Title: Department of Defence Newbridge


1
Department of DefenceNewbridge
  • Experience of Designing a Building Using
    Simulation Tools
  • A Case Study
  • Department of Defence Decentralised Offices
  • 28th Nov 2008
  • Jay Stuart
  • DW EcoCo
  • Integrated Sustainable Design Consultants

2
Department of DefenceNewbridge site
  • The final design now under construction

3
Department of DefenceNewbridge site
  • IES for dynamic thermal simulation of whole
    building
  • Ecotect for solar shading analysis
  • Therm for thermal bridging analysis

Shading Analysis
Simulations for Value Engineering
3D thermal bridging simulations
Shading with trees
Thermal simulation
CFD simulation
Simulation work
Drawings from architects
Simple advice on shading Ventilation strategy
Timeline
4
Department of DefenceNewbridge site
  • Natural Ventilation Required by OPW

5
Department of DefenceNewbridge site
  • Competition stage simulation work
  • (no shading, no atrium in the design)

6
Department of DefenceNewbridge site
  • Competition stage (no shading, no atrium)

7
Department of DefenceNewbridge site
  • Simple preliminary advice on shading options to
    the architects

8
Department of DefenceNewbridge site
  • Ventilation for simulation
  • Design guidelines provided to the architect for
  • Natural Ventilation strategy
  • Plan depth
  • Atrium design
  • Window design
  • Solar shading
  • U-values

9
Department of DefenceNewbridge site
  • Competition Stage

Energy Use Summary 138 kWh/m2/yr
10
Department of DefenceNewbridge site
  • CFD Simulation to SW corner office

11
Department of DefenceNewbridge site
  • The final design

12
Department of DefenceNewbridge site
  • The final design

13
Department of DefenceNewbridge site
  • Simulation work detail design simulation model
  • Changed layout
  • Solar shading
  • Atrium considered for natural ventilation

14
Department of DefenceNewbridge site
  • The atrium final design

15
Department of DefenceNewbridge site
  • Simulation work
  • Solar shading with trees TRANSFORMATION of an
    idea (considering information available and
    software capabilities)

16
Department of DefenceNewbridge site
  • Simulation work detail design simulation model
  • Solar shading
  • Atrium

17
Department of DefenceNewbridge site
  • Simulation work detail design simulation model
  • Solar shading
  • Atrium

18
Department of DefenceNewbridge site
  • Results
  • (after several iterations and discussions with
    services engineers)

19
Department of DefenceNewbridge site
  • Results
  • the energy breakdown

20
Department of DefenceNewbridge site
  • Thermal Comfort
  • OPW Brief Internal temperatures are not to
    exceed 26C for more than 5 of the occupied
    hours and are not to exceed 27C at any time
    during the year.
  • Measures
  • Natural ventilation system
  • An atrium to remove heat from the building and
    reduce temperatures in areas on the ground floor
  • Solar control glazing to minimise solar gains
  • Solar shading through brise soleil, overhangs,
    recessed fenestration and foliage

21
Department of DefenceNewbridge site
  • Simulation work for OPW
  • Thermal Comfort

Mean Radiant Temperature for the office of the
Minister of Defence
( local cooling required )
22
Department of DefenceNewbridge site
  • Solar shading detail design
  • The Ecotect model

23
Department of DefenceNewbridge site
  • Solar shading detail design
  • Refining the design with Ecotect
  • Original design
  • Refined Design

24
Department of DefenceNewbridge site
  • 3D Thermal Bridging Calculation

25
Department of DefenceNewbridge site
  • 3D Thermal Bridging Calculation
  • Isotherms in external wall, caused by steel
    fixings
  • Cold bridging is often not considered in U-value
    calculations
  • Therm software

26
Department of DefenceNewbridge site
  • 3D Thermal Bridging Calculation
  • U-value vs. insulation thickness

27
Department of DefenceNewbridge site
  • 3D Thermal Bridging Calculation
  • U-value vs.
  • density of cladding fixings

28
Department of DefenceNewbridge site
  • Simulation for Value Engineering
  • Client requested following changes for value
    engineering
  • Change U-value from 0.2 to 0.27 W/m2K
  • Reduce lighting controls to a basic specification

29
Department of DefenceNewbridge site
  • Simulation for Value Engineering
  • Previous model used variables changed one at a
    time

30
Department of DefenceNewbridge site
  • Simulation for Value Engineering

31
Department of DefenceNewbridge site
  • P.Elliott and Co. Ltd.
  • MOLA Architects
  • WYG Engineers
  • . 28th November 2008 . work continues.

32
Department of DefenceNewbridge site
Thank You
  • DW EcoCo Ltd.
  • Integrated Sustainable Design Consultants