BEE3133 Electrical Power Systems - PowerPoint PPT Presentation

1 / 70
About This Presentation
Title:

BEE3133 Electrical Power Systems

Description:

For Transmission and Sub-transmission Lines and Distribution Feeders, ... and, if the differential current exceeds the relay's pickup value, the relay ... – PowerPoint PPT presentation

Number of Views:14774
Avg rating:4.0/5.0
Slides: 71
Provided by: Owne8
Category:

less

Transcript and Presenter's Notes

Title: BEE3133 Electrical Power Systems


1
BEE3133 Electrical Power Systems
  • Chapter 6 System Protection
  • Rahmatul Hidayah Salimin

2
Introduction
  • System Protection the equipment use to detect
    and isolate the faulty section from the system
    automatically.

3
Introduction
  • Short circuit occur when equipment insulation
    fails due to system overvoltages caused by
  • Lightning or switching surges
  • Flashover line-line (caused by wind)
  • Flashover to tree
  • Insulation contamination by dirt/salt
  • Mechanical failure
  • Cable insulation failure
  • Natural causes
  • Tower/pole or conductor falls
  • Objects fall on conductors

4
Introduction
  • Short circuit currents can be several orders of
    magnitude larger than normal operating currents
  • If it is allowed to persist, may cause
  • Damage to the equipment due to heavy currents,
    unbalanced current, or low voltage produces by
    the short circuit
  • Fire and explosion effect equipment/people
  • Disruption of service in the entire power system
    area

5
Introduction
  • Careful design, operation and maintenance of
    system protection can minimize the occurrence of
    short circuit but cannot eliminate them.

6
Fault Currents and Voltages
7
Function of System Protection
  • Cause the prompt removal from service of any
    elements of power system when it suffers a short
    circuit, or when it start to operate in any
    abnormal manner that might cause damage or
    otherwise interfere with the effective operation
    of the rest of the system.
  • Provide indication of the location and type of
    failure so that the data can be used to assist in
    expediting repair and analyzing the effectiveness
    of fault-prevention and mitigation features.

8
Function of System Protection
  • Why do we need system protection
  • Detect fault
  • Isolate faulted component
  • Restore faulted component
  • Aims
  • Continued supply for rest of system
  • Protect faulted part from damage

9
Types of Protection
  • A Fuses
  • For LV Systems, Distribution Feeders and
    Transformers, VTs, Auxiliary Supplies
  •  
  • B - Over current and earth fault
  • Widely used in All Power Systems
  • Non-Directional
  • Directional
  •   

10
Types of Protection
  • C - Differential
  • For Distribution Feeders, Busbars, Transformers,
    Generators etc
  • High Impedance
  • Low Impedance
  • Restricted E/F
  • Biased
  • Pilot Wire

11
Types of Protection
  • D - Distance
  • For Transmission and Sub-transmission Lines and
    Distribution Feeders,
  • Also used as back-up protection for transformers
    and generators without signaling with signaling
    to provide unit protection e.g.
  • Time-stepped distance protection
  • Phase comparison for transmission lines
  • Directional comparison for transmission lines
  •  

12
Types of Protection
  • E - Miscellaneous
  • Under and over voltage
  • Under and over frequency
  • A special relay for generators, transformers,
    motors etc.
  • Control relays auto-reclose, tap change control,
    etc.
  • Tripping and auxiliary relays

13
Design Criteria/Characteristics
Economy
Simplicity
Speed
Reliability
Sensitivity
Selectivity
14
Design Criteria/Characteristics
  • Reliability
  • Operate dependably and in healthy operating
    condition when fault conditions occur, even after
    remaining idle for months or years.
  • Selectivity
  • Clearly discriminate between normal and abnormal
    system condition to avoid unnecessary, false
    trips.
  • Sensitivity
  • Ability to distinguish the fault condition,
    although the different between fault and normal
    condition is small.

