Heating and Air Conditioning I - PowerPoint PPT Presentation

1 / 44
About This Presentation
Title:

Heating and Air Conditioning I

Description:

Chapter 3 Basic HVAC Calculations Single-Path Systems Example Problem 3-3 Chapter 3 Basic HVAC Calculations Single-Path Systems ... – PowerPoint PPT presentation

Number of Views:417
Avg rating:3.0/5.0
Slides: 45
Provided by: engrIpfw
Category:

less

Transcript and Presenter's Notes

Title: Heating and Air Conditioning I


1
Heating and Air Conditioning I
  • Principles of Heating, Ventilating and Air
    Conditioning
  • R.H. Howell, H.J. Sauer, and W.J. Coad
  • ASHRAE, 2005

basic textbook/reference material For ME 421 John
P. Renie Adjunct Professor Spring 2009
2
Chapter 3 Basic HVAC Calculations
  • Applying Thermodynamics to HVAC Processes
  • Looking at a simplified (but complete)
    air-conditioning system
  • Terminology qsensible, mwater, qL, hw, solar
    gains
  • Look at first law of thermodynamics (energy) and
    conservation of mass
  • Air is removed from the room, returned to the
    air-conditioning apparatus where it is
    reconditioned, and then supplied again to the
    room.
  • Many cases, it is mixed with outside air required
    for ventilation
  • Outdoor air (o) is mixed with return air (r) from
    the room and enters the apparatus at condition
    (m)
  • Air flows through the conditioner and is supplied
    to the space (s).
  • The air supplied to the space absorbs heat qs and
    moisture mw, and the cycle continues.

3
Chapter 3 Basic HVAC Calculations
  • Applying Thermodynamics to HVAC Processes

4
Chapter 3 Basic HVAC Calculations
  • Applying Thermodynamics to HVAC Processes

5
Chapter 3 Basic HVAC Calculations
  • Applying Thermodynamics to HVAC Processes

6
Chapter 3 Basic HVAC Calculations
  • Absorption of Space Heat and Moisture Gains
  • AC usually reduces to determining the quantity of
    moist air that must supplied and the condition it
    must have to remove given amounts of energy and
    water from the space to be withdrawn at a
    specified condition.
  • Sensible heat gain addition of energy only
    not wrt water

7
Chapter 3 Basic HVAC Calculations
  • Heating or Cooling of Air without moisture gain
    or loss straight line on psychrometric chart
    since humidity ratio is constant

8
Chapter 3 Basic HVAC Calculations
  • Cooling and Dehumidifying Air
  • Moist air brought down below its dew point
    temperature some of the water will condense and
    leaves the air stream
  • Assume condensed water is cooled to the final air
    temperature before draining from the system

9
Chapter 3 Basic HVAC Calculations
  • Cooling and Dehumidifying Air

10
Chapter 3 Basic HVAC Calculations
  • Cooling and Dehumidifying Air
  • Moist air brought down below its dew point
    temperature some of the water will condense and
    leaves the air stream
  • Assume condensed water is cooled to the final air
    temperature before draining from the system
  • Cooling and dehumidifying process involves both
    sensible heat transfer and latent heat transfer
    where sensible heat transfer is associated with
    the decrease in dry-bulb temperature and the
    latent heat transfer is associated with the
    decrease in humidity ratio.

11
Chapter 3 Basic HVAC Calculations
  • Heating and Humidifying Air

12
Chapter 3 Basic HVAC Calculations
  • Adiabatic Mixing of Two Streams of Air

13
Chapter 3 Basic HVAC Calculations
  • Adiabatic Mixing of Moist Air with Injected Water

14
Chapter 3 Basic HVAC Calculations
  • Moving Air

15
Chapter 3 Basic HVAC Calculations
  • Approximate Equations Using Volume Flow Rates
  • Since volumes of air change need to make
    calculations with mass of dry air instead of
    volume. But volumetric flow rates define
    selection of fans, ducts, coils, etc.
  • Use volume while still considering mass by using
    volume rates based on standard air conditions
  • Dry air at 20 oC and 101.325 kPa (68 oF and 14.7
    psia)
  • Density is 1.204 kg/m3 (0.075 lb/ft3) dry air
  • Specific volume is 0.83 m3/kg (13.3 ft3/lb) dry
    air
  • Saturated air at 15 oC has about same density and
    volume
  • Need to convert actual volumetric flow conditions
    to standard
  • Say you need 1,000 cfm outside air rate at
    standard conditions
  • Outside measured at 35 oC dry bulb and 23.8 oC
    wet bulb corresponding to a specific volume of
    14.3 ft3/lb.
  • Then, the actual flow rate would be 1,000
    (14.3/13.3) 1,080 cfm
  • 1,000/13.3 1,080/14.3 mass rate (lb/min) of
    moist air

16
Chapter 3 Basic HVAC Calculations
  • Sensible heat gain corresponding to the change of
    dry-bulb temperature for a given airflow (at
    standard conditions)

17
Chapter 3 Basic HVAC Calculations
  • Latent heat gain corresponding to the change of
    humidity ratio W for a given airflow (at standard
    conditions).
  • The latent heat gain in Watts (Btu/h) as a result
    of a difference in humidity ratio DW between the
    incoming and leaving air flowing at standard
    conditions.

