Title: Estates and Buildings Division
1Estates and Buildings Division
- Martyn NewtonAssistant Director of Estates- Risk
and Sustainability.
2BIOMASS _at_ UEA
- Existing systems at UEA
- Why consider Biomass?
- What is Gasification and why that?
- Economics
- Project detail
3(No Transcript)
4The University of East Anglia
5Why do we need it?UEA Energy demand
- HEAT for space heating, domestic hot water,
Sportspark pool heating, and temperature
controlled research environments - 42,000,000 kWh per annum
- ELECTRICITY for lighting, office equipment,
cooking, research equipment, etc - 32,000,000 kWh per annum
- COOLING due to equipment or Solar heat gain
6What is CHP?Combined Heat and Power
7UEAs Combined Heat and Power
8UEAs District Chilling
9UEAs District Tri-generation
10But what fuel for the Future?
11Climate Change?
12UEA Energy Future
- Increasing need
- Increasing costs
- Future fuel availability
- Environmental issues Environmental school,
Climate Research Unit, Cred
13(No Transcript)
14Biomass CHP
15(No Transcript)
16RG2000 Simple Mass Balance85 Efficiency
To engine Electricity - 2531
kW Exhaust heat - 3168 kW Heat loss
- 965 kW
Clean Syngas (4000 Nm3/hr / 24000MJ / 6664kW)
Air inlet (2504 kg/hr)
cyclone
Gas tank
Woodchip (2000 kg/hr / 32000MJ)
filter
Scrubber
Gas (4000 Nm3/hr / 25336MJ)
Reactor
Heat ex
40oC
Fan
Gas (4000 Nm3/hr / 24000MJ)
500oC
Ash (40 kg/hr / 1040MJ)
Heavy tar (40 kg/hr)
Water Circulation system
Water tank
Pre-heated Air (2504 kg/hr / 1336MJ)
Char (160 kg/hr / 4160MJ)
Water circulation pump
Engine efficiency 38 Electricity
2531 kWh Exhaust heat 3168 kWh
17Proposed BIOMASS
- Increasing need
- Extra 1.4MWe ,2MWh
- Increasing costs
- Under 7 year payback
- Future fuel availability
- Local wood fuel
- Environmental issues, Cred, Environmental school
- Reduces Carbon Emissions of UEA by over 35
18BIOMASS Project as of June 2008
- 8.5 million (1m DEFRA GRANT)
- Reduction in Utility costs 1.2m
- Renewable Obligation Certificates 0.9m
- Export power 0.3 m
- Cost of wood approx. 0.4m
- Cost of maintenance 0.3m
19(No Transcript)
20UEA Carbon Emissions
- 1990-2006
- 5870-14,047 students (239 INCREASE)
- 138,-207,000 sq.m (49 INCREASE)
- 19,420-21,652 T of CO2(10 INCREASE)
- 1990-2006
- 3308-1541 kg/student (53 reduction)
- 140-104 Kg/CO2/sq.m (25reduction)
- 2009 Assuming Biomass
- 24.5 reduction in CO2 over 1990 levels despite
increases in students and building area
21 22UEA Gasifier
23- Tel (01244) 529589
- E-mail george_at_refgas-uk.com
- Address United Air Power Building, Unit 2
- Whittle Close, Engineer Park
- Sandycroft, Deeside
- Flintshire, CH5 2QE
24(No Transcript)
25(No Transcript)
26Possible Concerns
- Emissions smell, smoke, harmful nasties
- Noise
- Traffic
- Appearance
- Wood Supply
27Estates and Buildings Division
- Martyn Newton Assistant Director of Estates-
Facilities