Water Based Sprinkler Systems - PowerPoint PPT Presentation

1 / 28
About This Presentation
Title:

Water Based Sprinkler Systems

Description:

Water Based Sprinkler Systems 2 major different types of water sprinkler systems Wet pipe system Dry pipe system Wet Pipe System Water is in all piping As sprinkler ... – PowerPoint PPT presentation

Number of Views:215
Avg rating:3.0/5.0
Slides: 29
Provided by: IUP
Category:

less

Transcript and Presenter's Notes

Title: Water Based Sprinkler Systems


1
Water Based Sprinkler Systems
  • 2 major different types of water sprinkler
    systems
  • Wet pipe system
  • Dry pipe system

2
Wet Pipe System
  • Water is in all piping
  • As sprinkler heads open, water is discharged

3
Wet Pipe Clapper Valve
4
Dry Pipe System
  • Air is in system from above the clapper valve to
    to sprinkler head.
  • As sprinkler heads open, air escapes then water
    is discharged.

5
Dry Pipe Clapper Valve
6
Pre-action Systems
  • Sensors in the area of the fire are activated.
  • The water valve is then open.
  • And water flows to the area.

7
Deluge System
  • All sprinklers are activated at once when a
    detecting device is activated.

8
Typical Wet Pipe System
  • In a typical wet pipe system, water enters the
    building at a determined pressure.

9
Backflow Preventers
  • Backflow preventers are placed before the riser.
  • If there are significant decreases in water
    pressure, the backflow preventers prevent water
    from being sucked out of the sprinkler system.
  • These backflow preventers must be checked by
    certified plumbers at least annually (EPA
    requirements).

10
Back Flow Preventer
11
Sprinkler Riser
  • The water then flows to the riser.
  • At the riser, a series of valves and gauges,
    maintain the water in the system.

12
OS Y Valve
  • Outside stem and yoke valve.
  • The water first passes through an outside stem
    and yoke valve. (OS Y valve).
  • To close this valve, the handle must be rotated
    out.

13
OS Y Valve
14
OS Y Valve
15
OS Y Valve Example
16
Tamper Switches
  • In some instances, there are tamper switches on
    these valves.
  • If they are turned, the monitoring service will
    receive a trouble alarm.
  • This valve should be alarmed and chained open.

17
Tamper Switches
18
Main Water Clapper
  • The water then enters the main section of the
    riser.
  • There is a main water clapper that sits at the
    base of the riser.
  • If there is major water pressure loss, the water
    will stay in the sprinkler system.

19
Water Gauges
  • Water pressure gauges are found above and below
    the water clapper.
  • This will alert the person to pressure problems
    in the water lines.
  • In a wet pipe system, both pressure gauges may
    read the same.
  • Check the design spcifications!!

20
Water Flow Alarm
  • These are found above the main clapper.
  • If there is a flow of water, the alarms will be
    activated.

21
2" Main Drain
  • A two inch pipe comes out of the main riser area
    to a drain.
  • This two inch line is used for testing purposes.
  • Closing the water valve above the 2 inch line
    then opening the 2 inch water line tests water
    coming in from the municipal service.

22
Riser
  • The next section of pipe is the riser pipe
    itself.
  • The riser pipe goes up to the sprinkler branch
    lines in the building.

23
Branch Lines
  • The branch lines are typically smaller than the
    riser.
  • This decrease in the diameter of the branch lines
    increase the pressure in the lines.

24
Inspectors Test
  • Located at the furthest point from the riser
  • Simulates the opening of one sprinkler head

25
Wet Pipe Sprinkler System Inspections
  • Inspector's test
  • 2 inch main drain test
  • Water flow alarm test

26
Inspectors Test
  • Signifies that one sprinkler head at the
    sprinkler head furthest from the riser has been
    opened.
  • This verifies that adequate pressure and flow can
    be achieved.

27
Water Flow Alarm
  • "Trip test.
  • At the inspector's test valve, open the
    inspectors test valve.
  • A slight decrease in pressure should be observed.
  • The water flow alarm should be activated and the
    fire department should receive a signal that the
    fire alarm has been activated.
  • There should be a short time delay from when the
    water flows and the alarm is activated.
  • The delay should not be any greater than 90
    seconds.
  • Close the inspectors valve and reset the system.

28
Two Inch Main Drain Test
  • The purpose of the two inch drain is to determine
    if there is adequate water supply to the system.
  • Open the two inch drain fully, check and record
    the water pressure.
  • There should not be a significant drop in water
    pressure when the two inch drain is open.
  • If there is, there may be a blockage in the
    supply line.
  • Close the two inch drain and record the
    pressures.
  • The pressure should return to approximately
    normal.
Write a Comment
User Comments (0)
About PowerShow.com