Title: Heating and Air Conditioning I
1Heating and Air Conditioning I
- Principles of Heating, Ventilating and Air
Conditioning - R.H. Howell, H.J. Sauer, and W.J. Coad
- ASHRAE, 2005
basic textbook/reference material For ME 421 John
P. Renie Adjunct Professor Spring 2009
2Chapter 3 Basic HVAC Calculations
- Applying Thermodynamics to HVAC Processes
- Looking at a simplified (but complete)
air-conditioning system - Terminology qsensible, mwater, qL, hw, solar
gains - Look at first law of thermodynamics (energy) and
conservation of mass - Air is removed from the room, returned to the
air-conditioning apparatus where it is
reconditioned, and then supplied again to the
room. - Many cases, it is mixed with outside air required
for ventilation - Outdoor air (o) is mixed with return air (r) from
the room and enters the apparatus at condition
(m) - Air flows through the conditioner and is supplied
to the space (s). - The air supplied to the space absorbs heat qs and
moisture mw, and the cycle continues.
3Chapter 3 Basic HVAC Calculations
- Applying Thermodynamics to HVAC Processes
4Chapter 3 Basic HVAC Calculations
- Applying Thermodynamics to HVAC Processes
5Chapter 3 Basic HVAC Calculations
- Applying Thermodynamics to HVAC Processes
6Chapter 3 Basic HVAC Calculations
- Absorption of Space Heat and Moisture Gains
- AC usually reduces to determining the quantity of
moist air that must supplied and the condition it
must have to remove given amounts of energy and
water from the space to be withdrawn at a
specified condition. - Sensible heat gain addition of energy only
not wrt water
7Chapter 3 Basic HVAC Calculations
- Heating or Cooling of Air without moisture gain
or loss straight line on psychrometric chart
since humidity ratio is constant
8Chapter 3 Basic HVAC Calculations
- Cooling and Dehumidifying Air
- Moist air brought down below its dew point
temperature some of the water will condense and
leaves the air stream - Assume condensed water is cooled to the final air
temperature before draining from the system
9Chapter 3 Basic HVAC Calculations
- Cooling and Dehumidifying Air
10Chapter 3 Basic HVAC Calculations
- Cooling and Dehumidifying Air
- Moist air brought down below its dew point
temperature some of the water will condense and
leaves the air stream - Assume condensed water is cooled to the final air
temperature before draining from the system - Cooling and dehumidifying process involves both
sensible heat transfer and latent heat transfer
where sensible heat transfer is associated with
the decrease in dry-bulb temperature and the
latent heat transfer is associated with the
decrease in humidity ratio.
11Chapter 3 Basic HVAC Calculations
- Heating and Humidifying Air
12Chapter 3 Basic HVAC Calculations
- Adiabatic Mixing of Two Streams of Air
13Chapter 3 Basic HVAC Calculations
- Adiabatic Mixing of Moist Air with Injected Water
14Chapter 3 Basic HVAC Calculations
15Chapter 3 Basic HVAC Calculations
- Approximate Equations Using Volume Flow Rates
- Since volumes of air change need to make
calculations with mass of dry air instead of
volume. But volumetric flow rates define
selection of fans, ducts, coils, etc. - Use volume while still considering mass by using
volume rates based on standard air conditions - Dry air at 20 oC and 101.325 kPa (68 oF and 14.7
psia) - Density is 1.204 kg/m3 (0.075 lb/ft3) dry air
- Specific volume is 0.83 m3/kg (13.3 ft3/lb) dry
air - Saturated air at 15 oC has about same density and
volume - Need to convert actual volumetric flow conditions
to standard - Say you need 1,000 cfm outside air rate at
standard conditions - Outside measured at 35 oC dry bulb and 23.8 oC
wet bulb corresponding to a specific volume of
14.3 ft3/lb. - Then, the actual flow rate would be 1,000
(14.3/13.3) 1,080 cfm - 1,000/13.3 1,080/14.3 mass rate (lb/min) of
moist air
16Chapter 3 Basic HVAC Calculations
- Sensible heat gain corresponding to the change of
dry-bulb temperature for a given airflow (at
standard conditions)
17Chapter 3 Basic HVAC Calculations
- Latent heat gain corresponding to the change of
humidity ratio W for a given airflow (at standard
conditions). - The latent heat gain in Watts (Btu/h) as a result
of a difference in humidity ratio DW between the
incoming and leaving air flowing at standard
conditions.
18Chapter 3 Basic HVAC Calculations
- Total heat gain corresponding to the change of
dry-bulb temperature and humidity ratio W for a
given airflow (at standard conditions). - The total heat gain in Watts (Btu/h) as a result
of a difference in enthalpy Dh between the
incoming and leaving air flowing at standard
conditions.
19Chapter 3 Basic HVAC Calculations
- Total heat gain corresponding to the change of
dry-bulb temperature and humidity ratio W for a
given airflow (at standard conditions).