15
Design Criteria/Characteristics
  • Speed
  • Fault at any point in the system must be detected
    and isolated rapidly to minimize fault duration
    and equipment damage. Any intentional time delays
    should be precise.
  • Economy
  • Provide maximum protection at minimum cost
  • Simplicity
  • Minimize protection equipment and circuitry

16
Economic Factor
  • Total cost should take account of
  • Relays, schemes and associated panels and panel
    wiring
  • Setting studies
  • Commissioning
  • CTs and VTs
  • Maintenance and repairs to relays
  • Damage repair if protection fails to operate
  • Lost revenue if protection operates unnecessarily

17
Economic Factor
  • The cost of protection is equivalent to an
    insurance policy against damage to plant, and
    loss of supply and customer goodwill.
  • Acceptable cost is based on a balance of
    economics and technical factors. Cost of
    protection should be balanced against the cost of
    potential hazards.
  • There is an economic limit on what can be spent.
  • MINIMUM COST Must ensure that all faulty
    equipment is isolated by protection.

18
Relationship between reliability of supply, its
value and cost to the consumer
19
System Protection Components
  • Transducer / Instrument Transformer
  • Relay
  • Circuit Breaker

20
System Protection Components
  • Function
  • Transducers/Instrument Transformers
  • Provide low current and voltage, standardized
    levels suitable for the relays operation.
  • Relays
  • Discriminate between normal operating and fault
    conditions.
  • When current exceed a specified value relay will
    be operated and cause the trip coil of CB to be
    energized/open their contact.
  • Circuit Breakers
  • Open the line

21
System Protection Components
22
System Protection Components
23
System Protection Flow
voltage or current rise from normal condition
voltage/current is reduced to match with relay
rating
activate circuit breaker
circuit isolation
Relay
Transducer
Fault Occur
Circuit Breaker
Fault Clear
24
Zones of Protection
  • For fault anyway within the zone, the protection
    system responsible to isolate everything within
    the zone from the rest of the system.
  • Isolation done by CB
  • Must isolate only the faulty equipment or section

25
Zones of Protection
  • Zones are defined for
  • Generators
  • Transformers
  • Buses
  • Transmission and distribution lines
  • Motors

26
Zones of Protection
27
Zones of Protection
  • Characteristics
  • Zones are overlapped.
  • Circuit breakers are located in the overlap
    regions.
  • For a fault anywhere in a zone, all circuit
    breakers in that zone open to isolate the fault.

28
Overlapped of Protection
  • No blind spot
  • Neighboring zones are overlapped to avoid the
    possibility of unprotected areas
  • Use overlapping CTs
  • Isolation done by CB. Thus, it must be inserted
    in each overlap region to identify the boundary
    of protective zones.

29
Overlapped of Protection
  • Overlap accomplish by having 2 sets of instrument
    transformers and relays for each CB.
  • Achieved by the arrangement of CT and CB.

30
Primary Back-up Protection
  • Primary protection is the protection provided by
    each zone to its elements.
  • However, some component of a zone protection
    scheme fail to operate.
  • Back-up protection is provided which take over
    only in the event of primary protection failure.

31
Example
  • Consider the power system shown below, with the
    generating source beyond buses 1, 3 and 4. What
    are the zones of protection in which the system
    should be divided? Which circuit breakers will
    open for faults at P1 and P2?

32
Fault at P1 A, B, C Fault at P2 A, B, C,D, E
33
Example
  • If three circuits breakers are added at the tap
    point 2, how would the zones of protection be
    modified? Which circuit breakers will operate for
    fault at P1 and P2 under these conditions?

