Title: IFAX Product Detail
1IFAX Product Detail
IFAX
Multi
Do you want to look now?
YES - See it
NO - Skip it
2Multi
Control Panel Block
IFAX
External Connections
Repeater Connections
4 Line x 40-Character Display
IFAX Main Control Board
IFAX Twin Loop Driver Module(s)
User Keypad
M-A Part No.05-045
M-A Part No. 05-047
RS-232
RS-485
PC, Printer, Graphics System, Pager, BMS,
Connection
More..
External Connections
IFAX Interconnection Interface Module
M-A Part No. 05-046
IFAX PSU / Charger Unit
IFAX Sounder/Aux. Module(s)
M-A Part No. 05-055
M-A Part No. 05-021
More..
3Multi
PSU / Charger Unit
IFAX
Nominal 24OV AC Supply
Power In
Nominal 24V DC 5A (Maximum)
O/P 1
24V Stand-By Batteries
M-A Part No. 05-055
O/P 2
5V DC 1A (Maximum)
O/P 3
AC Supply Failure
Fault Outputs
Charger Fault
Battery Failure
4Multi
PSU / Charger Unit
IFAX
- Fully Protected And Regulated Outputs -
1. Nominal 24V DC at 5A
2. Stand-By
Battery Supply
3. 5V DC at 1A - Fault Outputs -
1. Charger Fault (Low Output Voltage)
2. Battery Failure (Disconnected/Low
Voltage) 3. AC Supply Failure.
5Multi
IFAX
Interconnection
Interface Module
24V 5V DC Supply
Aux. Power
24V DC
Power
To/From MA-05-055
Comms Power
Main Control Board
Repeater Control Panels
M-A Part No. 05-046
Comms Power)
To/From MA-05-045
(4-core connection)
Comms Power
Loop Driver Modules
Sounder/Auxiliary Modules
Comms Power
To/From MA-05-047
To/From MA-05-021
6Multi
IFAX
Interconnection
Interface Module
- Common Interconnection Point For IFAX Modules
- Also Provides Terminals For -
1. IFAX Repeater/Control
Panels (4-Core Link) 2. 24V
Auxiliary Supply
7Multi
Main Control Board
IFAX
User Operation Keypad
24V DC
User Keypad
Power
4 Line x 40-Character Display
5V DC
Printer - Pager - BMS
RS-232 Port 1
IFAX Network (Optional)
RS-485 Port 4
M-A Part No. 05-045
OPTION
Loop Driver Modules
RS-485 Port 2
Zonal LED Expansion (Optional)
Repeater Control Panels
LEDs Expand
Common Indicators 48 Zonal Fire LEDs
RS-485 Port 3
OPTION
8Multi
Main Control Board
IFAX
- 4 Line x 40-Character Text Display
- 48 Individual Zonal Fire LEDs - Can be
externally expanded to 240 - ESD Protected Communication Ports -
1. RS-232 - Printer / Pager / BMS Comms
2. RS-485 - Loop Driver Comms
3. RS-485 - Repeater Comms
4. RS-485 - IFAX Network Comms (optional)
9Multi
Loop Driver Module
IFAX
Nominal 24V DC Supply
Power
Discovery / XP95 Devices
Loop 1
Main Control Board RS-485 Control Signals
Data
M-A Part No. 05-047
Discovery / XP95 Devices
Loop 2
Data
To expansion Loop Driver Modules
10Multi
Loop Driver Module
IFAX
- Can supply continuous loads of 1A per loop
- Completes all pre-processing of sensor conditions
- Full open-circuit, short-circuit and earth fault
protection - Standalone operation mode on loss of
communication with main control board
11Multi
Loop Driver Module
IFAX
- Can operate 126 alarm sounders and 100 detectors
per loop - Each sounder operation programmable in
configuration data - Intelligent detector polling verification
algorithms minimise unwanted alarms - Continuously monitors loop data comms quality and
reports corruption
12Multi
Sounder/Aux.Module
IFAX
Nominal 24V DC Supply
Sounder Circuit
Cct 1
Power
Sounder Circuit
Cct 2
Data I/O
Main Control Board
Sounder Circuit
Cct 3
M-A Part No. 05-021
Sounder Circuit
Cct 4
Auxiliary Relay
Cct 5
Data I/O
Auxiliary Relay
Cct 6
To expansion Relay Modules
13Multi
Sounder/Aux.Module
IFAX
- 4 Programmable Fully Monitored Sounder
Circuits - 2 Programmable Auxiliary Relays
- Modules Can Be Simply Daisy-Chained As Required
14IFAX Product Detail
Repeater
IFAX
15IFAX
Repeater
Features
- Provides All IFAX Indication Control Facilities
- RS-232 Port For Local Printer (Optional)
- 4-Core Interconnection (Including Power)
- Up To 32 Repeaters Can Be Fitted
- Surface And Flush-Mounting Models Available
16IFAX
Repeater
Control Board
12 - 28V DC Supply
User Operation Keypad
User Keypad
Power
(2-Cores)
4 Line x 40-Character Display
Local Printer Interface (Optional)
RS-232 Port 1
OPTION
M-A Part No. 05-050
IFAX Control Panel
Zonal LED Expansion (Optional)
LEDs Expand
Common Indicators 48 Zonal Fire LEDs
RS-485 Port 3
OPTION
(2-Cores)
17 IFAX Product Detail
OnSite
IFAX
18IFAX
OnSite
Features
- Powerful Windows Based Configuration Program
- Fully Supported With 1200 Pages of On-Line
Context Sensitive Help - Simplified Working Windows Guarantee Ease Of Use
- Allows Ultimate Cause Effect Definition
19IFAX
OnSite
Features
- Enables Full Customisation Of System Operation
To Provide Ideal System User Facilities - Allows Definition and Total Control of All
Discovery Detector Features
- SOFTWARE IS OPENLY AVAILABLE TO
- TRAINED END USERS
20 IFAX Product Detail
Network
IFAX
21IFAX
Network
Features
- True Peer-to-Peer Seamless Network
Ideal for large building complexes and campus
style environments Provides flexible
distribution and co-ordination of system
control
- 32,256 Addressable Points, 1,536 Fire Zone
Capacity
22IFAX
Network
Features
- High Integrity Communication
Allows safety critical actions to be passed
across the network from one IFAX unit to
others Enables use of standard fire resistant
cable between Stations
- Maximum Network Fault Tolerance
Loss of one or more Stations does not affect the
operation of the the remainder of the network
23IFAX
Network
Block Diagram
2-Station Network
IFAX
IFAX
Multi
Multi
(Station 1)
(Station 2)
Network Port RS-485
Network Port RS-485
ADD...
ADD...
2-Cores
2-Cores
24IFAX
Network
Block Diagram
Multi-Station Network
IFAX
IFAX
IFAX
Multi
Multi
Multi
(Station 2)
(Station 1)
(Station 3)
Network Port
Network Port
Network Port
ADD...
ADD...
ADD...
IFAX Port
IFAX Port
IFAX Port
N.I.M. M-A Part No.05-810
N.I.M. M-A Part No.05-810
N.I.M. M-A Part No.05-810
Primary Ring (2-Cores)
Secondary Ring (2-Cores)
Port A
Port B
Port A
Port B
Port A
Port B