the end users, and the Insurer. - If you start planning now, you wont see the seam
- No Rocket Science. - Based on Two Standards
- PD6662 and DD243 Both been out before.
- DD 243 will and should be known to you all
- PD6662 is a Highbred of Old BS and EN50131
76Cannot purchase either!
- Simple BS4737 Withdrawn not forgotten.
- Duel Running 12 Months of Adjustment.
- Industry knows contents of PD6662
- Presenters Manufacturers Inspectors
- DD243 2002 is well known to the Industry but I
made reference to IMMEDIATE REVIEW - How do we cope
- Guess the changes to DD243 ? Dangerous
- Committee of 9 Industry experts Chairman
77Scope of DD243 has not changed
- The Main Plank of the Scope was to include
recommendations intended to minimize the
likelihood of false alarms. - Alterations cannot be drastic so we can plan.
- Can I purchase equipment Probably not yet.
- Manufacturers have been reluctant to produce the
Kit for a Dying Standard, hence New PD6662-2004
78What's was the Problem
- The reason for delay was that it had always been
agreed in Europe, that until a complete suite of
European Standards, were published there would be
no pressure to change. - With this knowledge no one pushed the industry to
complete the EN50131 suite - Until Last Year when someone in Brussels turned
the Euro Standards on it head.
79Problem ? No, an Opportunity
- Insurance companies want to know that when
specifying a BSIA, NACOSS, or an SSAIB companies
the specification is fit for the purpose. Most
reputable companies have done this or years.
Seamless transition - Under BS4737 3 Components a System.
- Regrettably some approved installers could not
care less, providing they won the job. - PD6662 will be their Waterloo
80An Opportunity
- An opportunity to have a level Playing field.
- Opportunities dont come cheep as Insurance
Companies now demand RISK ASSESMENT - You and I call it a commonsense approach.
- If you haven't a Risk System, BT Red have.
- Its an opportunity to be a Professional Design,
Installation and Service Company - Its an opportunity and sell the benefits of an
Integrated Security Solution - Not Alarms
81An Opportunity
- An opportunity to charge a proper rate.
- An opportunity to make a decent Profit for all
the 80 hour weeks you have worked. - An opportunity to make a similar return made by
the Industry leaders on TURNOVER 18. - A Proper return is no automatic right, look at
the Industry leaders, its been achieved by a
lot of professionalism.
82What's required
- An Understanding of What in PD6662
- Annex F a pre-publication copy of the
EN50131-1 16 Feb 2004. - And EN50131- 3 DDTS 6 7 DDTS
- A graded Approach, ABI will cover this area
- 1 Low Risk
- 2X Low to Medium
- 2 Low to Medium
- 3 Medium to High
- 4 High Risk
83What else?
- A New and structured approach to the survey
- A Question, Answer and recording approach
- Dont accept any liability for value, few of us
are trained to value, so record all information
as part of the quotation - You need to understand risk
- You need to know the area risk
- You need to know Police response times
- You must learn new skills or redefine those you
have used for years.
84Risk
- When Surveying, specify how you quantify what is
risk - My approach is to ensure an intruder cannot
arrive in an area of SIGNIFICEANT value without a
confirmed alarm being generated. - So how does that statement work
- I inform my customers that my companies approach
is, anything that exceeds 1000 on the first
loss is of significant value. - This means that intrusion in an area of
significant value has to generate a confirmed
Alarm
85Grading
- If you fail to catalogue the premises correctly
you will expose your company to liability. - If having obtained the information and fail to
adequately cover the premised you will again
expose your company. - If you are Hell bent on winning jobs by price you
will run the risk of under specifying there by
exposing your company to a claims. - The Surveyor needs to understand the PD6662
grading system dont assume, if in doubt ask
the Insurers.
86Tease out the information
- If Customers hold information back or areas of a
site have no value, specify these fact in your
specification, you will have no risk. - Dont Forget the item of the lowest grade
installed is the grade of the system. - Equipment will be graded by the Manufacturer
- The Surveyor must have an understanding of the
hardware, communication and panel programming. - If the Surveyor gets it wrong and you install a
grade 2 system and need to upgrade to a grade 3
it will be an expensive mistake. -
87Maintenance records
- Same as Old BS4737 - Cant sell the Helicopter!
