Title: Modern Refrigeration and
1Modern Refrigeration and Air Conditioning
Althouse Turnquist Bracciano
PowerPoint Presentation by Associated
Technical Authors
PublisherThe Goodheart-Willcox Company,
Inc.Tinley Park, Illinois
2Chapter 12
Servicing and Installing Small Hermetic Systems
3Learning Objectives
- Select proper tools and instruments needed for
installing or servicing domestic and small
commercial systems. - List supplies needed on a typical installation or
service call. - Service internal and external mechanisms using
the proper tools and materials. - Locate areas causing noise and make necessary
adjustments to the system.
4Learning Objectives
- Recognize trouble signals.
- List common external service operations.
- Start a stuck compressor.
- Demonstrate proper use of piercing valves.
- Check for restrictions in the system.
- Troubleshoot common refrigeration problems.
5Learning Objectives
- Use the proper methods and equipment for checking
electrical systems of refrigerators and freezers. - Follow approved safety procedures.
6Refrigerants
- R-12 was the primary refrigerant used in domestic
refrigerators and freezers for most of the
twentieth century. - As of 1996, R-12 is no longer manufactured.
- R-134a is now the primary refrigerant used in
domestic equipment. However, units with R-12 will
be operational for years to come and will require
repair.
7Instruments, Tools and Supplies
12.1.1
- Instruments needed for refrigeration service
work - Pressure recorder.
- Temperature recorder.
- Off-On recorder.
- Watt recorder.
- Electronic sound tracer.
- Electronic leak detector.
- Compound gauge.
- Pressure gauge.
8Instruments, Tools and Suppliescontinued
12..1.1
- Instruments needed for refrigeration service
work - Thermometer with a range of 20ºF to 212ºF
(29ºC to 100ºC). - Voltmeter.
- Ammeter.
- Ohmmeter.
- Test light (incandescent, 120V, 100W).
9Refrigerant Tools
12..1.2
- High-vacuum pump.
- Recovery/recycling unit.
- Service cylinders for R-12, R-22, R-502, and
R-134a. - Purging line (1/4" diameter by 15', equipped with
hand shut-off needle valve and check valve). - Capillary tube cleaner.
- Capillary tube sizing kit.
- Soldering-brazing torch (LP fuel-air,
acetylene-air, or oxyacetylene).
10Refrigerant Toolscontinued
12..1.2
- Hand vacuum cleaner.
- Gauge manifold.
- Process tube adaptors.
- Bending springs.
11Wrenches
12..1.2
- Set of 3/8" drive sockets (12 point, 7/16" to
1"), with 3/8" drive torque handle, speed handle,
swivel handle, and T-handle. - Adjustable open-end wrenches (8").
- Set of Allen setscrew wrenches.
- Refrigeration ratchet wrench3/16", 7/32", and
1/4"with square openings. - Set of 15º open-end wrenches (1/2", 3/4", 7/8",
and 1"). - Box-end wrench (1/2").
- T-socket wrench (1/2").
12More Tools
12..1.2
- Pliers
- Combination (6").
- Wire cutter.
- Slim nose.
- Hammers
- Claw hammer.
- Rubber mallet.
13Tubing Tools
12..1.2
- Bending springs for 1/4", 3/8", and 1/2" OD
tubing. - Flaring tool (3/16" to 1/2" capacity).
- Tubing cutter.
- Pinch-off tool.
- Swaging tool.
14Screwdrivers
12..1.2
- Standard screwdrivers (3", 6", and 8") with
insulated handles. - Phillips screwdrivers (3", 6", and 8") with
insulated handles.
15Supplies
12..1.3
- Wire solders (60/40 and 95/5).
- Soldering flux.
- Silver brazing wire (3060 silver no cadmium).
- Phosphorous-copper alloy wire.
- Brazing flux.
- Steel wool.
- Medium-grade sandpaper.
- Plastic tape.
- Refrigerant recovery unit.
16Suppliescontinued
12..1.3
- Disposable cylinders of refrigerant.
- Coils of soft copper tubing (1/4", 5/16", 3/8",
and 1/2"). - Copper pipe (as needed).
- Capillary tubing.
- Filter-drier cartridges.
- Refrigerant oil (150 and 300 viscosity).
- Refrigerant oil can (spout type).
- Cleaning cloths.
17Suppliescontinued
12..1.3
- Relays.
- Capacitors.
- Motor controls.
- Refrigerant controls.
- Overload protectors.
- Light switches.
- Sealing compounds.
- Driers (flared and soldered fittings).
- Filter-driers (flared and soldered fittings).
18Suppliescontinued
12..1.3
- Sight glasses (flared and soldered fittings).
- Flared fittings (SAEall sizes and shapes).
- Piercing valves and valve adaptors.
- Valve cores.
19Installing Refrigeratorsand Freezers
12.2
- Correct installation ensures proper operation of
a refrigerator or freezer. - Units are shipped with full written instructions.
20Uncrating aRefrigerator or Freezer
12.2.1
- Carefully follow the directions in the crate.
- Areas of the cabinet may be easily damaged in
moving or uncrating. They include - BottomCondensing unit.
- BackCondenser may be damaged.
- DoorMay be forced out of alignment or buckled.
- Compressor domes may be shipped with either
removable shipping bolts or loosened dome
shipping bolts.
21Uncrating aRefrigerator or Freezer
12.2.1
A hand-truck may be used to aid in moving the
appliance.
22Properly Positioning a Refrigerator-Freezer
12.2.2
- Do not locate refrigerator-freezer in direct
sunlight or near an oven, warm air register, or
other heat source. - The room should be large enough to provide proper
air flow to cool the condenser.
23Electrical Supply
12.2.3
- Check the electrical rating on the appliance
against the electrical supply provided at the
wall outlet. - There should be a separate circuit from the fuse
or circuit breaker box to the refrigerator-freezer
outlet. - Do not use an extension cord between the power
cord and wall outlet resulting voltage may be
too low. - Voltage at refrigerator outlet can be checked
with a voltmeter or multimeter.