18
Chapter 3 Basic HVAC Calculations
  • Total heat gain corresponding to the change of
    dry-bulb temperature and humidity ratio W for a
    given airflow (at standard conditions).
  • The total heat gain in Watts (Btu/h) as a result
    of a difference in enthalpy Dh between the
    incoming and leaving air flowing at standard
    conditions.

19
Chapter 3 Basic HVAC Calculations
  • Total heat gain corresponding to the change of
    dry-bulb temperature and humidity ratio W for a
    given airflow (at standard conditions).

20
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems
  • Simplest form of all-air HVAC system serving a
    single temperature control zone
  • Responds to one set of space conditions, where
    conditions vary uniformly and the load is
    stable.
  • Schematic of system return fan necessary under
    certain conditions of Dp.
  • Need for reheat necessary to control humidity
    independent of the temperature requirements.
  • Equations for single-path systems air supplied
    must be adequate to take care of each rooms peak
    load conditions. Peak loads may be governed by
    sensible or latent room cooling loads, heating
    loads, outdoor air requirements, air motion, and
    exhaust. let us look at each of these loads and
    what air volume is required to satisfy these
    demands.

21
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems - schematic

22
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems equations for supply air

23
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems equations for supply air

24
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems supply air for ventilation
  • Supply air for ventilation needed when the
    amount of outside air is not adequate
  • Supply air not adequate for the amount of exhaust
    makeup required no return air comes from the
    room and entire volume of make-up ventilation air
    becomes an outside air burden to system
  • Desired air exchange rate not satisfied supply
    air is determined
  • Desired air movement not satisfied, based on area
    index parameter, K.
  • Each of the above conditions are used at
    different times Case 1 when outside air
    governs, Cases 3 and 4 when air movement governs,
    and Case 2 when exhaust governs.

25
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Example Problem 3-3

26
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Example Problem 3-3

27
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Example Problem 3-3

28
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Example Problem 3-3

29
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Cycle Diagram

30
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Cycle Diagram
  • Each state point is identified both in summer and
    winter
  • Change of Dt is result of sensible heat loss or
    gain, qS
  • Change in DW is result of latent heat loss or
    gain, gL
  • All return air is assumed to pass from the room
    through a hung-ceiling return air plenum
  • Supply air CFMS at the fan discharge temperature
    tsf (summer mode) absorbs the transmitted supply
    duct heat qsd and supply air fan velocity
    pressure energy qsf,vp thereby raising the
    temperature to ts

31
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Cycle Diagram
  • Room supply air absorbs room sensible and latent
    heat qSR and qLR along the room sensible heat
    factor (SHR) line s-R, reaching the desired room
    state, tR and WR.

32
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Cycle Diagram
  • Room (internal) sensible loads which determine
    the CFMs consist of

33
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Cycle Diagram

34
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Psychrometric Representation

35
Chapter 3 Basic HVAC Calculations
  • Single-Path Systems Psychrometric Representation

36
Chapter 3 Basic HVAC Calculations
  • Single-Path System - Psychrometric Representation

37
Chapter 3 Basic HVAC Calculations
  • Single-Path System Sensible Heat Factor (Ratio)
  • Sensible heat factor (ratio), SHF or SHR, is the
    ratio of sensible heat for a process to the total
    of sensible and latent heat for the process.
  • The sensible and latent combined is referred to
    as the total heat
  • On psychrometric chart, the protractor provides
    this ratio and may be used to establish the
    process line for changes in the conditions of the
    air across the room or the conditioner on the
    chart
  • The supply air to a conditioned space must have
    the capabilty to offset both the rooms sensible
    and latent heat loads.
  • Connecting the room and supply points with a
    straight line provides the sensible heat factor
    condition. The conditioner provides the
    simultaneous cooling and dehumidifying that
    occurs.
  • Horizontal line would be SHF 0.0 (only
    sensible)
  • Line with SHF 0.5 would be half sensible and
    half latent

38
Chapter 3 Basic HVAC Calculations
  • Single-Path System Final Example

39
Chapter 3 Basic HVAC Calculations
  • Single-Path System Final Example
  • Sensible and latent loads given
  • Room Conditions (75 oF and 55 RH) Supply at
    58 oF
  • Outside Conditions 96 oF DB, 77 oF WB and 20
    of total flow

40
Chapter 3 Basic HVAC Calculations
  • Single-Path System Final Example

41
Chapter 3 Basic HVAC Calculations
  • Single-Path System Final Example

42
Chapter 3 Basic HVAC Calculations
  • Single-Path System Final Example

43
Chapter 3 Basic HVAC Calculations
  • Single-Path System Final Example

44
Chapter 3 Basic HVAC Calculations
  • Single-Path System Final Example
Write a Comment
User Comments (0)
About PowerShow.com