- Always available, 4 Hour response - BUT
- Grade 1 Annually
- Grade 2X Annually
- Grade 2 2 Visits per Year or 1 Visit and
- Grade 3 1 Remote system check
- Grade 4 2 Visits per Year
88Remote Systems Checks
- Written agreement
- Details of checks
- Where carried out from
- Remote checks should not commence until
communication - Established by CIE or
- By manual command at CIE or
- By CIE following an initiating call from remote
location
89Remote Systems Checks
- ARC to be informed
- Before remote checks commence
- When completed
- Remote checks not to generate false alarms
- If IAS is set, remote checks must not compromise
operation - Detailed records to be maintained
- Problems to be reported to user and remedial
action agreed
90Remote Systems Checks
- Checks
- a review of the event log, for successful setting
and unsetting - a check on any zones that are on soak test
- a check on any zones that are disabled/isolated
- a check to ensure that the time and date of the
CIE clock are correct - a check on the normal and standby power supplies,
for correct functioning (see note)
91Remote Systems Checks
- a check that all voltage and current levels are
within acceptable tolerances - a check on the recent activity of all detectors
which would be expected to operate during the
normal occupation of the building. There should
be a written agreement with the client that
details those detectors that will operate during
the normal occupation of the supervised premises
92Remote Systems Checks
- a check for the correct operation of any alarm
transmission system, in conjunction with the
alarm receiving centre. Where multiple signaling
is installed, all signaling paths should be
checked - A check on the normal and standby power supplies
of all alarm transmission equipment for correct
functioning (see note)
93Qualification
- National foreword included in BSEN 50131-72004
stating recommendation for qualifications are set
aside. - Not for long, EN501-7 Application Guidelines is a
DDTS and will be reviewed in two years. - From today's presentations you will realise that
without a large input of Professionalism many
Companies will not survive.
94Qualification Time is running out
- The BSIA is working with SITO the National
Occupational Standards Setting Body to ensure
that the standards are incorporated into
appropriate qualifications offered by such
institutes such as City Guilds. - SIA have introduced qualification into Manned
guarding - Cost of covering all operators has
been overwhelming. - We must not leave it until the Last Minute
- Fast track, NVQs, City Guild 185-2
95Closing Thoughts Give me a date
- We waiting for new Panels that are European 50131
with DD243, Many Manufacturers are close to
having developed hardware but the software cannot
be finalised until the contents of DD234 2004 is
known. I expect to be installing PD6662 Systems
by January 2005.
96NEW PD 6662 SCHEME
- Tony Weeks
- NSI Technical Manager
97PD 6662 2004
- Expect Publication in April / May
- Then Parallel Running with BS Intruder Alarms
- Then Phase-Out of BS Intruder Alarms
98PD 6662 Scheme
- System Standards
- Component Standards
- Marking, Identification and Classification
- Identity Cards
- Claims of Compliance
- Technical Annexes
99System Standards
- Draft EN 50131-1 System Requirements
- DD CLC/TS 50131-7 Application Guidelines
- BS EN 50136-1 series ATS
- PD 6662 2004 Annex D Maintenance
- DD 243 2002 Alarm Confirmation
100Component Standards
- BS 4737 Part 3 Sections 3.0 to 3.14
- BS EN 50131-6 Power Supplies
- BS EN 50136-2 series ATE
- PD 6662 2004 Annexes A, B, C and E
- Hold-Up Devices
- Control and Indicating Equipment
- Warning Devices
- ATS, Standby Power, Restore
101Overview of changes
- BUSINESS PROCESSES UNCHANGED
- Survey, Quote, Install, Commission, etc
- INSTALLING SIMILAR EQUIPMENT
- Detectors, CIE, PSUs, WDs
- MAIN CHANGES IN STANDARDS
- Aim of this short presentation
- DETAILED CHANGES IN STANDARDS
- Many of these unfortunately!!