24Electrical Supply
12.2.3
25Electrical Supplycontinued
12.2.3
- If the voltage at the refrigerator outlet drops
more than 10V when starting, the wiring in the
circuit is not heavy enough. A flicker in the
lights at the moment of starting is a sign of
poor electrical supply. - If the wall outlet has a three-prong socket and
the unit has a matching power cord plug, there is
grounding. If not, a wire must be attached
between a metal part of the cabinet and a good
ground, such as a water pipe.
26Electrical Supplycontinued
12.2.3
- CautionAlways check for proper grounding in the
outlet box supplying current to the unit being
serviced. Take a voltmeter reading from the
live wall receptacle connection to the
receptacle ground connection. A full voltage
reading indicates the outlet is properly grounded.
27Providing Proper Ventilation
12.2.4
- In installations where there is inadequate space
for air movement, cooling fans must be used. - Units with a shroud covering the condenser must
have air circulation at the bottom, back, and
top. - Units that use the outside shell as the condenser
surface must have at least 2" (51mm) of space
between the surrounding cabinet and surfaces. - A spirit level should be used during installation
to ensure correct leveling.
28Providing Proper Ventilationcontinued
12.2.4
Front supports are usually adjustable.
29Starting a Refrigerator-Freezer
12.2.5
- Test the wall outlet with voltmeter to determine
presence of electrical power. - Put the temperature control in the off position.
- Connect the electrical cord to the wall outlet.
- Test the unit for operation prior to moving it
into position. - Set the temperature control at the middle range.
After a few hours of operation, check the
thermometer in the refrigerator compartment.
Adjust the temperature control setting as needed.
30Starting a Refrigerator-Freezer
12.2.5
- If the unit does not start, check that the
electrical circuit is in good condition. Next,
check for mechanical trouble. Open and close the
doors to make sure the interior lights are
functioning properly. - Note If a refrigerator-freezer using a capillary
tube system refrigerant is stopped and then
started immediately, it may fail to operate.
Disconnect the refrigerator for a few minutes.
Allow the refrigerant pressure time to balance
between the high and the low sides. Then, start
the system again.
31Installing an Ice Cube Maker
12.2.6
- Many domestic refrigerators have automatic ice
makers. These are connected to a cold water line
by a coil of 1/4" copper or plastic tubing. - Prior to putting refrigerator in place, run the
copper tubing to the nearest cold water line.
(Cabinet partitions or the floor may need to be
drilled.) Mount a tap valve on the water line. - Connect the tubing to the valve. Connect the
other end of the tubing to the water line
fitting. Allow several large loops of tubing so
the unit may be moved out for cleaning and
servicing. - Turn the tap valve stem in slowly and pierce the
cold water pipe. Check for leaks. Gently move the
unit back into place.
32Installing an Ice Cube Maker
12.2.6
33Shutting Down aRefrigerator-Freezer
12.2.7
- When shutting down for a period of time,
precautions must be taken to prevent rusting and
remove odor. Remove the plug and switch off
current. Defrost until unit is completely
defrosted. - Remove water from interior. Wash inside of
cabinet with solution of baking soda and water.
Thoroughly dry the cabinet. - Leave the doors or lids slightly ajar to allow
circulation of air during shutdown period.
34Shutting Down aRefrigerator-Freezercontinued
12.2.7
- Caution Federal law requires the removal of the
door(s) from any out-of-service refrigerator or
freezer. Children can suffocate when hiding or
playing in a discarded unit! When taking a
refrigerator or freezer out of service, always
remove the cabinet door(s).
35Troubleshooting the Hermetic Refrigerator-Freezer
12.3
- Potential complaints of unsatisfactory
performance - Refrigerator does not run.
- Refrigerator runs all the time temperatures are
too cold. - Refrigerator runs all the time temperatures are
too warm. - Refrigerator runs all the time temperatures are
satisfactory. - Refrigerator cycles, but food compartment is too
warm freezing compartment is satisfactory.
36Troubleshooting the Hermetic Refrigerator-Freezer
continued
12.3
- Potential complaints of unsatisfactory
performance - Refrigerator cycles, but freezing compartment is
too cold. - Motor control cuts out.
- Refrigerator cycles satisfactorily refrigeration
is poor. - Refrigerator cycles, but does not freeze ice
cubes. - Refrigerator cycles, but too much ice accumulates
on the evaporator. - Refrigerator mechanism is very noisy.
37Ice on the Evaporator
12.3.1
- Large ice buildup in food storage space results
in poor cooling. Cause is usually a leaky door
seal (gasket). - In a frost-free or automatic defrost
refrigerator, frost buildup indicates defrost is
not operating. - Refrigerators with a separate freezer compartment
door often have an electric heater around the
door opening. This is referred to as a mullion
heater. The mullion heater prevents ice or
moisture from forming around the door opening. - Insert a thin piece of paper between the door and
cabinet. It should hold tightly when the door is
closed. If it can be pulled out easily, the
gasket needs to be replaced.
38Moisture and Icein the Cabinet Insulation
12.3.2
- Moisture and ice in the insulation indicates an
air leak in the outside cabinet seal or shell.
Wet insulation will lose its heat-insulating
qualities. - Two indicators of moisture in the insulation are
- Condensing unit will run more often than normal.
- Outside surface of the refrigerator will feel
colder than normal wherever insulation is wet. - Most freezers provide a small opening through the
inner lining, connecting the insulated area with
the inside of the freezer cabinet. Moisture will
tend to escape through this opening and condense
on the evaporator surface.
39Temperature-Pressure Conditions
12.3.3
- Prior to servicing a refrigerator, you must know
- Normal temperature in the evaporator during the
operating cycle. - Normal pressure on the low-pressure side during
the operating cycle. - Normal temperature of the condenser during the
operating cycle. - Normal pressure on the high-pressure side during
the operating cycle.
40Temperature-Pressure Conditionscontinued
12.3.3
A temperature recorder using vapor-filled bulbs
may be used to test operating temperatures.
