ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES - PowerPoint PPT Presentation

About This Presentation
Title:

ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES

Description:

environmental engineering concrete structures ce 498 design project november 16, 21, 2006 outline introduction loading conditions design method wall thickness ... – PowerPoint PPT presentation

Number of Views:138
Avg rating:3.0/5.0
Slides: 35
Provided by: engineeri46
Category:

less

Transcript and Presenter's Notes

Title: ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES


1
ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES
  • CE 498 Design Project
  • November 16, 21, 2006

2
OUTLINE
  • INTRODUCTION
  • LOADING CONDITIONS
  • DESIGN METHOD
  • WALL THICKNESS
  • REINFORCEMENT
  • CRACK CONTROL

3
INTRODUCTION
  • Conventionally reinforced circular concrete tanks
    have been used extensively. They will be the
    focus of our lecture today
  • Structural design must focus on both the strength
    and serviceability. The tank must withstand
    applied loads without cracks that would permit
    leakage.
  • This is achieved by
  • Providing proper reinforcement and distribution
  • Proper spacing and detailing of construction
    joints
  • Use of quality concrete placed using proper
    construction procedures
  • A thorough review of the latest report by ACI 350
    is important for understanding the design of
    tanks.

4
LOADING CONDITIONS
  • The tank must be designed to withstand the loads
    that it will be subjected to during many years of
    use. Additionally, the loads during construction
    must also be considered.
  • Loading conditions for partially buried tank.
  • The tank must be designed and detailed to
    withstand the forces from each of these loading
    conditions

5
LOADING CONDITIONS
  • The tank may also be subjected to uplift forces
    from hydrostatic pressure at the bottom when
    empty.
  • It is important to consider all possible loading
    conditions on the structure.
  • Full effects of the soil loads and water pressure
    must be designed for without using them to
    minimize the effects of each other.
  • The effects of water table must be considered for
    the design loading conditions.

6
DESIGN METHODS
  • Two approaches exist for the design of RC members
  • Strength design, and allowable stress design.
  • Strength design is the most commonly adopted
    procedure for conventional buildings
  • The use of strength design was considered
    inappropriate due to the lack of reliable
    assessment of crack widths at service loads.
  • Advances in this area of knowledge in the last
    two decades has led to the acceptance of strength
    design methods
  • The recommendations for strength design suggest
    inflated load factors to control service load
    crack widths in the range of 0.004 0.008 in.

7
Design Methods
  • Service state analyses of RC structures should
    include computations of crack widths and their
    long term effects on the structure durability and
    functional performance.
  • The current approach for RC design include
    computations done by a modified form of elastic
    analysis for composite reinforced steel/concrete
    systems.
  • The effects of creep, shrinkage, volume changes,
    and temperature are well known at service level
  • The computed stresses serve as the indices of
    performance of the structure.

8
DESIGN METHODS
  • The load combinations to determine the required
    strength (U) are given in ACI 318. ACI 350
    requires two modifications
  • Modification 1 the load factor for lateral
    liquid pressure is taken as 1.7 rather than 1.4.
    This may be over conservative due to the fact
    that tanks are filled to the top only during leak
    testing or accidental overflow
  • Modification 2 The members must be designed to
    meet the required strength. The ACI required
    strength U must be increased by multiplying with
    a sanitary coefficient
  • The increased design loads provide more
    conservative design with less cracking.
  • Required strength Sanitary coefficient X U
  • Where, sanitary coefficient 1.3 for flexure,
    1.65 for direct tension, and 1.3 for shear beyond
    the capacity provided by the concrete.

9
WALL THICKNESS
  • The walls of circular tanks are subjected to ring
    or hoop tension due to the internal pressure and
    restraint to concrete shrinkage.
  • Any significant cracking in the tank is
    unacceptable.
  • The tensile stress in the concrete (due to ring
    tension from pressure and shrinkage) has to kept
    at a minimum to prevent excessive cracking.
  • The concrete tension strength will be assumed 10
    fc in this document.
  • RC walls 10 ft. or higher shall have a minimum
    thickness of 12 in.
  • The concrete wall thickness will be calculated as
    follows

10
WALL THICKNESS
  • Effects of shrinkage
  • Figure 2(a) shows a block of concrete with a
    re-bar. The block height is 1 ft, t corresponds
    to the wall thickness, the steel area is As, and
    the steel percentage is r.
  • Figure 2(b) shows the behavior of the block
    assuming that the re-bar is absent. The block
    will shorten due to shrinkage. C is the shrinkage
    per unit length.
  • Figure 2(c) shows the behavior of the block when
    the re-bar is present. The re-bar restrains some
    shortening.
  • The difference in length between Fig.2(b) and
    2(c) is xC, an unknown quantity.