102Risk Assessment
- PREMISES SURVEY
- Need Better Documentation
- Capture Survey Details
- Record Name
- CHOOSE SECURITY GRADE
- Insurer May Specify Grade OR
- Decide in Consultation with Customer
103Security Grading
- GRADE 1 Low Risk
- Little knowledge, Limited tools
- GRADE 2 Low to Medium Risk
- Limited knowledge, General tools/equipment
- GRADE 3 Medium to High Risk
- Conversant, Comprehensive tools/equipment
- GRADE 4 High Risk
- Detailed planning, Full range of equipment
104Environmental Class
- CLASS I Indoor
- 5 oC to 40 oC 75 Relative Humidity (RH)
- CLASS II Indoor General
- -10 oC to 40 oC 75 RH
- CLASS III Outdoor Sheltered
- -25 oC to 50 oC 75 RH (30 days 85 to 95)
- CLASS IV Outdoor General
- -25 oC to 60 oC 75 RH (30 days 85 to 95)
105Access Levels
- Level 1
- Access by any person
- Level 2
- User access (e.g. by an operator)
- Level 3 Requires Level 2 Permission
- User access (e.g. by alarm company personnel)
- Level 4 Requires Level 23 Permission
- User access (e.g. by the manufacturer of the
equipment)
106Authorisation Codes
107Setting and unsetting
- BASIC CONCEPTS SIMILAR TO DD 243
- UNSETTING
- 45 SECONDS MAXIMUM
- NO REMOTE NOTIFICATION FOR 30 SECONDS
- SETTING
- PREVENTION OF SETTING
- OVERRIDING OF PREVENTION
- DD 243 STILL APPLIES IF POLICE CALLING
108Access levels to restore
109Movement Detectors
- GRADE 3
- Means to Detect Masking
- GRADE 4
- Means to Detect Masking
- Means to Detect Range Reduction
- 50 Reduction of Range on the Central Axis
110Notification by WD
- CAN SUPPRESS OPERATION OF WD
- E.g. Activation of Hold-Up Device
- CAN DELAY OPERATION OF WD
- Up to 10 minutes, but only if WD ATS
- CAN SUPPRESS WD AFTER DELAY
- If Notification Confirmed by ARC during Delay
Period - OPERATION OF WDs
- 90 Seconds Minimum
- 15 Minutes Maximum !
111Notification Options
112ATS Performance Criteria
113Duration of Standby Power
114Preventive Maintenance
115Summary of Key Issues
- risk assessment
- grading
- marking of components
- notification
- indications
- remote maintenance
- surviving new terminology!!!
116EN50131ACPO View
- Ken Meanwell Staff Officer
- Security Systems Group
- ACPO Crime Prevention Initiatives Group
117Background
- Member of ACPO Intruder Alarm Group - January
1995 - Became Secretary to Group - December 2002
- Full-time Staff Officer employed by ACPO CPI Ltd
- January 2004.
118Secured By Design
- SBD is a police initiative to encourage the
building industry to adopt Crime Prevention
measures in development and design to assist in
reducing the opportunity for crime and the fear
of crime creating a safer and more secure
environment
119Secured by Design
- Owned and managed by ACPO CPI
- Supported by the Scottish Executive and the Home
Office - Administered by approx. 400 ALOs and CPOs in
the UK
and
and
and
120ACPO European Standards
- ACPO welcome the introduction of European
Standards that will ensure systems are installed
by qualified engineers at a higher standard.
121Advantages
- Thorough risk assessments
- Qualified Engineers
- High quality reliable systems
122Concerns
- Graded systems
- Maintenance visits
- Remote checks
123Opportunities
- Educate users
- Examine causes of false alarms
- Improve record keeping
124Police response levels
- Level 1 - Immediate
- Level 2 - Routine
- Level 3 - No Response
- All dependent upon operational police
requirements of Force
125Attendance Times
- Urban - 10 minutes
- Rural - 20 minutes
126ACPO Policy The future
- To be reviewed in 2004
- Ensure unified approach by Forces
- Introduce combined ACPO Industry Strategy
- REDUCE FALSE CALLS
127QA
128Thank you.
- For more information on EN50131 and risk
assessment register on www.redcare.bt.com/riskasse
ssment