41Temperature-Pressure Conditionscontinued
12.3.3
A high-pressure gauge and compound gauge may be
used to determine the operating pressures.
42Locating and Eliminating Noises
12.3.4
- Noises in the refrigerator usually come from
rattles. Sources may include - Loose baffles or ducts.
- Tubing touching something while vibrating.
- A tilting of the condensing unit caused by an
uneven floor. - Fan and motor vibration.
- A loose evaporator unit door.
- Loose articles on shelves.
- Shelves not seated properly on supports.
43Locating and Eliminating Noisescontinued
12.3.4
An ultrasonic leak detector may be used to
isolate many noises. ASensor.BDisplay.CSensit
ivity dial.DEarphone.
44Locating and Eliminating Noisescontinued
12.3.4
- Noise from within the unit may indicate it is
laboring too hard. - To determine this, test the electrical load with
an ammeter or wattmeter. - Three seconds is the average time to operate a
relay on starting. A slower start indicates an
overload.
45Locating and Eliminating Noisescontinued
12.3.4
A vibration or hum may be reduced by carefully
bending the tubing away from contact or clamping
rubber blocks on the tubing.
46Locating and Eliminating Noisescontinued
12.3.4
- Loose baffles and ducts can be secured with
self-tapping sheet metal screws. - Pressure sensitive tapes provide protection
against moisture, heat, sound, and
electromagnetic waves.
47Locating and Eliminating Noisescontinued
12.3.4
An inspection mirror is often needed to see into
hard-to-reach places.
48Cycling Timefor Refrigerators and Freezers
12.3.5
- Cycling times for residential refrigerators and
freezers vary depending on a number of factors
including amount of storage space being used,
outside box temperature, and compressor
condition. - Any unusual change in cycling time should be
investigated immediately.
49Hermetic Servicing
12.4
- Check all performance data information prior to
servicing a unit. Usually located on the
identification plate mounted on the compressor,
information will include - Type of refrigerant.
- Refrigerant charge.
- Compressor hp.
- Compressor speed.
- Running amperes.
- Voltage.
- Phase.
- Other items.
50Hermetic Servicing
12.4
Chart showing operating characteristics.
51Hermetic Servicingcontinued
12.4
- Servicing of hermetic refrigerators includes
- External servicing.
- Internal servicing.
- Overhaul of hermetic systems.
52External Servicing Operations
12.5
- External servicing operations may include
- Cabinet hardware.
- Ice cube maker.
- Cleaning.
- Eliminating noise (rattle).
53External Servicing Operationscontinued
12.5
- External servicing operations may include
- Electrical.
- Power-in circuit.
- Thermostat.
- Defrost thermostat.
- Interior light and circuit.
- Fan motor and circuit.
- Damper controls.
- Motor compressor (relay and overload protector,
capacitor, or motor terminals).
54External Servicing Operationscontinued
12.5
- External servicing operations may include
- Defroster.
- Defroster control and circuit.
- Defroster heater coil.
- Cabinet heaters.
- Evaporator fan and circuit.
- Condenser fan and circuit.
- Light circuit.
- Butter conditioner circuit.
55External Servicing Operationscontinued
12.5
External mechanisms, electrical wiring, and
electrical parts can all be checked for operation
quickly usinga volt-amp-ohmmeter or multimeter.
56External Servicing Operationscontinued
12.5
- Additional external service troubles can be
located by checking for - Ice on evaporator.
- Frost or sweat on suction line.
- Warm or hot discharge line.
- Ice or sweat on driers.
- Dirty condensers.
57Diagnosing External Troubles
12.5.1
- Carefully check the following parts of the
external electrical circuit prior to replacing a
hermetic compressor - Power-in connections.
- Thermostat.
- Wire terminals.
- Relay.
- Capacitor (if unit has one).
58Diagnosing External Troublescontinued
12.5.1
- The external electrical components can be checked
independently by removing them from the system.
Another method is to temporarily replace the item
with test part of the proper size. The unit may
then be checked to see if it will run. - Electrical connections must be clean and tight.
If loose or dirty, they may overheat. This high
temperature will discolor the connection. A blue
or greenish tint indicates overheating and
corrosion. If insulation is charred, overheating
has occurred.
59Diagnosing External Troublescontinued
12.5.1
A plug-on thermal motor protector protects the
motor from overheating. In addition, a start
relay positive temperature coefficient thermistor
(PTCT) is used.
60Diagnosing External Troublescontinued
12.5.1
- Conditions such as open circuits and grounded
electrical wires are easily checked with a
multimeter. - A test cord may be used to check four-pole
motors. - Two-pole motors may be tested only by using a
proper size relay in the circuit. These motors
overheat if starting circuit is connected more
than two or three seconds.
61TroubleshootingHermetic Electrical Units
12.5.1
- Check electrical supply.
- Check appliance voltage specifications. Use a
voltmeter to test the open circuit voltage. - Plug in appliance and check the voltage while
unit is running. The open circuit voltage is
likely to be slightly higher (no more than 5V)
with the motor running. - A difference of 10V or more indicates serious
trouble - An overload.
- Motor winding damage.
- Poor wiring to wall outlet.
62TroubleshootingHermetic Electrical
Unitscontinued
12.5.1
Locate the wiring diagram and check each circuit
independently.
63TroubleshootingHermetic Electrical
Unitscontinued
12.5.1
- If compressor fails to start
- Determine if electricity is reaching the motor
compressor. - If it is, check the starting relay and circuit
protectors. - Disconnect all wiring from the motor compressor.
- Check the motor compressor with a manual start
cord. The ground clip must be fastened to the
dome. - All clips or connectors should be plastic coated
to protect from shocks.
64TroubleshootingHermetic Electrical
Unitscontinued
12.5.1
All clips or connectors should be plastic coated
to protect from shocks.
65TroubleshootingHermetic Electrical
Unitscontinued
12.5.1
- Press manual switch.
- After one or two seconds, lift the switch button
to open the starting winding circuit. - If the motor operates, the problem is in the
external circuit.