11
WALL THICKNESS
  • The re-bar restrains shrinkage of the concrete.
    As a result, the concrete is subjected to
    tension, the re-bar to compression, but the
    section is in force equilibrium
  • Concrete tensile stress is fcs xCEc
  • Steel compressive stress is fss (1-x)CEs
  • Section force equilibrium. So, rfssfcs
  • Solve for x from above equation for force
    equilibrium
  • The resulting stresses are
  • fssCEs1/(1nr) and fcsCEsr/(1nr)
  • The concrete stress due to an applied ring or
    hoop tension of T will be equal to
  • T Ec/(EcAcEsAs) T 1/AcnAs
    T/Ac(1nr)
  • The total concrete tension stress CEsAs
    T/AcnAs

12
WALL THICKNESS
  • The usual procedure in tank design is to provide
    horizontal steel As for all the ring tension at
    an allowable stress fs as though designing for a
    cracked section.
  • Assume AsT/fs and realize Ac12t
  • Substitute in equation on previous slide to
    calculate tension stress in the concrete.
  • Limit the max. concrete tension stress to fc
    0.1 fc
  • Then, the wall thickness can be calculated as
  • t CEsfsnfc/12fcfs T
  • This formula can be used to estimate the wall
    thickness
  • The values of C, coefficient of shrinkage for RC
    is in the range of 0.0002 to 0.0004.
  • Use the value of C0.0003
  • Assume fs allowable steel tension 18000 psi
  • Therefore, wall thickness t0.0003 T

13
WALL THICKNESS
  • The allowable steel stress fs should not be made
    too small. Low fs will actually tend to increase
    the concrete stress and potential cracking.
  • For example, the concrete stress fc
    CEsfs/AcfsnTT
  • For the case of T24,000 lb, n8, Es29106 psi,
    C0.0003 and Ac12 x 10 120 in3
  • If the allowable steel stress is reduced from
    20,000 psi to 10,000 psi, the resulting concrete
    stress is increased from 266 psi to 322 psi.
  • Desirable to use a higher allowable steel stress.

14
REINFORCEMENT
  • The amount size and spacing of reinforcement has
    a great effect on the extent of cracking.
  • The amount must be sufficient for strength and
    serviceability including temperature and
    shrinkage effects
  • The amount of temperature and shrinkage
    reinforcement is dependent on the length between
    construction joints

15
REINFORCEMENT
  • The size of re-bars should be chosen recognizing
    that cracking can be better controlled by using
    larger number of small diameter bars rather than
    fewer large diameter bars
  • The size of reinforcing bars should not exceed
    11. Spacing of re-bars should be limited to a
    maximum of 12 in. Concrete cover should be at
    least 2 in.
  • In circular tanks the locations of horizontal
    splices should be staggered by not less than one
    lap length or 3 ft.
  • Reinforcement splices should confirm to ACI 318
  • Chapter 12 of ACI 318 for determining splice
    lengths.
  • The length depends on the class of splice, clear
    cover, clear distance between adjacent bars, and
    the size of the bar, concrete used, bar coating
    etc.

16
CRACK CONTROL
  • Crack widths must be minimized in tank walls to
    prevent leakage and corrosion of reinforcement
  • A criterion for flexural crack width is provided
    in ACI 318. This is based on the Gergely-Lutz
    equation zfs(dcA)1/3
  • Where z quantity limiting distribution of
    flexural re-bar
  • dc concrete cover measured from extreme tension
    fiber to center of bar located closest.
  • A effective tension area of concrete
    surrounding the flexural tension reinforcement
    having the same centroid as the reinforcement,
    divided by the number of bars.

17
CRACK CONTROL
  • In ACI 350, the cover is taken equal to 2.0 in.
    for any cover greater than 2.0 in.
  • Rearranging the equation and solving for the
    maximum bar spacing give max spacing z3/(2 dc2
    fs3)
  • Using the limiting value of z given by ACI 350,
    the maximum bar spacing can be computed
  • For ACI 350, z has a limiting value of 115 k/in.
  • For severe environmental exposures, z 95 k/in.