34
Fault at P1 A, F Fault at P2 C,D,E,G
35
Zone Discrimination
  • A system as shown with relays and breakers
    marked. A single fault has resulted in the
    operation of breakers B1, B2, B3 and B4.Identify
    the location of the fault
  • Answer
  • Fault in the overlap zone at breaker B2 as shown

36
Back-up Protection
  • 1.Duplicate Primary
  • Provide primary protection when the
    primary-relaying equipment is out of service for
    maintenance or repair
  • Disconnect when primary relaying operates
    correctly
  • Operate with sufficient time delay (coordination
    time delay) if primary not operate
  • When short circuit occur, both primary and
    back-up start to operate, but if primary is
    operate, then the back-up will reset.

37
Back-up Protection
  • 2.Remote Back-up
  • located outside boundary of Zone of Protection

38
Example
C, D, E
A, B, F
39
Example
C, D, E, F, G, H
A, B, I, J
40
Transducers
  • Also known as Instrument Transformer
  • Use to reduce abnormal current voltage levels
    and transmit input signals to the relays of a
    protection system.
  • Why do we need transducer
  • The lower level input to the relays ensures that
    the physical hardware used to construct the
    relays will be small cheap
  • The personnel who work with the relays will be
    working in a safe environment.

41
Transducers
  • Current and Voltage Transformers
  • Correct connection of CTs and VTs to the
    protection is important directional, distance,
    phase comparison and differential protections.
  • Earth CT and VT circuits at one point only

42
VT and CT Schematic
43
Voltage Transformers
  • VT is considered to be sufficiently accurate.
  • It is generally modeled as an ideal transformer.
  • VT secondary connected to voltage-sensing device
    with infinite impedance.

44
Voltage Transformers
  • Types of VTs
  • Electromagnetic VT
  • Capacitive VT
  • Busbar VTs
  • Special consideration needed when used for line
    protection
  • LV application(12 kV or lower)
  • Industry standard transformer with a primary
    winding at a system voltage and secondary winding
    at 67 V(line-to-neutral) and 116 V(line-to-line).

45
Voltage Transformers
46
Voltage Transformers
  • Voltage/Potential
  • Transformer (VT/PT)

47
Voltage Transformers
48
Voltage Transformers
49
Voltage Transformers
  • HV and EHV
  • Capacitor-coupled VT (CVT)
  • C1 C2 are adjusted, so that a few kVs of
    voltage is obtains across C2
  • Then, stepped down by T
  • VTs must be fused or protected by MCB.

50
Voltage Transformers
51
Voltage Transformers
  • VT ratios
  • ratio of the high voltage/secondary voltage
  • 11 21 2.51 41
  • 51 201 401 601
  • 801 1001 2001 3001
  • 4001 6001 8001 10001
  • 20001 30001 45001

52
Current Transformers
  • CT is an instrument transformer that is used to
    supply a reduced value of current to meters,
    protective relays, and other instruments.
  • The primary winding consist of a single turn
    which is the power conductor itself.
  • CT secondary is connected to a current-sensing
    device with zero impedance.

53
Current Transformers
  • CTs ratio(secondary current rating is 5A)
  • 505 1005 1505 2005
  • 2505 3005 4005 4505
  • 5005 6005 8005 9005
  • 10005 12005
  • CTs also available with the secondary rating of 1A

54
Current Transformers
55
Current Transformers
56
Reclosers and Fuses
  • Automatic reclosers are commonly used for
    distribution circuit protection.
  • Recloser self-controlled device for
    automatically interrupting and reclosing an AC
    circuit with preset sequence of openings and
    reclosures
  • Have built-in control to clear temporary faults
    and restores service with momentary outages.
  • Disadvantages
  • increase hazard when circuit is physically
    contacted by people.
  • Recloser should be locked out during live-line
    maintenance.