66TroubleshootingHermetic Electrical
Unitscontinued
12.5.1
Testing a capacitor-start, induction-run motor.
67TroubleshootingHermetic Electrical
Unitscontinued
12.5.1
- Testing a capacitor-start, induction-run motor
- Replace the capacitor with a new one of the same
voltage and microfarad rating. An extra clip wire
or lead is needed. - Operate the switch as in previous frame.
- If the motor compressor works, check the
electrical system up to the compressor. - If the motor does not start, further motor checks
are needed.
68TroubleshootingHermetic Electrical
Unitscontinued
12.5.1
69TroubleshootingHermetic Electrical
Unitscontinued
12.5.1
- Testing a capacitor-start, induction-run motor
- Caution After testing is completed, short the
testing capacitor using a 20,000W (20kW), 2W
resistor. This will eliminate possibility of
electrical shock! - Test cords can be used for checking continuity
and grounding by replacing the fuse with a
lightbulb. - If trouble is found in evaporator or condenser,
they should be replaced.
70Defective Mullion Heater
12.5.1
- A defective mullion heater may cause door gasket
to freeze to the cabinet. - Locate the circuit in the wiring diagram.
- Disconnect both ends of the mullion heater leads.
- Test the heater for continuity. If proven
defective, check for another mullion heater in
the insulation. - Test it. If operating properly, install it.
- If there is no additional heater, install a new
one of the same wattage rating. - If the problem is a faulty wire, use a stiff
steel wire to pull new wiring through the
insulation.
71Electrical Troubleshooting
12.5.1
The RED system can be used to check electrical
circuits on General Electric products. It checks
circuits for faults in the defrost system,
thermostats, heaters, fans, and
compressor. AMale connector.BFemale connector.
72Electrical Troubleshootingcontinued
12.5.1
A multiple-circuit connector mounted at the front
bottom of the cabinet is used.
73Electrical Troubleshootingcontinued
12.5.1
- Always turn the thermostat to the off position
prior to separating the connector. - After connecting tester, turn power on. The
power on light should be lighted. If not, the
power circuit needs repair.
74Electrical Troubleshootingcontinued
12.5.1
All Tecumseh motor compressor terminals are set
up to read Common-Start-Run (from left to
right).
75Electrical Troubleshootingcontinued
12.5.1
- Motor terminal connection may be stamped R, S,
and C. If they are not identified, measure the
resistance of the compressor windings. - First, measure the resistance across each set of
terminals. The sum of two of the readings should
equal the third.
76Electrical Troubleshooting
12.5.1
77Electrical Troubleshootingcontinued
12.5.1
- Determine which terminal is common. The common
terminal is the one which does not contain the
greatest resistance. - Determine which terminal is the start terminal.
The start terminal should include the greatest
resistance between itself and the common. - The last terminal is the run terminal. Mark the
final motor terminal locations.
78Starting a Stuck Compressor
12.5.1
- Three ways to start a stuck compressor
- Disconnect the wiring to the motor compressor.
Connect test cord into electrical circuit of the
main winding. Connect an extra capacitor into the
circuit. Turn on the power from one to three
seconds. The extra capacitor will try to reverse
the compression rotation. - Caution The capacitor cannot be left in the
circuit more than a second or two or it will
cause the motor to overheat!
79Starting a Stuck Compressor
12.5.1
- Three ways to start a stuck compressor
(continued) - Connect the 120V motor compressor into a 240V
power circuit, using a starter cord. - Caution Press the pushbutton switch for only a
second at a time to avoid motor damage! The extra
voltage may break the stuck compressor loose. - An extra-torque method is to connect a 240V, 100
microfarad start capacitor across the terminals
of the run capacitor. The connection must be for
no more than one second.
80Short-Cycling
12.5.1
- Short cycling is a term used to describe a unit
that starts and stops too frequently. Cause may
be - Thermostat not mounted securely.
- Loose connections in the starting relays.
- Caution Do not tap a relay to check it! This may
cause the points to damage the motor.
81Cleaning theExternal Mechanism
12.5.1
- The condenser and compressor should be cleaned
every three months. Units with condenser fans
should be disconnected from electrical power
prior to cleaning. - Clean hermetic dome using a vacuum cleaner.
- In the shop, high-pressure air, carbon dioxide,
or nitrogen may be used for cleaning. - Caution Goggles should always be used and there
should be adequate ventilation.
82Internal Service Operations
12.6
- Internal service includes any of the following
- Removal of any part of the hermetic system.
- Determination of air in the system.
- Discovery of lack of refrigerant.
- Investigation for clogged filter-drier or
capillary tube. - Internal service operations require gauges and
servicing devices. These include vacuum pumps,
refrigerant cylinders, etc.
83Internal Service Operationsconditions
12.6
- Prior to opening the system
- Thoroughly clean all connections and valve
fittings. - Install a valve adaptor or piercing valve.
- Install a gauge manifold.
- Install refrigerant recovery equipment.
84Internal Service Operationsconditions
12.6
- The following are the most common service
operations - Locating and repairing refrigerant leaks.
- Purging, charging, and recovery of refrigerant.
- Cleaning or replacing the capillary tube.
- Replacing a compressor.
- Replacing a filter-drier on the high side.
- Installing a filter-drier on the low side.
- Evacuating the system.
85Internal Service Operationsconditions
12.6
- The following are the most common service
operations performed (continued) - Adding oil.
- Using a high-vacuum pump.
- Replacing an evaporator and/or condenser.
- NoteSome service operations are best performed
in the shop.
86Diagnosing Internal Troubles
12.6.1
- Gauges, thermometers, electrical instruments, and
careful observation can assist in diagnosing
internal troubles. - A partially frosted evaporator, with another part
heavily frosted, indicates a lack of refrigerant. - A sweating or frosted suction line indicates
liquid refrigerant in the suction line. The cause
may be a broken thermostat or too much
refrigerant (if a capillary tube is used).
87Diagnosing Internal Troublescontinued
12.6.1
- Internal electrical troubles involving the motor
and connections are very rare (3 of 1000 cases!).