18
ANALYSIS OF VARIOUS TANKS
  • Wall with fixed base and free top triangular
    load
  • Wall with hinged base and free top triangular
    load and trapezoidal load
  • Wall with shear applied at top
  • Wall with shear applied at base
  • Wall with moment applied at top
  • Wall with moment applied at base

19
CIRCULAR TANK ANALYSIS
  • In practice, it would be rare that a base would
    be fixed against rotation and such an assumption
    would lead to an improperly designed wall.
  • For the tank structure, assume
  • Height H 20 ft.
  • Diameter of inside D 54 ft.
  • Weight of liquid w 62.5 lb/ft3
  • Shrinkage coefficient C 0.0003
  • Elasticity of steel Es 29 x 106 psi
  • Ratio of Es/Ec n 8
  • Concrete compressive strength fc 4000 psi
  • Yield strength of reinforcement fy 60,000 psi

20
CIRCULAR TANK ANALYSIS
  • It is difficult to predict the behavior of the
    subgrade and its effect upon restraint at the
    base. But, it is more reasonable to assume that
    the base is hinged rather than fixed, which
    results in more conservative design.
  • For a wall with a hinged base and free top, the
    coefficients to determine the ring tension,
    moments, and shears in the tank wall are shown in
    Tables A-5, A-7, and A-12 of the Appendix
  • Each of these tables, presents the results as
    functions of H2/Dt, which is a parameter.
  • The values of thickness t cannot be calculated
    till the ring tension T is calculated.
  • Assume, thickness t 10 in.
  • Therefore, H2/Dt (202)/(54 x 10/12) 8.89
    (approx. 9 in.)

21
Table A-5 showing the ring tension values
22
Table A-7, A-12 showing the moment and shear
23
CIRCULAR TANK ANALYSIS
  • In these tables, 0.0 H corresponds to the top of
    the tank, and 1.0 H corresponds to the bottom of
    the tank.
  • The ring tension per foot of height is computed
    by multiplying wu HR by the coefficients in Table
    A-5 for the values of H2/Dt9.0
  • wu for the case of ring tension is computed as
  • wu sanitary coefficient x (1.7 x Lateral
    Forces)wu 1.65 x (1.7 x 62.5) 175.3 lb/ft3
  • Therefore, wu HR 175.3 x 20 x 54/2 94, 662
    lb/ft3
  • The value of wu HR corresponds to the behavior
    where the base is free to slide. Since, it cannot
    do that, the value of wu HR must be multiplied by
    coefficients from Table A-5

24
CIRCULAR TANK ANALYSIS
  • A plus sign indicates tension, so there is a
    slight compression at the top, but it is very
    small.
  • The ring tension is zero at the base since it is
    assumed that the base has no radial displacement
  • Figure compares the ring tension for tanks with
    free sliding base, fixed base, and hinged base.

25
CIRCULAR TANK ANALYSIS
  • Which case is conservative? (Fixed or hinged
    base)
  • The amount of ring steel required is given by
  • As maximum ring tension / (0.9 Fy)
  • As 67494/(0.9 60000) 1.25 in2/ft.
  • Therefore at 0.7H use 6bars spaced at 8 in. on
    center in two curtains.
  • Resulting As 1.32in2/ft.
  • The reinforcement along the height of the wall
    can be determined similarly, but it is better to
    have the same bar and spacing.
  • Concrete cracking check
  • The maximum tensile stress in the concrete under
    service loads including the effects of shrinkage
    is
  • fc CEsAs Tmax, unfactored/AcnAs 272
    psi lt 400 psi
  • Therefore, adequate

26
CIRCULAR TANK ANALYSIS
  • The moments in vertical wall strips that are
    considered 1 ft. wide are computed by multiplying
    wuH3 by the coefficients from table A-7.
  • The value of wu for flexure sanitary
    coefficient x (1.7 x lateral forces)
  • Therefore, wu 1.3 x 1.7 x 62.5 138.1 lb/ft3
  • Therefore wuH3 138.1 x 203 1,104,800 ft-lb/ft
  • The computed moments along the height are shown
    in the Table.
  • The figure includes the moment for both the
    hinged and fix conditions

27
CIRCULAR TANK ANALYSIS
  • The actual restraint is somewhere in between
    fixed and hinged, but probably closer to hinged.
  • For the exterior face, the hinged condition
    provides a conservative although not wasteful
    design
  • Depending on the fixity of the base, reinforcing
    may be required to resist moment on the interior
    face at the lower portion of the wall.
  • The required reinforcement for the outside face
    of the wall for a maximum moment of 5,524
    ft-lb/ft. is
  • Mu/(f fc bd2) 0.0273 (where d t cover
    dbar/2)
  • From the standard design aid of Appendix A, take
    the value of 0.0273 and obtain a value for w from
    the Table.
  • Obtain w0.0278
  • Required As w bdfc/fy 0.167 in2

