Title: Corrosion Control and Monitoring
1Corrosion Control and Monitoring
- ABC Company
- ABC Chemical Complex
- Engineering Specification
2Corrosion Control Monitoring
- SCOPE
- This Engineering Specification includes external
and internal corrosion control and monitoring for
DOT regulated pipelines. - Design, construction, construction inspection,
construction acceptance, operation, and
maintenance of DOT regulated pipelines are
covered by this Engineering Specification.
3Corrosion Control Monitoring
- GENERAL
- All DOT regulated ABC pipelines require
protection from the environment. - Corrosive elements in the pipeline stream must be
neutralized or the pipe material must be
resistant to the stream.
4Corrosion Control Monitoring
- Minimum requirements for corrosion control
- External Corrosion Control
- Buried DOT regulated pipelines will be coated and
cathodically protected - Internal Corrosion Control
- Known corrosion rate based on historical data
- Corrosion rate from a national standard data base
- Data collected from laboratory prototype testing
5Corrosion Control Monitoring
- Minimum requirements for corrosion control
(Continued) - Above Ground External Corrosion Control
- Coat with an approved system with resistance to
the soil and internal fluid temperature
6Corrosion Control Monitoring
- REFERENCES
- NACE RP 0169-92
- Surface Preparation
- NACE No. 1, SSPC-SP 5, White Metal Blast Cleaning
- NACE No. 2, SSPC-SP 10, Near White Metal Blast
- NACE No. 3, SSPC-SP6, Commercial Blast
- NACE No. 4, SSPC-SP 7, Brush-Off Blast
7Corrosion Control Monitoring
- PERSONNEL REQUIREMENTS
- Engineering design will be performed by a
Corrosion Engineer with training and experience
in the proposed corrosion control system. - Coating, lining, and painting inspection will be
performed by an inspector with appropriate
training and experience.
8Corrosion Control Monitoring
- PERSONNEL REQUIREMENTS (Cont..)
- Cathodic protection installations will be
inspected by an inspector with training and
experience in cathodic protection inspection. - Internal corrosion monitoring installations will
be inspected by an inspector with training and
experience in internal corrosion monitoring
inspection.
9Corrosion Control Monitoring
- DESIGN REQUIREMENTS, EXTERNAL
- Cathodic Protection Criteria
- Buried Onshore Pipelines Pipe-to-soil potential
equal to or more negative than -0.85 volts
referenced to copper-copper sulfate electrode and
recorded immediately after current interruption
(Instant-off potential). - Offshore Pipelines Pipe-to-water potential
equal to or more negative than -0.80 volts
referenced to a silver-silver chloride electrode
with instant off potential reading.
10Corrosion Control Monitoring
- Tank Bottoms Steel-to-soil potential equal to
or more negative than -0.85 volts with a
copper-copper sulfate half cell and instant
off potential. - Maximum pipeline potential Equal to or less than
-1.5 volts to a standard copper-copper sulfate
half cell with the current temporarily
interrupted.
11Corrosion Control Monitoring
- Coating Requirements
- New buried pipe sections shall be coated with one
of the following types - Fusion bonded epoxy
- Coal tar epoxy
- Polyolefin tape
- Prefabricated films
- Other coating systems approved by Central
Engineering - Surface preparation shall be in accordance with
manufacturers recommendation and Appendix B.
12Corrosion Control Monitoring
- Methods Used for Cathodic Protection
- Galvanic Anode Systems
- Provide protection to the structure by the
potential difference generated by the
electrochemical reaction between the structure
and the anode through a soil or water
electrolyte. - Typically used in soil or water with resistivity
less than 5000 ohm-cm.
13Corrosion Control Monitoring
- Methods Used For Cathodic Protection (Cont)
- Impressed Current Systems
- Uses external source of DC power, usually an AC
trans-former with an AC to DC rectifier, to
provide the driving voltage to the structure to
be protected. - Potential difference between the anode and the
structure creates current flow from the anode
into the soil and onto the pipeline. - Used when the soil resistivity exceeds 5000
ohm-cm and/or more than 5 amperes of impressed
current are required.
14Corrosion Control Monitoring
- Equipment
- Galvanic Anode Systems
- Anode Magnesium onshore, Galvalum III offshore.
- Junction box to connect leads from structure and
anode. - Impressed Current Systems
- DC transformer/rectifier (supplied as a unit).
- Anode(s) with inert or low reactivity
characteristics. - Terminal box with resistors to adjust current
flow to each anode or anode string.
15Corrosion Control Monitoring
- Miscellaneous
- Install lightning arrestors.
- Provide electrical isolation Insulating flanges
or spools. - Minimize interference with bonding stations.
- Install test stations to measure potentials.
- Complete the following documentation
- Bonding and/or anode bed data sheet.
- Bonding station data sheet.
- Test station data sheet.
16Corrosion Control Monitoring
- Impact on Operating Equipment
- Apply NEMA electrical-class safety requirements
to all equipment associated with impressed
current installations. - Install CP equipment in areas not requiring
intrinsically safe design. - Locate anode beds to minimize effect on other
structures and to minimize mechanical damage from
foreign construction.
17Corrosion Control Monitoring
- Perform interference testing on all equipment
that may be damaged by the new CP installation.
Testing shall include, but is not limited to, the
following situations - Pipelines crossing within 5 feet.
- Metal Structures within 5 feet of the pipeline.