Most internal problems are due to air and
moisture in the motor compressor causing
corrosion, and eventually, burnout. - Liquid refrigerant reaching the compressor may
remove oil or slug compressor. Valves may be
broken as the compressor attempts to pump oil or
liquid refrigerant. - Continuous running and no refrigeration, and a
condenser cooler than normal may indicate a
restriction in the capillary tube or filter-drier
or screen on the high side.
88Moisture in theRefrigerant Circuit
12.6.1
- Moisture in the system will cause the unit to
malfunction. Moisture will form ice in the
refrigerant control at the point the liquid
refrigerant is expanding into the evaporator.
This is noted by the following. - System will completely defrost. Ice that caused
the blockage will disappear. Unit will work again
only until the ice forms again at the refrigerant
control. - Pressure will decrease in the suction line.
Compound gauge shows a steady decrease over
several hours. Pressure will suddenly become
normal again. This cycle will keep repeating.
89Moisture in theRefrigerant Circuitcontinued
12.6.1
- Moisture in the system will cause the unit to
malfunction. Moisture will form ice in the
refrigerant control at the point the liquid
refrigerant is expanding into the evaporator.
This is noted by the following. - Warming the refrigerant control using a safe
resistance heater (hot pad) or radiant heat bulb
during system shutdown will cause the ice to
melt. If the system begins to work properly,
moisture is present. - Moisture creates corrosion problems within the
system. The refrigerants react with the water
molecules to form acids. The acids increase
corrosion.
90Moisture in theRefrigerant Circuitcontinued
12.6.1
- Moisture in the refrigerant circuit may be
removed by installing a drier in the liquid line.
The procedure is - Install gauge manifold.
- Recover refrigerant.
- Dry and clean filter-drier connections.
- Apply flux.
- Heat the connections.
- Remove the old drier.
- Install the new drier.
91Moisture in theRefrigerant Circuitcontinued
12.6.1
- Procedure (continued)
- Braze the connections.
- Test for leaks.
- Evacuate the system.
- Charge the system.
- Warm the refrigerant control enough to melt the
ice. The drier will absorb the moisture as it
circulates.
92Wax in Oil
12.6.1
- A small amount of wax is contained in oil.
- Oil circulates with refrigerant. Sudden expansion
at the refrigerant control, accompanied by low
temperature and pressure, cause some wax to
separate from the oil. This wax collects in the
refrigerant control. Over time, it may restrict
flow or clog the control.
93Wax in Oilcontinued
12.6.1
- A restriction can be checked with a piercing
valve. Observe the following - A pressure test showing low-side pressure to be
very low. - Liquid refrigerant shows up in the condenser.
- The unit does not produce any refrigeration at
all. - Always clean or replace a clogged valve or
capillary tube. Pack the control in dry ice prior
to removal to keep ice or wax locked in the
faulty refrigerant control.
94Shortage of Refrigerant
12.6.1
- Shortage of refrigerant usually indicates a leak
in the system. Lack of refrigerant is indicated
by - Low-side pressure below normal.
- Evaporator (or the outlet end of the evaporator)
that is warm. - High-side pressure that is below normal.
- Piercing valve mounted on the outlet of condenser
that, when opened, allows only gas to escape.
95Gauge (Service) Manifold Types and Construction
12.7
- A gauge (service) manifold is used to service a
hermetic system. - Two types of manifolds
- Block manifold.
- Standard manifold.
- Gauge manifold with two gauges, two hand valves,
and three separate lengths of flexible
refrigerant tubing is most useful for performing
necessary operations.
96Gauge (Service) Manifold Types and
Constructioncontinued
12.7
97Gauge (Service) Manifold Types and
Constructioncontinued
12.7
- The hoses have 1/4" (6mm) flare fittings with
synthetic rubber gaskets. Connections can be made
pressure-tight with finger pressure alone. - Manifold gauges can be used to produce a vacuum.
98Gauge (Service) Manifold Types and
Constructioncontinued
12.7
Usage of a Gauge Manifold for Various Purposes
99Connecting a Gauge Manifold
12.7.1
- Gauges are used to check pressure in a system.
- Connection must be made without air, moisture, or
dirt entering system. - System design determines procedure for connecting
gauges. - Purge hoses prior to and following service.
- When checking high-side pressure, use piercing
valve if system is already charged. - If system is not charged, braze a process tube
into the condenser line.
100Connecting a Gauge Manifoldcontinued
12.7.1
- After installing gauge manifold, operate system
through at least three cycles. - Record suction pressures, condensing pressures,
evaporator temperature, and the condenser
temperature.
101System with Two Service Valves
12.7.1
- Easiest for attaching gauges.
- Permits checking both the low-side and high-side
pressures. - Most common on commercial systems.
102Valve Adaptor
12.7.1
- Used with hermetic systems.
- Adaptor is fastened to the dome.
- Adaptor has removable service valve.
103Process Tube
12.7.1
- Can be adapted for service by installing a
piercing valve. - Used to evacuate, test and charge the new unit.
- May braze an extension to it.
104Piercing Valve
12.7.1
- Most common method of accessing a small hermetic
system. - Mounted on the suction tubing, discharge tubing,
or both. - May be mounted on a process tube.
105Purging Service Lines
12.7.1
106Hermetic ServiceValves and Adaptors
12.8
- Most hermetic refrigerators do not have service
valves. - Some have fittings to which valves can be
attached.
107Hermetic ServiceValves and Adaptorscontinued
12.8
- Purpose for attaching service valves
- Check internal pressures.
- Discharge system or add refrigerant.
- Add oil.
- Evacuate the system.
- Make it easier to replace driers, motor
compressors, evaporators, and refrigerant
controls. - Recharge the system.
108Hermetic ServiceValves and Adaptorscontinued
12.8
- Use of a service valve adaptor
- Connect a flexible charging line to the service
valve adaptor. - This is attached to either a hand valve or a
service manifold mounted on the other end of this
tubing. - The valve should be loose at the attachment
point. - Use vapor from the cylinder to purge the lines.
