Basic 12V DC Installations - PowerPoint PPT Presentation

1 / 30
About This Presentation
Title:

Basic 12V DC Installations

Description:

... wire or cable as suggested by the ABYC for the marine environment. ... West Marine lists 4/0 red or black ... West Marine lists 2/0 red or black ... – PowerPoint PPT presentation

Number of Views:158
Avg rating:3.0/5.0
Slides: 31
Provided by: dav5201
Category:

less

Transcript and Presenter's Notes

Title: Basic 12V DC Installations


1
Basic 12V DC Installations
2
Saftey
  • Remove all Metal Jewelry
  • Rings
  • Watches
  • Neck Chains
  • CIRCUMFERENTIAL ELECTRIC BURNS OF THE RING FINGER

3
OHMs Law
  • Ohm's Law defines the relationships between (P)
    power, (E) voltage, (I) current, and (R)
    resistance. One ohm is the resistance value
    through which one volt will maintain a current of
    one ampere. ( I ) Current is what flows on a
    wire or conductor like water flowing down a
    river. Current flows from negative to positive on
    the surface of a conductor. Current is measured
    in (A) amperes or amps. ( E ) Voltage is the
    difference in electrical potential between two
    points in a circuit. It's the push or pressure
    behind current flow through a circuit, and is
    measured in (V) volts. ( R ) Resistance
    determines how much current will flow through a
    component. Resistors are used to control voltage
    and current levels. A very high resistance allows
    a small amount of current to flow. A very low
    resistance allows a large amount of current to
    flow. Resistance is measured in ohms. ( P )
    Power is the amount of current times the voltage
    level at a given point measured in wattage or
    watts.

4
OHMs Law
E
Volts
I R
Ohms
Amps
5
OHMs Law
P
Watts
I E
Volts
Amps
6
(No Transcript)
7
Plumbing Analogy
  • Battery Source of water at a certain Pressure
  • Volts Pressure like PSI (Pounds per Square
    inch)
  • Current Flow/ How much Water is actually moving
    GPH
  • Resistance disruptions to the flow/ valves,
    reducers, motors, etc.

8
Load
12V
Valve
9
Series Circuit

12V
-
5W
5w/12v .416A
.416A
10
Parallel Circuit

12V
-
5w
5w
5w
5w
.42 A
.84 A
1.26 A
1.68 A
.42 A
.42 A
.42 A
.42 A
11
Electrical concerns for any installation on a
boat?
  • What is the max rated current draw of the device?
  • What is the round trip length for the wire run,
    from the batteries to the load and back?
  • What amount of Voltage drop is acceptable?
  • What gauge wire do I need?
  • How big of a breaker do I need/want?

12
AYBC Standards
  • Properly sizing your wire or cable as suggested
    by the ABYC for the marine environment. These
    standards might be a bit more strict than those
    in the automotive environment however, they err
    on the side of caution and were developed with
    safety in mind.
  • In the boating world it is suggested3 max
    voltage drop for conductors providing power to
    panels and switchboards, navigation lighting,
    bilge blowers, main DC feeders, and any other
    circuit where voltage drop should be kept to a
    minimum10 max voltage drop on conductors used
    for general lighting and other non-critical
    circuits
  • The ampacity (amperage) tables help to choose the
    correct size cable to handle the power load for
    which you are trying to find the correct wiring.
    There are individual tables for single conductor
    and multiple conductor runs as current carrying
    conductors which are bundled together will
    transfer heat to each other in effect reducing
    their safe current handling capabilities.

13
ABYC Standards
  • After calculating the Circular Mil Area (CM), use
    Table B to determine the proper conductor size. 
    The National Fire Protection Agency and Coast
    Guard require that the next larger conductor be
    used when the calculated CM area falls between
    two conductor sizes.
  • CMK x l x L / E
  • CM Circular Mil area of Conductors
  • K 10.75 (Constant representing the mil-foot
    resistance of copper)
  • I Current - amps
  • L Length - feet
  • E Voltage drop at load (in volts)

14
  • For Example...
  • Q.  A bilge pump draws 10 amps.  The positive run
    is 11 feet from the power panel, including the
    float switch.  The negative run is only 10 feet. 
    What size wire?
  • A.  Use the following formula to reach the
    correct answer CM 10.75 x 10 (amps) x 21
    (total length of run) / 0.36 (3 of 12v) 6,271
  • The table below shows that 12 AWG wire has a CM
    area of 6,500 and is the correct choice. However,
    SAE wire has a CM area of only 5,833.  Under NFPA
    and USCG regulations, 10 SAE wire must be used.
  • CM 10.75 x 10 (amps) x 21 (total length of run)
    / 0.96 (3 of 32v) 2,352
  • Ampacity is the ultimate safe current carrying
    capacity of the wire before damage occurs to the
    insulation, without regard to voltage drop!

15
Circular Mils Chart
16
(No Transcript)
17
Wire Sizer
  • Go to WireSizer.xls

18
(No Transcript)
19
Lofrans Progress 2
20
(No Transcript)
21
Lighthouse 1501
22
Assuming 60ft round trip and 100 amps at max
load. What gauge wire is necessary for 3 voltage
drop?
Method 1 Straight run of large cable from the
Batteries to the windlass and back.
Assuming The same run and load what gauge wire is
necessary for 5 voltage drop?
A. 2/0 AWG
A. 4/0 AWG
West Marine lists 4/0 red or black _at_ 17.99 per
foot.
West Marine lists 2/0 red or black _at_ 14.99 per
foot.
Polar Wire lists 4/0 red or black _at_ 5.95 per
foot.
Polar Wire lists 4/0 red or black _at_ 4.02 per
foot.
23
  • 3 drop 60ft of 4/0 _at_ 5.95 per foot 357
  • 5 drop 60ft of 2/0 _at_ 4.02 per foot 241

24
Assuming 40ft round trip to the Fwd battery and a
60amp max current through the ACR. What gauge
wire is necessary for 3 voltage drop?
Method 2 Install a dedicated battery for the
windlass as close as feasible to the windlass and
charge the battery using a Blue sea ACR.
Assuming 20ft round trip to the Windlass and a
100 amp max load. What gauge wire is necessary
for 3 voltage drop?
ACR
A. 2 AWG
A. 1 AWG
Polar Wire lists 2AWG red or black _at_ 2.12 per
foot.
Polar Wire lists 1/0 AWG red or black _at_ 3.12 per
foot. This would be 2.5 Voltage drop. They dont
list 1awg on the site. It would be less..
25
Method 2 - 3
  • 40ft 1/0 awg _at_ 3.12 125
  • 20ft 2 awg _at_2.20 44
  • Battery 100
  • ACR 95

26
(No Transcript)
27
Washdown Pump
28
Washdown pump
29
Washdown Pump
  • Looking at the max distance of 100ft round trip
    and using 12.4 amps at max pressure this is a 20
    voltage drop or 9.6 volts using 12AWG at the
    Pump????? What crap! Use the charts!

30
Trouble Shooting

12V
-
5W
5w/12v .416A
.416A
Write a Comment
User Comments (0)
About PowerShow.com