57
Reclosers and Fuses
  • An upstream fuse/relay has detected a fault
  • Downstream system isolated by fuse or breaker
  • Automatic re-closing after delay successful if
    fault not permanent

58
Relays
  • Discriminate between normal operating and fault
    conditions.
  • Type of Relays
  • Magnitude Relay
  • Directional Relay
  • Distance/Ratio Relay
  • Differential Relay
  • Pilot Relay

59
Magnitude Relays
  • Also called as Overcurrent Relay
  • Response to the magnitude of input quantities ie.
    current.
  • Energize CB trip coil when the fault current
    magnitude exceeds a predetermined value or trips
    when a current rises above a set point (pick-up
    current).
  • If it is less than the set point value, the relay
    remains open, blocking the trip coil.
  • Time-delay Overcurrent Relay also have the same
    operating method but with an intentional
    time-delay.

60
Directional Relays
  • Responds to fault only in one direction, either
    to the left or to the right of its location
  • Operation depends upon the direction (lead or
    lag) of the fault current with respect to a
    reference voltage.
  • The directional element of these relays checks
    the phase angle between the current and voltage
    of one phase, and allows the overcurrent unit to
    operate if this phase angle indicates current in
    the reverse direction.

61
Ratio Relays
  • Operate for certain relations between the
    magnitudes of voltage, current and the phase
    angle between them.
  • Measures the distance between the relay location
    and the point of fault, in term of impedance,
    reactance and admittance.
  • Respond to the ratio of two phasor quantities as
    example Voltage and Current (Z V/R)
  • Also called impedance or distance relay

62
Differential Relays
  • Respond to the vector difference between two
    currents within the zone protection determined by
    the location of CTs.
  • Not suitable for transmission-line protection
    because the terminals of a line are separated by
    too great a distance to interconnect the CT
    secondaries.
  • For the protection of generators, transformers,
    buses,
  • Most differential-relay applications are of the
    current-differential type.

63
Differential Relays
Relay
  • Fault occur at X
  • Suppose that current flows through the primary
    circuit either to a load or to a short circuit
    located at X.
  • If the two current transformers have the same
    ratio, and are properly connected, their
    secondary currents will merely circulate between
    the two CTs as shown by the arrows, and no
    current will flow through the differential relay.

64
Differential Relays
Relay
  • A flow on one side only, or even some current
    flowing out of one side while a larger current
    enters the other side, will cause a differential
    current.
  • In other words, the differential-relay current
    will be proportional to the vector difference
    between the currents entering and leaving the
    protected circuit and, if the differential
    current exceeds the relays pickup value, the
    relay

65
Differential Relays
Relay
  • When a short circuit develop anywhere between the
    two CTs.
  • If current flows to the short circuit from both
    sides as shown, the sum of the CT secondary
    currents will flow through the differential
    relay.
  • It is not necessary that short-circuit current
    flow to the fault from both sides to cause
    secondary current to flow through the
    differential relay.

66
Pilot Relays
  • The term pilot means that between the ends of
    the transmission line there is an interconnecting
    channel of some sort over which information can
    be conveyed.
  • Use communicated information from remote sites as
    input signals.

67
Pilot Relays
  • Transmitting fault signals from a remote zone
    boundary to relays at the terminals of a long TL
  • Pilot relaying provides primary protection only
    back-up protection must be provided by
    supplementary relaying.
  • Type wire pilot, carrier-current pilot and
    microwave pilot.

68
Pilot Relays
ZA
ZB
  • Station 1 consist of meter for reading voltage,
    current and power factor.
  • Distance relay, tell the different between fault
    at A (middle) and B (end) by knowing the
    impedance characteristic per unit length of the
    line.

69
Pilot Relays
  • Could not possibly distinguish between fault B
    and C because impedance would be so small-
    Mistake in tripping CB for fault B or C
  • Solution- indication from station B, when the
    phase angle of the current at S-B(with respect to
    current A) is different by approximately 180o
    from it value for fault in the line section AB.

70
Pilot Relays
2
1
B
C
A
(with respect to current A) is different by
approximately 180o from it value for fault in the
line section
(with respect to current A) is not different in
degree from it value for fault in the line section
Write a Comment
User Comments (0)
About PowerShow.com