- Gauge may be located on the compressor dome,
suction line, or process tube.
109Hermetic ServiceValves and Adaptorscontinued
12.8
110Systems with Valve Adaptors
12.8.1
Valve adaptor is fastened to the compressor dome.
111Systems with Valve Adaptorscontinued
12.8.1
Adaptor has a removable service valve.
112Systems with Valve Adaptorscontinued
12.8.1
Valve and adaptor connect together.
113Systems with Valve Adaptorscontinued
12.8.1
- Service valves may have two openings.
- One for pressure gauge.
- One for performing service.
114Systems with Valve Adaptorscontinued
12.8.1
- Procedure for using valve adaptors
- Clean outside.
- Remove dust cap from adaptor.
- Choose correct valve stem drive.
- Push the service valve stem forward in body of
valve attachment. - Engage the valve stem in the valve adaptor
needle. - Thread the valve adaptor unit into the attachment
body. - Use good gaskets.
115Systems with Valve Adaptorscontinued
12.8.1
- Procedure for using valve adaptors (continued)
- Prior to opening valve adaptor needle, tighten
packing unit around the valve stem. - Bleed the passages.
- Purge the assembly.
- Leave flexible line fitting loose at valve
attachment. - After purging, tighten the loose connection.
- Always test for leaks using a refrigerant
pressure of 15 psig (30 psia) to 20 psig (35
psia) (206.8 kPa to 241.3 kPa).
116Process Tube and Adaptors
12.8.2
- As handle is turned, ball bearing presses into
the tubing, compressing it. - Process tube can be used for service by
installing a piercing valve on the process tube. - An extension may be brazed to the process tube or
a process tube adaptor mounted on it. Adaptors
are of various sizes.
117Process Tube and Adaptorscontinued
12.8.2
- Pinch-Off Tool.
- Used when necessary to seal off soft copper
tubing (up to 3/8" OD). - Has screw-type action shaft with a ball bearing
on the end that presses against the tube. - Tool is placed over the copper tubing.ABefore
pinch.BAfter pinch.
118Process Tube and Adaptorscontinued
12.8.2
- Pinch-Off Tool (continued).
- Produces a permanently pinched line.
- Tool is left in place until adaptor is removed.
Brazing seals tubing end. - Can be used in an emergency to isolate parts.
- ADone with pliers-type tool.BDone with tool
shown on previous slide.
119Piercing Valves
12.8.3
- Most common method for accessing small hermetic
systems. - May be mounted on suction tubing, discharge
tubing, or both. - May be mounted on process tube.
120Piercing Valvescontinued
12.8.3
Two general typesABolted-on.BBrazed-on.
121Installation ofBolted-on Piercing Valves
12.8.3
- Tubing must be straight, round, and clean.
- Be certain there is enough space to operate the
valve. - Place a small amount of clean refrigerant oil on
the tubing. - Check that the synthetic sealing washer is in
place and needlepoint piercing valve stem is all
the way out. - Mount the valve on the tubing.
- Tighten the unit clamping screws evenly.
- The valves are usually left in place on the
system.
122Installation ofBolted-on Piercing
Valvescontinued
12.8.3
Three types of piercing valves.ACharge-and-tap
valve.BHand-valve type.CLine-tap type with
hexagonal wrench.
123Installation ofBrazed-on Piercing Valves
12.8.3
- Safe to use since neither the suction tubing nor
condenser tubing has liquid in them. However,
make certain no flammables or soft-soldered
joints are near the brazing area. - Be certain tubing is straight and round at
brazing point. - Clean the saddle and tubing mating surfaces with
clean sandpaper or steel wool.
124Installation ofBrazed-on Piercing Valves
continued
12.8.3
- Remove the piercing valve stem and the gasket
from the saddle. - Put clean, fresh brazing flux on the saddle.
- Mount saddle on tubing, ensuring clearance for
mounting the valve. - Heat both the tubing and saddle until filler rod
material flows around saddle. - Do not move or shift saddle during brazing or
cooling process.
125Installation ofBrazed-on Piercing Valves
continued
12.8.3
- Caution Do not overheat the tubing. It may be
weakened to point of failure and burst. Wear
goggles during the brazing operation. - Inspect joint and, when cooled, install the
piercing needle and gasket. - Unit is now ready for installation of service
valve attachment.
126Questions
- Should there be a separate circuit from the
circuit breaker panel to the refrigerator-freezer
outlet?
Yes.
- How much space must there be between a
refrigeration unit and surrounding surfaces if
the outside shell of a cabinet is the condenser?
At least 2" (50mm).
- Refrigerators with a separate freezer compartment
door often have an electric heater around the
door opening. This is referred to as a
___________________.
mullion heater
127Questionscontinued
- In a frost-free or automatic defrost
refrigerator, what does a formation of frost
indicate?
Defrost system malfunction.
- What may cause the outside of a refrigerator to
feel colder than normal?
Insulation within the unit has gotten wet.
- What symptoms are found with dirty or loose
electrical connections?
High temperatures causing discoloring of the
connection (blue or greenish tint).
128Questionscontinued
- What is the maximum allowable voltage drop to a
refrigerator?
10.
- Before servicing a capacitor, what safety
precaution must be taken?
Short the capacitor using a 20,000W (20kW), 2W
resistor.
- What are symptoms of a defective mullion heater?
The door gasket freezes to the cabinet or
excessive condensation around the door.
129Questionscontinued
- When testing single-phase motor terminals, which
two terminals will have the highest resistance?
Between the run and start terminals.
- Name two internal service procedures.
Removal of any hermetic system component and loss
of refrigerant charge.
- Name two problems that will occur if liquid
refrigerant reaches the compressor.
Broken valve and thinning of refrigerant oil.
130Questionscontinued
- What symptoms will be found if moisture freezes
at a refrigerant control?
Low suction pressures (vacuum) until refrigerant
control is warmed. Pressures then return to
normal.
