Title: Change out Duct Testing
1Welcome
Duct Testing Requirements forHVAC System
Change-outs
2- This program is funded by California utility
customers and administered by Pacific Gas and
Electric Company, under the auspices of the
California Public Utilities Commission.
3www.pge.com/stockton
4Douglas Beaman
- Douglas Beaman Associates
- 612 13th Street
- Modesto, CA 95354
- (209) 524-1000
- Gary_at_DougBeaman.com
5CEC Website
- New Standards and Manuals can be downloaded at
- www.energy.ca.gov/title24
6Blueprint is a newsletter of the California
Energy Commission. It focuses on California's
Title 24 Building Efficiency Standards.
7(No Transcript)
8http//www.energy.ca.gov/efficiency/blueprint/
9How-To Videos
California Energy Commission videos http//www.co
nsumerenergycenter.com/videos/
10Why Change-Outs?
- Energy Standards are starting to address energy
efficiency of existing homes and businesses as
well as new buildings.
11(No Transcript)
12Duct Testing
- 1. Residential New Construction
- 2. NonResidential New Construction
- 3. Residential HVAC System Change-outs (in some
climate zones) - 4. NonResidential HVAC Change-outs (in all
climate zones)
13Typical Leakage Rates for Residential Systems
- Statewide average duct leakage in existing
residential systems 28 - 35 - 3-ton _at_ 400 cfm 1200 .28 336 cfm
14Quick Review of Common Duct Problems
15(No Transcript)
16(No Transcript)
17(No Transcript)
18(No Transcript)
19(No Transcript)
20Residential HVAC Change-outs
- Duct systems must be tested sealed if ALL of
the following conditions apply - Building permit applied for on or after October
1, 2005
21Climate Zones
- Residential Duct Testing Rules
- Apply ONLY in Climate Zones 2, 9, 10, 11,
12, 13, 14, 15 16 - Exempt Climate Zones 1, 3, 4, 5, 6, 7, 8
22California Climate Zones
23Ducts in Unconditioned Space
- At least 40 linear feet of duct work must be
located in unconditioned space.
24Asbestos Exemption
- Ductwork made with or insulated with asbestos is
EXEMPT
25Duct Testing Required When Any of the Following
Components are Replaced
- Air handler or furnace
- Outdoor condensing unit (split systems)
- Heating or cooling coil
- Furnace heat exchanger
- Package unit
26Additional Ductwork
- Adding or replacing 40 linear feet or more of
duct work in unconditioned space
27Maximum Leakage RateExisting Duct Work
- 1. 15 of fan flow
- 400 cfm/ton .15 60 cfm3 tons 60 cfm 180
cfm target - or
- 2. 60 Reduction
- Test before replacement and after
- 600 cfm initial test (example only) 60
reduction 240 cfm target - or
28Maximum Leakage (cont)
- 3. Duct leakage to outside of house 10 or less
(whole house blower door test plus duct leakage
test) - or
- 4. Seal all accessible leaks and verify by HERS
Rater (with smoke)
29Maximum Leakage RatesCompletely New Duct System
- HVAC system change-outs that include all new duct
work same duct testing standards as new
construction. - 6 of air flow (24 cfm / ton)
30Verification
- 1. Contractor tests
- 2. HERS Rater verifies
31Residential Alternatives
- Are there any alternatives to performing the
duct sealing and testing?
32(No Transcript)
33Option 1
- Climate Zones 2, 12, 16 only
- 0.92 AFUE Furnace
34Option 2
- Climate Zones 10, 13, 15 only
- SEER 14
- EER 12
- TXV
- R-8 insulation on all new duct work
- Additional R-4 on all existing duct work
35Option 3 All Climate Zones
- SEER 14
- EER 12
- TXV
- Plus
- 0.82 AFUE Furnace
- R-8 insulation on all new duct work
- Additional R-4 on all existing duct work
SEER 14 EER 12 TXV Plus 0.92 AFUE Furnace
36TXV
- Options 2 3 do not require TXVs with package
systems.
37(No Transcript)
38October 1, 2005
- NonResidential Duct systems must be sealed when
all of the following apply - Permit applied for on or after October 1, 2005
-
- And (next page)
39Unconditioned Space
- At least 25 of ductwork is outdoors or in
unconditioned space -
- And (next page)
40Climate Zones
- NonResidential Duct Testing Rules
- Apply in ALL Climate Zones
- And (next page)
41Asbestos Exemption
- Ductwork made with or insulated with asbestos is
EXEMPT - And (next page)
42Constant Volume
- Constant volume package or split system
- (not a VAV system)
- And (next page)
435,000 s.f. each unit
- Each HVAC unit serves 5,000 s.f. or less floor
area.Rules still apply if total area is greater,
as long as each unit serves only 5,000 s.f. - And (next page)
44Scope of Work
- Air handler or furnace
- Outdoor condensing unit (split systems)
- Heating or cooling coil
- Furnace heat exchanger
- Package unit
-
45Maximum LeakageExisting Ductwork
- 1. 15 of fan flow
- 400 cfm/ton .15 60 cfm3 tons 60 cfm 180
cfm target - 2. 60 Reduction
- Test before and after replacement
- For example 600 cfm initial test 60 reduction
240 cfm target
46Maximum Leakage (cont)
- 3. Seal all accessible leaks verified by HERS
Rater (usually with smoke)
47Maximum LeakageCompletely New Duct System
- HVAC system change-outs that include all new duct
work - 6 of air flow (24 cfm / ton)
48NonRes Alternatives
- Are there any alternatives to performing the
duct sealing and testing?
49(No Transcript)