- Metal Structures within 200 feet of the anode bed.
18Corrosion Control Monitoring
- Impact on Operating Equipment
- Design CP systems with capacity for current loss
through interference bonds and future current
loss due to coating deterioration. - Minimize casing installations for protection of
the carrier pipe. Perform interference testing
as shown in Company Corrosion Control
Monitoring Specification Appendix E. Provide
bonding stations for each casing installation.
19Corrosion Control Monitoring
- DESIGN REQUIREMENTS, INTERNAL
- Corrosive chemicals in the pipeline stream
- May reduce stream (liquid or gas) quality or
- Cause general thinning or pitting attack
- Shall be handled by one of the following methods
- Neutralization or removal of the corrosive
chemicals. - Select a pipe material which is resistant.
- Coat the internal surfaces of the pipe.
20Corrosion Control Monitoring
- Design package will contain
- Provisions for upset/emergency conditions.
- Recommended corrosion monitoring program.
- Recommended corrosion monitoring equipment.
- Installation of personnel safety devices and
platforms required for safe performance of
duties. - Pigging procedure when pigging facilities are
included in the design package. - Compliance with regulations of local, state, and
federal jurisdiction for pigging procedures.
21Corrosion Control Monitoring
- Documentation Requirements
- Determine thickness measurement locations (TMLs)
based on the most probable locations for
corrosion or erosion-corrosion damage. Select
TMLs with the assistance of the Corrosion
Engineer. - Collect baseline thickness readings on all new
installations. - Install corrosion monitoring equipment where the
worst case corrosion attack is expected. - Provide corrosion monitoring data sheets.
22Corrosion Control Monitoring
- DESIGN REQUIREMENTS, ABOVE GROUND EXTERNAL
- Coat with a coating system that is recom-mended
for the environment. - Prepare surface in accordance with
external-coating-system manufacturers
recommendations. See Company Corrosion Control
Monitoring Specification Appendix B.
23Corrosion Control Monitoring
- INSTALLATION
- Quality Control, External Systems
- Coatings
- Qualified Inspector presence - 100.
- Field applied coating systems - 100 inspection.
- Shop applied coating systems - 100 inspection.
- Coating repairs - 100 inspection.
- Protect all stored coating materials at the
construction site from weather, particularly
directly sunlight and heat.
24Corrosion Control Monitoring
- Pad in the pipe trench
- Inspect just prior to laying the pipe in the
trench. - Remove all trash and construction debris.
- Cables
- Inspect upon receipt at job site to detect nicks
and damage. - 100 inspection at the mill with proper mill
cert.. - Avoid damaging cable insulation during
installation. - Splice cables aboveground in terminal boxes.
- Use non-conductive conduits for cable
installation. - Make cathode cable connections aboveground, if
possible. - Repair buried connection in accordance with the
original coating manufacturers recommendations.
25Corrosion Control Monitoring
- Transformer/Rectifier Systems
- Install by a qualified electrician.
- Test rectifier at maximum design load to assure
the DC output meets the manufacturers
specifications including the maximum AC ripple. - Calculate rectifier efficiency and record on the
rectifier data sheet. - Verify the positive cable is attached to the
anode bed and the negative cable is attached to
the protected structure or pipe.
26Corrosion Control Monitoring
- Miscellaneous Considerations
- Inspect cables in terminal boxes to assure
correct labels. - Verify test stations, bonding stations, and
associated hardware for cathodic protection
service. - Contact owners/operators of foreign pipelines to
enable testing before and after new cathodic
protection project commissioning. - Record base readings on the new pipeline or
structure prior to cathodic protection system
energizing. Record potentials at all interference
bonds and test stations. - Energize system in small current increments and
record potentials with each increase until
protection is achieved. - Check bonding stations for interference problems.
- File all commissioning data in the original
equipment file.
27Corrosion Control Monitoring
- Quality Control Requirements, Internal Surface
- Inspect corrosion monitoring installations with
the services of a qualified Corrosion Technician. - Take baseline data prior to pipeline
commissioning. - Install lined pipelines per design.
- Repair lining of field joints as recommended.
- Install corrosion monitoring devices per design.
- Complete electrical installations with qualified
electricians. - Document commissioning information as a part of
the original equipment file.
28Corrosion Control Monitoring
- Quality Control Requirements, Internal Surface
- Delay work initiation pending review of design
package by coating inspector. - Protect coating material from weather.
- Prepare surface for coating per manufacturers
recommendation immediately before coating
installation. - Follow manufacturers recommendation for dew
point and humidity.
29Corrosion Control Monitoring
- OPERATIONS
- Perform cathodic protection surveys annually in
accordance with Company CP procedure. - Monitor bonding and test stations annually.
- Read and record rectifier output monthly with
changes reported to the SR. Inspector for
evaluation and action. - Correct deficiencies in a timely manner.
30Corrosion Control Monitoring
- MAINTENANCE
- Test rectifier stacks for proper performance
annually. - Check anode bed resistance annually.
- Check insulating flanges and spools annually.
- Document all maintenance tests and add to the
equipment file.
31Corrosion Control MonitoringAppendices
- A - Coating Reference Index
- B - Surface Preparation
- C - Sample Data Sheets
- Rectifier Data Sheet
- Anode Bed Data Sheet
- Galvanic Anode Data Sheet
- Potential Survey Data Sheet
- Predesign Testing