Renewable Energy Systems - PowerPoint PPT Presentation

1 / 16
About This Presentation
Title:

Renewable Energy Systems

Description:

Renewable Energy Systems. John Seryak. Natural Ventilation Using Wind Towers or Chimneys ... Venturi effect of constricted airflow through chimney exhaust opening ... – PowerPoint PPT presentation

Number of Views:85
Avg rating:3.0/5.0
Slides: 17
Provided by: johnas6
Category:

less

Transcript and Presenter's Notes

Title: Renewable Energy Systems


1
Renewable Energy Systems
Natural Ventilation Using Wind Towers or Chimneys
John Seryak
4/24/2002
2
Why is a Wind Tower Useful?
  • A wind tower uses natural ventilation to
    displace the need for air-conditioning equipment
    and energy consuming fans.

How Does a Wind Tower Work?
  • A wind tower utilizes pressure differences to
    create a draft. There are four ways a pressure
    differential can be created
  • Temperature differences between inside and
    outside air
  • Pressure difference from stack height
  • Bernoulli effect of wind on a sloped roof
  • Venturi effect of constricted airflow through
    chimney exhaust opening

3
What Does a Wind Tower Look Like? Do They Really
Work?
Yes! They Do! Check out the Queens Building of De
Montfort University
4
Model for Simulation
Ft Ac x (Pi Po) Ac x h x ?o x g
Fst Ac x h x ?i x g
5
Model for Simulation
Fnet Ac x h x g x (?o ?i)
? P / (R x T)
Student Project Equation
Pnet h x g x Pbar x (1/To) (1/Ti) / R
ASHRAE Published Equation
Pnet ?i x g x h x (Ti/To 1)
6
Model for Simulation
Velocity v(2 x Pnet/ ?)   Volume Flow Rate
(VFR) Velocity x Ac
Ti (Qgain) / (Aw/Rw Ac/Rc VFR ? Cp)
To
7
Model for Simulation
Qgain Qwalls Qventilation Qceiling 0
Qgain Aw/Rw x (Ti To) VFR x ? x Cp x (Ti
To) Ac/Rc x (Ti To) 0
Ti (Qgain) / (Aw/Rw Ac/Rc VFR ? Cp)
To
8
Results
  • Velocity
  • Student Project 0.61 m/s
  • ASHRAE 0.61 m/s
  • Physical Experiment 0.43 m/s
  • Temperature
  • Student Project 305.1 K
  • ASHRAE 305.1 K
  • Physical Experiment 304.2 K

9
Results Auditorium Simulation
  • With No Ventilation, Internal Temperature
    reaches 323 K (121 F).

10
Results Auditorium Simulation
  • Temperatures decrease asymptotically, 294 K (69.5
    F) can be Obtained Inside by Using a Chimney Stack

11
Results Auditorium Simulation
12
Results Auditorium Simulation
13
Results Auditorium Simulation
14
Results Auditorium Simulation
15
Recommendations
  • Add Bernoulli and Venturi effect algorithms to
    simulation.
  • Add algorithms for chimney placement and number
    of chimneys.
  • Rerun physical experiment to calibrate to
    simulation. Run physical experiment in wind
    tunnel to calibrate to Bernoulli/Venture model.
  • Use Esim and year round simulation to calculate
    a simple payback.

16