1
Team Green
Speed Control Root Locus Plotting
  • John Barker
  • Keith Skiles
  • John Beverly

UTC ENG 329 March 22, 2006
2
Presentation Purpose
  • Root Locus Plotting
  • Determine various Kc Values for system controller
  • Determine Offsets for Different Kc Values

3
Steady State Operating Curve (SSOC) and FOPDT
Parameters Review
  • System Background Review
  • (Description, SSOC, Step Response)
  • Step Response (Experiment Model)
  • Sine Response (Experiment Model)
  • Bode Plots

4
Aerator Mixer Speed Control System
5
Block Diagram of System
6
SSOC Graph
7
First Order Plus Dead Time(FOPDT) Theory
-t0s
  • System Transfer Function
  • G(s) Ke-to /ts1
  • Parameters
  • t0Dead Time
  • K System Gain
  • t Time Constant

8
Step Response Results
9
Step Response Averages
10
Frequency Response PlotSine Response Freq.
0.3 Amplitude 15
11
Frequency Response Model Conclusions
Frequency Response
Step Response
K 17.3 rpm/ to .2s t .17s
K 17.1 rpm/ to0.14s t 0.19s
12
Bode Plot Model
Baseline Modeling Variables
t00.14s K 17.1 rpm/ t 0.19s
13
Bode Plot AR
14
Bode Plot Phase Angle
15
System Conclusions
Order 1 fu 2.3 Hz Kcu 0.2 ( / RPM)
K 17.1 rpm/ to0.14s t 0.19s
16
Feedback Control
17
Root Locus Parameters
  • KCD Critically Damped
  • KQD Value of KC that produces one-quarter
    oscillating decay
  • KCU Ultimate Controller Gain

18
z Locations
All Kc Units are / RPM
19
Results from Root Locus
  • Ultimate KCU 0.16
  • Quarter Decay KQD 0.10
  • Critically Damping KCD 0.002
  • Underdamped 0.002ltKClt0.16
  • Overdamped 0ltKClt0.002
  • Ultimate Frequency fu 2.3 Hz
  • All Units unless noted are ( / RPM)

20
Offset
  • Steady State Error
  • Steady state deviation of controlled variable
    from the set point

21
Offset for KCD
Mbar 81
22
Offset for Decay Ratio of 1/500
23
Offset for Decay Ratio of 1/10
?r -400 RPM
24
Offset for Decay Ratio of 1/4
25
Offset for KCU
?r -400 RPM
26
Offsets for Different Kc Values
27
Final Values for Set Point of 1400 RPM
28
Final Values for a Set Point of 1400 RPM
29
Conclusions
  • For KC Needed
  • Overdamped 0ltKClt0.002
  • Critically Damped KC 0.002
  • 1/500 Decay KC 0.03
  • 1/10 Decay KC 0.08
  • 1/4 Decay KC 0.10
  • All Units are ( / RPM)