Title: Calculation of PFP Thickness
1Calculation of PFP Thickness
2- The thickness of fire protection required is
determined by - Duration
- Critical Steel Temperature
- Steel section size and type
- Hp/A ratio
- Thickness stated in the local or international
approval
3SI Units Hp/A M/D A/V Imperial (US)
Units W/D A/P
metres
Heated Perimeter
m-1 or /m
metres²
Cross Section Area
Kilograms / metre
Mass of Section
kg/m²
metres
Heated Perimeter
Heated Surface Area
metres²
m-1 or /m
metres³
Volume of Steel
Pounds/foot
Weight of section
lb/ft/in
inches
Heated Perimeter
Square inches
Cross Section Area
in2/in
Heated Perimeter
inches
All express the relationship between the amount
of steel capable of absorbing heat to the area of
steel surface exposed to the fire.
4How much PFP do I need?
Hp/A - Section Factors
Heated Perimeter (Hp m)
Cross Sectional Area (A m²)
Low Hp/A Thinner PFP 305 x 305 x 240 kg/mHp/A
1.905m / 0.0305m² Hp/A 62 m-1 For H120
(400C) Chartek 7 11 mm
High Hp/A Thicker PFP 305 x 305 x 97 kg/m Hp/A
1.789m / 0.0123m² Hp/A 145 m-1 For H120
(400C) Chartek 7 16 mm
5How much PFP do I need?
How Hp/A changes with sides exposed to
fire. (Example 305 x 305 x240 Kg/m UC)
Wall, Floor or Deck
Wall, Floor or Deck
Flange only exposed Hp/A Hp/A 13 m-1
3 Sides exposed Hp/A Hp/A 52 m-1
4 Sides exposed Hp/A Hp/A 62 m-1
1.587 m
0.393 m
1.905 m
0.0305 m²
0.0305 m²
0.0305 m²
Note Cross Sectional Area Remains the same in
all cases!
6How to calculate an Hp/A?
The Yellow Book!
www.asfp.org.uk
7How to calculate an Hp/A?
8What do I do with my Hp/A?
Chartek 7 Certificate
Interchar 963 loadings
Example of Certificate of Fire Approval with
table of Hp/A v required PFP thickness
9What do I do with my Hp/A?
Interchar 963 loadings
10What about other section shapes?
Wall, Floor or Deck
Wall, Floor or Deck
Decreasing Hp/A Lower PFP thickness required