1
The Nuts Bolts of TBLL Development
  • Duyen Tran
  • OMI, Inc.

2
The Bible
  • EPA Guidance Manual on the Development and
    Implementation of Local Discharge Limitations
    Under the Pretreatment Program
  • EPA 833-R-04-002A
  • July 2004

3
7-steps process
  • Preliminary Data Collection
  • Identify Pollutants of Concern
  • Sampling Plan
  • Data Collection Evaluation
  • Calculation
  • Technical Review
  • TBLL Submission

4
Preliminary Data Collection
  • Receiving stream designation
  • Water Quality Standards for the designated
    receiving stream
  • Most recent priority pollutant scans on plant
    influent (include analyses of additional
    pollutants specified in State Water Quality
    Standards)

5
Identify Pollutants of Concern (POC)
  • Pollutants with concentration greater than 0.1
    mg/l in the influent scan, adjust for
    inflow/infiltration if the plant has I/I problem
  • Pollutants associated with historical plant
    problems
  • Fifteen EPAs POCs Cd, Cr, Cu, Pb, Ni, Zn, As,
    CN, Ag, Hg, Mo, Se, BOD, TSS, Ammonia

6
Sampling Plan
  • Review historical data on pollutants of concern
    for influent, effluent, primary effluent,
    sludge, industrial effluent, inhibition data,
    background (domestic commercial)
  • Reject data that is anomaly
  • Reject data that does not meet laboratory QA/QC
    or required MDLs

7
Sampling Plan (contd)
  • In lieu of at least 6 months of historical data,
    collect at least 6 consecutive days of samples
    for influent, effluent, and background
  • Consider plant retention time when collecting new
    influent and effluent data
  • In all cases, obtain the most representative
    collection of data for TBLL calculation

8
Data Collection Evaluation
  • NPDES Permit
  • State WQS
  • 503 Sludge Criteria
  • Receiving Stream, 7Q10 or 7Q2
  • Plant diagram and description of plant processes
  • POTW Flow
  • Digester Flow
  • Industrial Flows
  • Background Flow (Domestic Commerical)

9
Data Collection Evaluation
  • Review analytical data for
  • Chain of custody
  • Laboratory QA/QC
  • MDLs
  • Reject data that appears to be anomaly or does
    not meet the above criteria
  • Document the data evaluation process

10
Calculation
  • Plant Removal Efficiency,
  • Allowable Headworks Loadings
  • Background (Domestic) Loadings
  • Derive Maximum Allowable Headworks Loadings
    (MAHL)
  • Maximum Allowable Industrial Loadings (MAIL)

11
Allowable Headworks Loadings (AHL)
  • Calculate AHL for
  • Water Quality Standards
  • NPDES Permit
  • Process Inhibition/Operational Problems
  • Sludge Disposal Criteria

12
(No Transcript)
13
Maximum Allowable Industrial Loadings, MAIL
  • MAIL MAHL - (Background Safety Factor)

14
(No Transcript)
15
Allocation
  • Uniform Concentration
  • Industrial Contributory Flow
  • Mass Proportion Method
  • Selected Industrial Reduction Method

16
Applications of Local Limits
  • Industrial Discharge Permit Limits Calculation
  • New Discharge Permit Consideration
  • Plant Loadings Assessment

17
Technical Review
  • Technical Support Staff
  • City Engineers
  • City Council

18
TBLL Submission
  • Use State guidelines and checklist on program
    modification and submittal
  • Prepare a professional certification
  • Incorporate the new technically based local
    limits to the sewer use ordinance (SUO)
  • Submit three copies of the TBLL study and revised
    SUO to the State

19
(No Transcript)
20
Resources
  • EPA Guidance Manual on the Development and
    Implementation of Local Discharge Limitations
    Under the Pretreatment Program
  • EPA Supplemental Manual