System Role of Generation - PowerPoint PPT Presentation

1 / 29
About This Presentation
Title:

System Role of Generation

Description:

System Role of Generation. Leslie Bryans & Alan Kennedy ... released into the system and arrests the rate at which the system speed or frequency changes. ... – PowerPoint PPT presentation

Number of Views:69
Avg rating:3.0/5.0
Slides: 30
Provided by: dad152
Category:

less

Transcript and Presenter's Notes

Title: System Role of Generation


1
System Role of Generation
  • Leslie Bryans Alan Kennedy

2
Generators contribute to
  • System stability and power quality
  • Inertia and fault level
  • Reactive power balance
  • SONI will discuss
  • Active power balance
  • SONI will discuss

3
What is Inertia
  • It is the energy stored in generators because
    they are rotating.

4
Inertia
  • Large spinning machines provide stored energy due
    to the rotating mass of their rotor, driving
    turbine shafts etc. Engineers model this as a
    number of rotating masses.
  • When a disturbance occurs e.g. the unanticipated
    loss of a generator, the stored energy is
    released into the system and arrests the rate at
    which the system speed or frequency changes.

5
System Frequency Issue
Solutions wind farms to contribute to
restorative power and system inertia?
6
Frequency trace NI system only - low inertia

7
Frequency trace for the combined NI RoI System
- higher inertia
8
Why is the rate of change of system frequency
important?
  • We need to understand this better as it likely to
    be a limiting factor in accommodating higher
    levels of wind.
  • ROCOF protection
  • Question could this become backup Loss of Mains
    protection? (DGSEE with Prof. Jim McDonald)
  • System effects e.g. traditional generation
    auxiliary plant trips CCGT flame outs.
  • Raised with DGSEE as requiring investigation

9
Wind turbines
  • Fixed speed turbines seem to deliver an inertia
    of around 4.3MWs/MVA which is similar to
    traditional plant so do not reduce system
    inertia.
  • DFIGs and Fully converted wind farms are
    presently thought to deliver close to 0MWs/MVA
    so at present reduce system inertia.

10
Work done
  • In order to understand the problem, we have
    explored what happens to inertia and rate of
    change of frequency with very high levels of
    penetration of wind power on the island of
    Ireland.
  • This is to understand what we need to tackle
    rather than alarm the present position.

11
Inertia, Rate of change of frequency and
frequency nadir
  • 80 wind operating
  • (40 energy target)

12
Inertia summer min ( 80 wind)
13
Inertia - winter ( 80 wind)
14
400MW trip in Winter 80 wind
15
400MW trip in Summer 80 wind
16
Enlarged Graph section 400MW trip in summer 80
wind
17
Work by UMIST for DGSEE
  • DFIGs could deliver inertia as required but
    require control modifications
  • Hardware transient loading is not an obstacle. (
    Prof. Jenkins says that the transient loading on
    gearboxes, drive trains etc. falls well within
    that needed for dynamic braking of the turbines.)

18
Our Proposal
  • To seek a modification to the NI Grid Code to
    require wind turbines to provide inertia at 4
    6MWs/MVA.
  • This would need to be harmonised with an
    equivalent provision in the EirGrid Grid Code and
    Distribution Codes.
  • This will be a world first and waiting does not
    seem an option.

19
Fault level
  • With wind farms

20
What is Fault level?
  • Fault level is measured in current or MVA.
  • When a short circuit occurs a large current flows
    this causes the operation of protective devices
    (fuses and circuit breakers open) to isolate the
    fault.
  • Protection systems are designed to isolate only
    the faulty section of network.
  • Fault level is also a measure of system stiffness
    which determines power quality issues.

21
High and Low fault level
  • Too high fault currents can be hard to interrupt.
  • Too low and the protective devices may not
    operate.
  • The problem with high penetration of wind farms
    is too low fault levels.
  • (Work is on-going with DG and SEE for the UK
    Grid. They are going to study NI as well).

22
Power quality
  • Very low fault level results in excessive voltage
    dips when equipment is switched on.

23
GB results
  • With the expected penetration of wind farms in GB
    2010 the minimum fault level is reduced by a few
    percentage points on average.
  • In some places because traditional generation is
    off-the bars the fault level is reduced by 70.
  • This leads to problems with distance protection
    (the main 110kV system protection). In
    particular, resistance faults may result in
    mal-operation of distance protection.
  • The NI situation is likely to be much worse
    because we only have 3 traditional generating
    units operating at periods of low fault level.

24
Our proposal
  • To ensure that the fault level tools developed by
    DGSEE (which assess fault level throughout the
    range of generation dispatches) are applied to
    the NI network and to consider what further
    action may be needed. At the extremewe may need
    to convert the distance protection schemes to
    unit schemes which is very expensive.
  • Also, DGSEE have not considered the knock-on
    effect of low fault level on the distribution
    protection systems. This may be more serious and
    potentially intolerable. Further work is
    required.

25
Reactive power
26
Reactive Power Balance
  • Static Balance
  • To ensure an adequate voltage everywhere on the
    system and provide reactive power requirements to
    load
  • More heavily loaded transmission system requires
    relatively more reactive power due to I²X losses
  • Reactive power doesnt travel well on a
    transmission system due to the high X/R ratio,
    but NI transmission system is small.
  • Studying the reactive power balance is more
    complex when embedded generation is included

27
Static Reactive Power
Lines Cables capacitance Q V²/Xc
Gen AVR controls terminals to approx 1pu voltage

Capacitor banks Q V²/Xc
Transmission System
Gen transformer tapped to pump reactive power
into the transmission network.
Consumption of Reactive Power
28
Problem with Embedded Gen
P
Q
G
R
X
Step-down Transformer
Gen Bus
Back-bone transmission network
P Q
R
X
load
Max limit at EG
Voltage
Min limit at load
29
  • Static Reactive Power Balance
  • - Within reason this could be achieved with
    suitably sited capacitors but there are technical
    difficulties with many capacitors installed
  • Dynamic Reactive Power Balance
  • - Needed during and after system disturbances
  • - Quantity depends on many factors but rule of
    thumb is dynamic static
  • - Synchronous generators can supply high levels
    of dynamic reactive power
  • - Reactive power output of DFIGs and
    fully-converted wind turbines is limited to
    rated MVA, but even this is of limited use on the
    transmission system
  • - Need for alternative forms of dynamic reactive
    support on transmission system eg. SVC, STATCOM,
    synch-comp
Write a Comment
User Comments (0)
About PowerShow.com