20Chapter 3 Basic HVAC Calculations
- Single-Path Systems
- Simplest form of all-air HVAC system serving a
single temperature control zone - Responds to one set of space conditions, where
conditions vary uniformly and the load is
stable. - Schematic of system return fan necessary under
certain conditions of Dp. - Need for reheat necessary to control humidity
independent of the temperature requirements. - Equations for single-path systems air supplied
must be adequate to take care of each rooms peak
load conditions. Peak loads may be governed by
sensible or latent room cooling loads, heating
loads, outdoor air requirements, air motion, and
exhaust. let us look at each of these loads and
what air volume is required to satisfy these
demands.
21Chapter 3 Basic HVAC Calculations
- Single-Path Systems - schematic
22Chapter 3 Basic HVAC Calculations
- Single-Path Systems equations for supply air
23Chapter 3 Basic HVAC Calculations
- Single-Path Systems equations for supply air
24Chapter 3 Basic HVAC Calculations
- Single-Path Systems supply air for ventilation
- Supply air for ventilation needed when the
amount of outside air is not adequate - Supply air not adequate for the amount of exhaust
makeup required no return air comes from the
room and entire volume of make-up ventilation air
becomes an outside air burden to system - Desired air exchange rate not satisfied supply
air is determined - Desired air movement not satisfied, based on area
index parameter, K. - Each of the above conditions are used at
different times Case 1 when outside air
governs, Cases 3 and 4 when air movement governs,
and Case 2 when exhaust governs.
25Chapter 3 Basic HVAC Calculations
- Single-Path Systems Example Problem 3-3
26Chapter 3 Basic HVAC Calculations
- Single-Path Systems Example Problem 3-3
27Chapter 3 Basic HVAC Calculations
- Single-Path Systems Example Problem 3-3
28Chapter 3 Basic HVAC Calculations
- Single-Path Systems Example Problem 3-3
29Chapter 3 Basic HVAC Calculations
- Single-Path Systems Cycle Diagram
30Chapter 3 Basic HVAC Calculations
- Single-Path Systems Cycle Diagram
- Each state point is identified both in summer and
winter - Change of Dt is result of sensible heat loss or
gain, qS - Change in DW is result of latent heat loss or
gain, gL - All return air is assumed to pass from the room
through a hung-ceiling return air plenum - Supply air CFMS at the fan discharge temperature
tsf (summer mode) absorbs the transmitted supply
duct heat qsd and supply air fan velocity
pressure energy qsf,vp thereby raising the
temperature to ts
31Chapter 3 Basic HVAC Calculations
- Single-Path Systems Cycle Diagram
- Room supply air absorbs room sensible and latent
heat qSR and qLR along the room sensible heat
factor (SHR) line s-R, reaching the desired room
state, tR and WR.
32Chapter 3 Basic HVAC Calculations
- Single-Path Systems Cycle Diagram
- Room (internal) sensible loads which determine
the CFMs consist of
33Chapter 3 Basic HVAC Calculations
- Single-Path Systems Cycle Diagram
34Chapter 3 Basic HVAC Calculations
- Single-Path Systems Psychrometric Representation
35Chapter 3 Basic HVAC Calculations
- Single-Path Systems Psychrometric Representation
36Chapter 3 Basic HVAC Calculations
- Single-Path System - Psychrometric Representation
37Chapter 3 Basic HVAC Calculations
- Single-Path System Sensible Heat Factor (Ratio)
- Sensible heat factor (ratio), SHF or SHR, is the
ratio of sensible heat for a process to the total
of sensible and latent heat for the process. - The sensible and latent combined is referred to
as the total heat - On psychrometric chart, the protractor provides
this ratio and may be used to establish the
process line for changes in the conditions of the
air across the room or the conditioner on the
chart - The supply air to a conditioned space must have
the capabilty to offset both the rooms sensible
and latent heat loads. - Connecting the room and supply points with a
straight line provides the sensible heat factor
condition. The conditioner provides the
simultaneous cooling and dehumidifying that
occurs. - Horizontal line would be SHF 0.0 (only
sensible) - Line with SHF 0.5 would be half sensible and
half latent
38Chapter 3 Basic HVAC Calculations
- Single-Path System Final Example
39Chapter 3 Basic HVAC Calculations
- Single-Path System Final Example
- Sensible and latent loads given
- Room Conditions (75 oF and 55 RH) Supply at
58 oF - Outside Conditions 96 oF DB, 77 oF WB and 20
of total flow
40Chapter 3 Basic HVAC Calculations
- Single-Path System Final Example
41Chapter 3 Basic HVAC Calculations
- Single-Path System Final Example
42Chapter 3 Basic HVAC Calculations
- Single-Path System Final Example
43Chapter 3 Basic HVAC Calculations
- Single-Path System Final Example
44Chapter 3 Basic HVAC Calculations
- Single-Path System Final Example