28
CIRCULAR TANK ANALYSIS
  • r0.167/(12 x 7.5) 0.00189
  • rmin 200/Fy 0.0033 gt 0.00189
  • Use 5 bars at the maximum allowable spacing of
    12 in.
  • As 0.31 in2 and r 0.0035
  • The shear capacity of a 10 in. wall with fc4000
    psi is
  • Vc 2 (fc)0.5 bwd 11,384 kips
  • Therefore, f Vc 0.85 x 11,284 9676 kips
  • The applied shear is given by multiplying wu H2
    with the coefficient from Table A-12
  • The value of wu is determined with sanitary
    coefficient 1.0 (assuming that no steel rft.
    will be needed)
  • wuH2 1.0 x 1.7 x 62.5 x 202 42,520 kips
  • Applied shear Vu 0.092 x wuH2 3912 kips lt
    fVc

29
RECTANGULAR TANK DESIGN
  • The cylindrical shape is structurally best suited
    for tank construction, but rectangular tanks are
    frequently preferred for specific purposes
  • Rectangular tanks can be used instead of circular
    tanks when the footprint needs to be reduced
  • Rectangular tanks are used where partitions or
    tanks with more than one cell are needed.
  • The behavior of rectangular tanks is different
    from the behavior of circular tanks
  • The behavior of circular tanks is axisymmetric.
    That is the reason for our analysis of only unit
    width of the tank
  • The ring tension in circular tanks was uniform
    around the circumference

30
RECTANGULAR TANK DESIGN
  • The design of rectangular tanks is very similar
    in concept to the design of circular tanks
  • The loading combinations are the same. The
    modifications for the liquid pressure loading
    factor and the sanitary coefficient are the same.
  • The major differences are the calculated moments,
    shears, and tensions in the rectangular tank
    walls.
  • The requirements for durability are the same for
    rectangular and circular tanks. This is related
    to crack width control, which is achieved using
    the Gergely Lutz parameter z.
  • The requirements for reinforcement (minimum or
    otherwise) are very similar to those for circular
    tanks.
  • The loading conditions that must be considered
    for the design are similar to those for circular
    tanks.

31
RECTANGULAR TANK DESIGN
  • The restraint condition at the base is needed to
    determine deflection, shears and bending moments
    for loading conditions.
  • Base restraint conditions considered in the
    publication include both hinged and fixed edges.
  • However, in reality, neither of these two
    extremes actually exist.
  • It is important that the designer understand the
    degree of restraint provided by the reinforcing
    that extends into the footing from the tank wall.
  • If the designer is unsure, both extremes should
    be investigated.
  • Buoyancy Forces must be considered in the design
    process
  • The lifting force of the water pressure is
    resisted by the weight of the tank and the weight
    of soil on top of the slab

32
RECTANGULAR TANK BEHAVIOR
Mx moment per unit width about the x-axis
stretching the fibers in the y direction when the
plate is in the x-y plane. This moment determines
the steel in the y (vertical direction).
My moment per unit width about the y-axis
stretching the fibers in the x direction when the
plate is in the x-y plane. This moment determines
the steel in the x (horizontal direction).
Mz moment per unit width about the z-axis
stretching the fibers in the y direction when the
plate is in the y-z plane. This moment determines
the steel in the y (vertical direction).
33
RECTANGULAR TANK BEHAVIOR
  • Mxy or Myz torsion or twisting moments for
    plate or wall in the x-y and y-z planes,
    respectively.
  • All these moments can be computed using the
    equations
  • Mx(Mx Coeff.) x q a2/1000
  • My(My Coeff.) x q a2/1000
  • Mz(Mz Coeff.) x q a2/1000
  • Mxy(Mxy Coeff.) x q a2/1000
  • Myz(Myz Coeff.) x q a2/1000
  • These coefficients are presented in Tables 2 and
    3 for rectangular tanks
  • The shear in one wall becomes axial tension in
    the adjacent wall. Follow force equilibrium -
    explain in class.

34
RECTANGULAR TANK BEHAVIOR
  • The twisting moment effects such as Mxy may be
    used to add to the effects of orthogonal moments
    Mx and My for the purpose of determining the
    steel reinforcement
  • The Principal of Minimum Resistance may be used
    for determining the equivalent orthogonal moments
    for design
  • Where positive moments produce tension
  • Mtx Mx Mxy
  • Mty My Mxy
  • However, if the calculated Mtx lt 0,
  • then Mtx0 and MtyMy Mxy2/Mx gt 0
  • If the calculated Mty lt 0
  • Then Mty 0 and Mtx Mx Mxy2/My gt 0
  • Similar equations for where negative moments
    produce tension
Write a Comment
User Comments (0)
About PowerShow.com