- What other problems can moisture cause in a
refrigeration system?
The formation of hydrofluoric and hydrochloric
acids.
- What can cause wax to separate out of refrigerant
oils?
Sudden expansion at the refrigerant control,
accompanied by low temperature and pressure.
131Questionscontinued
- Name two symptoms indicating a lack of
refrigerant charge.
A decrease in both low-side and high-side
pressures.
- Name three purposes for attaching service valves
to a hermetically sealed system.
Check internal pressures, add refrigerant, and
add refrigerant oil.
- Name two general types of piercing valves.
Bolted-on and brazed-on types.
132Core Valve
12.8.4
Many systems use a Schrader core valve to access
a hermetic system.
133Core Valvecontinued
12.8.4
A clamp-on core valve adaptor is used with
flexible service tubing fitting with a pin. The
pin depresses the core valve stem as the fitting
or service device is mounted.
134Core Valvecontinued
12.8.4
A service valve attachment that mounts on the
Schrader valve adaptor may be used. Its long stem
loosens the valve core while evacuating the
system. This allows more flow of vapor when
drawing a vacuum.
135Locating Refrigerant Leaks
12.9
- Although testing for leaks may vary with
refrigerant used, all methods require applying
pressure to the system with an inert gas such as
nitrogen. - To begin testing, a positive pressure of 5 psig
(20 psia) to 30 psig (45 psia) (137.9 kPa to
310.2 kPa) is necessary throughout the circuit. - If no leaks are found, test again at or above the
normal condensing pressure for the refrigerant. - Check for leaks prior to evacuating the unit.
- Use proper recycle/recover equipment.
136Locating Refrigerant Leakscontinued
12.9
- An electronic leak detector can be used for leaks
of CFC, HCFC, and HFC refrigerants. - If a leak is found and service has occurred,
recheck the complete unit for additional leaks.
137Pressure-Testing for Leaks
12.9.1
- With proper care, nitrogen may be used when
testing for leaks. - Pressure in the nitrogen cylinder is about 2000
psig (14 Mpa). - Caution A pressure-reducing device that has both
a pressure regulator and a pressure relief valve
must always be used when testing with nitrogen.
138Pressure-Testing for Leaks
12.9.1
139Pressure-Testing for Leakscontinued
12.9.1
- Caution A refrigerating system can explode if
pressure is allowed to build up in the system.
Too much pressure can lead to serious/deadly
accidents. - Prior to using nitrogen to test a system, check
the system nameplate. In most cases, it will give
recommended testing pressures. - Caution If pressures are not known, never test
all or part of a hermetic system at a pressure
over 170 psig (185 psia or 1275 kPa).
140Pressure-Testing for Leakscontinued
12.9.1
- Caution Never use oxygen or acetylene to develop
pressure when checking for leaks. Oxygen will
cause an explosion in the presence of oil.
Acetylene will decompose and explode if it is
pressurized over 30 psig (45 psia or 310.2 kPa).
141Leak Detecting Devices
12.9.2
- System leaks are usually very small, so sensitive
detecting devices are needed. - Commonly used devices
- Bubble solutions.
- Fluorescent dyes.
- Refrigerant dyes.
- Halide torch.
- Electronic detection.
142Bubble Solutions
12.9.2
- A water-soap solution is brushed over an area
suspected of leaking. - Gas coming through the solution will cause
bubbles. - Advantages include ease of use, low cost, and
ease of application, and use around urethane
insulation. - A disadvantage is that the larger leaks will blow
through the solution and no bubbles will occur.
143Refrigerant Dye andFluorescent Leak Detecting
12.9.2
- Dye in a system produces a bright red color at
the point of leakage. - Most leaks show up quickly however, up to 24
hours may be required in some cases. - In most systems, the entire refrigerant charge
must be replaced with refrigerant containing the
dye. - An ultraviolet fluorescent leak detector scans
the system. May be used with a variety of
refrigerants, including R-134a.
144Refrigerant Dye andFluorescent Leak Detecting
12.9.2
145Halide Torch Leak Detector
12.9.2
- Notes presence of halogen refrigerant by
displaying a light green color. - Torch burner is at top. One end of rubber tube is
connected to base of burner. Other end is moved
to various parts of system. Rubber tube draws air
from open end into burner.
146Halide Torch Leak Detectorcontinued
12.9.2
- When open end of tube nears leaking connection,
it draws up some of the leaking refrigerant
vapor. - When vapor contacts the burner, the flame color
becomes green indicating a leak.
147Electronic Leak Detector
12.9.2
- Three commonly used types
- Electrochemical sensor.
- Ultrasonic.
- Dielectric.
148Electrochemical Sensor
12.9.2
- Ceramic layer covered by reactive element
maintained at high temperature by a built-in
heating element. - Contact with halogen-bearing gas causes an
electrical current to flow to a collection
electrode. - No need to reset detector for different
refrigerants. No need for technician to determine
refrigerant in use.
149Dielectric (Electronic) Sensor
12.9.2
- Detects all halogenated refrigerants except R-14.
- Caution Electronic leak detector should not be
used in areas containing explosive or flammable
vapors. - Avoid drafts when using.
- Gases are run between plates of a capacitor.
- Gases act as the dielectric (insulator) for each
capacitor.
150Dielectric (Electronic) Sensorcontinued
12.9.2
- Leak-detecting probe is passed below suspected
leak. - If leak exists, refrigerant is drawn into probe.
New vapor changes the resistance in the circuit. - Detector will emit a piercing sound, or light
will flash, or both.
151Ultrasonic Leak Detectors
12.9.2
- Use headphones and a portable, hand-held
detector. - Ultrasonic frequencies are sound waves beyond the
range of human hearing. - Detect the sound that vapor makes escaping from a
pressurized system.
152Repairing Leaks
12.10
- Remove and recover the refrigerant from the part
of the system with the leak. (Note In some
cases, you may have to empty the complete
system.) - Check the pressure to ensure it is 0 psi (no
pressure or vacuum in the system). - Avoid soldering or brazing a system with
refrigerant in it. Heat may break down the
refrigerant.
