Progress Report on the DIAMOND Light Source to
the EPICS Meeting Santa Fe May 04
2
Diamond
  • Diamond is the new UK Synchrotron Light Source
  • Located at the Rutherford Appleton Laboratory
    (RAL) Oxfordshire
  • Due online early 2007 ( First beam SR Jan 2006)

3
Diamond Accelerators
Linear accelerator (Linac) 100 MeV
energy Booster synchrotron 100 MeV - 3 GeV 158
m in circumference Storage Ring 3 GeV
energy 562 m in circumference
4
Diamond Building Concepts
Courtesy of Crispin Wride Architectural Design
Studio, JacobsGibb Ltd.
5
Storage Ring Building Jan 2004
6
Storage Ring Building March 2004
7
Booster March 2004
8
Office Block March 2004
9
Controls Group Aerial Photography
Angelos Gonias (pilot) and Yuri Chernousko
(camera operator)
10
Control System Architecture
  • Based on EPICS using Two Layer Model
  • Primary interface to CS through VME IOCs
  • Use VME64x, IP carriers, IP Modules and
    transition board for rear connection
  • Hot Swap capability
  • Will use PLCs to manage interlocks for
    protection
  • Avoids Watch Dogs on IOCs and allow warm reboot
    of IOCs
  • Omron CJ PLCs for low end applications, eg Vac
    Valve control
  • Siemens S7/300 and S7/400 for high end
    applications, eg Linac and Cryoplant
  • Serial Interface to Instrumentation
  • Potentially several thousand
  • Serial support through Stream Device and ORNL
    Serial

11
Hardware
  • Development
  • Linux for Development
  • Running EPICS 3.13.4 but moving to 3.13.9 but
    will also use 3.14.x
  • Currently Tornado 2.02 but moving to Tornado 2.2
    to use MVME5500
  • Consoles
  • PCs running Linux RH 9.0
  • Will support Win2000
  • IOCs
  • VME64x
  • PPC Processor boards
  • Evaluating MVME5500
  • Will use IP carrier and modules
  • Primarily 7 slot crates

12
Generic Work IO Module Procurement
  • Primary CS interface through Industry Pack IO
    Module from Hytec Electronics
  • Included some EPICS support

13
Linac
  • Turn-key contract for 100 MeV Linac with Accel
    Gmb
  • Includes installation and commissioning to a
    performance spec.
  • EPICS Controls included in contract
  • Uses Siemens S7 300 and S7 400 PLCs for control
    and protection of modulators and electron source
  • Interfaced to IOC using Network connection

14
Technical Systems PSUs
  • 4 Large and 434 medium and 780 small PSUs all
    controlled by the PSI designed PSU controller.
  • PSUs interfaced to IOC by high speed point to
    point link and IP modules
  • Procurement Model
  • DLS will design EPICS IOC functionality
  • Large PSUs will be integrated into controls by
    DLS
  • Medium supplies DLS will free issues IOCs, to be
    integrated at part of contract
  • For Small Supplies DLS will design PSUs and
    integrate PSU controllers and IOCs
  • Progress IOC software support for PSI PSU
    controlled tested
  • Simulation model for all PSUs being constructed

15
Technical Systems Diagnostics
  • Electron Beam Position Monitors
  • 207 EBPMS using Libera EBPM Detectors form
    Instrumentation Technology
  • Undersampling of BPM signal and digital detection
    and signal processing within FPGAs
  • Gives three data paths, trading off resolution
    and BW
  • Embedded ARM processor board running Linux and an
    EPICS 3.14 server
  • Network interface for general control
    functionality and other diagnostics and high
    speed SPF modules for global feedback system
  • Other Diagnostics Includes Screens, Current
    transformers and Loss Monitors
  • Screens will use CCD Cameras with FireWire
    interface to EPICS (S Hunts Talk)

16
Technical Systems Vacuum
  • 528 Gauges MKS937A Interfaced through serial
    connections using Stream Device
  • 624 Ion pumps and 60 TSPs controlled by MPCs from
    Gamma Vacuum, interfaced through serial
    connections using ORNL Serial
  • 139 vacuum valves controlled through Omron CJ PLC
    based valve control units
  • Valve Control Units provide vacuum protection and
    interlocking
  • PLCs interfaced through serial connections using
    ORNL Serial to support protocol CRCs
  • Same PLCs used for MPS

17
Technical Systems Girder Motion Control
  • 72 Girders for Storage Ring
  • Each girder has motorised Kinematic mounts to
    provide 5 degree of freedom so enabling auto
    alignment
  • 360 axes of motion control driving concentric
    cams
  • Each cell
  • Three Girders or 15 axes
  • Controlled by two OMS VME 58 controller cards in
    one IOC
  • Procurement Model
  • Turn-key solution from industry based on EPICS
    with industry delivering functionality to
    control each axis and manage protection
  • DLS implements high-level algorithms and tools
    for girder alignment

18
Technical Systems Insertion Device
  • Common motion control system for all permanent
    magnet IDs
  • In-Vacuum and Ex-Vacuum
  • 6 axis motion control using OMS VME58
  • Each beam two independent jacks
  • Each beam has Phase change of magnet array
  • 4 or 8 DC PSUs
  • Synchronous operation of Axis and PSUs
  • Synchronous operation of ID with BL mono
  • Omron CJ PLC based protection sub-system manage
    safe operating window
  • Procurement
  • Contract design of prototype control system by
    industry based on EPICS controls ystem
  • Manufacture of production control systems for
    all In Vac and Outer Vac devices by industry,
    against build to print
  • DLS will provide detailed EPICS controls to synch
    ID to SR Magnetic elements and BL Mono

19
SR RF System
  • 3 SC RF cavities use Siemens S7 PLCs for Cavity
    Cryogenic Control
  • 3 RF amplifier using combined output of
    Inductive Output Tubes and controls based on IOCs
  • Single cryo-plant Siemens S7 PLC

20
Machine Protection System (1)
  • Machine Protection System manages interlocks on a
    global basis to protect components from damage
    caused by
  • Stored beam in the case of
  • loss of cooling
  • loss of vacuum
  • Obstructions in beam path
  • Mis-steering of the beam
  • Other potentially hazardous situations
  • Storage Ring two protection circuits
  • Vessel and Dipole
  • Booster four protection circuits
  • Vessel, Dipole, FQuad and DQuad

21
Control Instrumentation Areas (CIA)
  • CIA per Cell
  • CIAs house instrumentation racks in a clean
    temperature controlled environment
  • IOCs for each technical area
  • Quad/Sext PSUs, Steerer PSUs, BPMS, Vacuum, MPS,
    Girder Alignment, 2x Front Ends, 2x IDs, PSS
  • Design once, build 24
  • CIAs linked to MCR using FOs Cables
  • 2x Computer networks, Timing signals, Reflective
    memory, MPS, Video and Point to Point Analogues
  • Minimise Copper connections CIA to CIA
  • (See Tim Haytons Talk)

22
Recruitment
  • There are the following Vacancies in Diamond
    Controls
  • DIA0058 Software Engineer Control System Toolkit
  • DIA0059 Software Engineer Diagnostics
  • DIA0060 Software Systems Engineer Photon
    Beamlines
  • DIA0057 Electronics Design Engineer FPGAs
  • See http//www.diamond.ac.uk/

23
(No Transcript)