153Repairing Leakscontinued
12.10
- May use nitrogen cylinder connected to process
tube when soldering or brazing. - System is pressurized and checked for leaks.
- When leak is found, area can be brazed.
- Recheck for leaks prior to removing nitrogen
cylinder.
154Leaks in Tubing Connections
12.10
- May occur at flared connection if
- Tube flare is not correct.
- Flare nut has not been tightened securely.
- Threads are stripped.
- Evacuate system using proper recycle/recovery
equipment. - On recovery, use a traditional vacuum pump to
fully evacuate the system prior to recharging.
155Leaks in Tubing Connectionscontinued
12.10
- Replace leaking fitting by making a new flare.
- Use a new flared fitting.
- If brazed or silver-soldered connection, repair
by cleaning, coating with flux, and reheating. - When reheating, use a fire-resistant material to
protect nearby materials.
156Leaks in Tubing Connectionscontinued
12.10
- Caution Avoid overheating other parts of the
system. Never heat a drier. Moisture will be
driven out into the system.
157Refrigerant Recovery and Evacuation
12.11
- Indications of insufficient refrigerant charge in
a hermetic unit - Partially frosted evaporator.
- Low-head pressure.
- Low pressure on the low side.
- Unit runs too frequently.
- Confirmation of a leak.
158Refrigerant Recovery and Evacuationcontinued
12.11
- Procedure for adding refrigerant
- Evacuate the system.
- Connect a refrigerant cylinder to the charging
manifold. Charge with the correct refrigerant
vapor. - Refrigerant cylinder may be heated with warm
water or electric heater insert. - Caution Temperature must not exceed 120º F
(48.9º C). Never use an open flame for heating.
159Compressor-Running Test 1
12.11
- Start the unit.
- Open the line service valve, gauge manifold
valve, and refrigerant cylinder valve. - Observe low-side pressure gauge. Pressure of not
more than 25 psig (40 psia or 275.8 kPa) should
be created. Control pressure by adjusting
refrigerant cylinder valve.
160Compressor-Running Test 1
12.11
161Compressor-Running Test 1continued
12.11
- Allow refrigerant charge to enter system for
three to five minutes. - Close gauge manifold valve.
- Allow unit to operate and check frost line on
evaporator. - If frost line is inadequate, repeat the charging
for short intervals. Frost line must not go
beyond the accumulator in the suction line. - When proper amount of frost is observed, close
refrigerant cylinder valve, adaptor valve, and
gauge manifold valve.
162Compressor-Running Test 1continued
12.11
- Check for leaks using a leak detector.
- If system contained a process tube, pinch off
with a proper tool. Remove adaptor valve. Flatten
tube end by crimping and braze end of tubing.
163Compressor-Running Test 2
12.11
- Mount charging device between the refrigerant
cylinder and the low side. - The charging device will allow liquid refrigerant
to flow into it from the cylinder. The
refrigerant vaporizes inside the device. - NoteAlways charge a unit with vapor. Never
charge liquid refrigerant into the low side of a
domestic or small commercial unit!
164Compressor-Running Test 2continued
12.11
- When charging device is first used, process tube
will sweat and perhaps frost. As unit becomes
fully charged, sweating and frost will disappear. - Check suction line temperature. It should be
about 20ºF higher at 6" to 10" from the
compressor than at the evaporator outlet. - If temperature is lower, liquid refrigerant may
enter compressor and cause damage. If temperature
is higher, motor compressor may overheat and burn
out.
165Evacuation Data
12.11
- A charging device mounted between refrigerant
cylinder and low side should contain a check
valve that can be attached to the line allowing
easy evacuation of system. - These charging units are available in three
capacities - Less than 1 hp.
- 1 hp to 4.75 hp.
- 5 hp to 10 hp.
- The correct size must be used.
166Compressor-Running Test 3
12.11
- Must have an exact refrigerant charge.
- If overcharged, evaporator will be flooded.
- Use of accumulator at outlet of evaporator
relieves the problem somewhat. - Carefully monitor the amount charged into these
systems. - Slowly charge system with refrigerant in vapor
state until suction line starts to sweat or frost
back. Purge a bit until the frost back
disappears.
167Charging with Exact Amount
12.11
- Completely discharge the system.
- Recharge with a cylinder containing the exact
amount of refrigerant needed as determined by the
manufacturers recommendations.
168Reminders Regarding Charging
12.11
- Charge a system into the low side, if possible.
- Refrigerant should be put into the system in
vapor form. Forcing liquid refrigerant into
system may damage the compressor and injure the
technician. - If a system is short of refrigerant, there is a
leak. Locate and correct the leak before the
system is charged. - Use the proper recovery/recycling equipment when
locating and repairing leaks. - If after adding refrigerant to a system it
becomes noisy, oil should be added.
169Charging with Portable Charging Cylinder or
Digital Scale
12.11.1
- Charging cylinder with a glass-tube liquid level
indicator allows transfer of refrigerant into a
system and measures the amount on a scale. Some
may be electrically heated to speed up
evaporation and maintain pressure in the
cylinder. - Caution When heating a cylinder or compressor,
required temperature and pressure safety controls
must be provided. A pressure control relief valve
and a thermostat must be provided!
170Charging with Portable Charging Cylinder or
Digital Scale
12.11.1
171Charging with Portable Charging Cylinder or
Digital Scalecontinued
12.11.1
- The system has a pressure gauge and a hand valve
on the bottom. They are used for filling the
charging cylinder or charging liquid refrigerant
into a system. - The valve at the top of the cylinder is used for
charging refrigerant vapor into the system (the
best and safest method).
172Procedures for Use of a Portable Charging
Cylinder after Evacuation
12.11.1
- Attach line from charging cylinder to the center
of the gauge manifold. Purge with the fitting
loose at the center part of the gauge manifold.
Tighten this connection. - Open piercing valve or valve adaptor and gauge
manifold valve.
173Procedures for Use of a Portable Charging
Cylinder after Ev