Building Safety and Accommodation Requirements - PowerPoint PPT Presentation

1 / 20
About This Presentation
Title:

Building Safety and Accommodation Requirements

Description:

RSE's structural justification for increased load such as raised screed and partition wall ... Raised screed. Fire Resisting Construction (1) Compliance with. FRC Code ... – PowerPoint PPT presentation

Number of Views:200
Avg rating:3.0/5.0
Slides: 21
Provided by: build7
Category:

less

Transcript and Presenter's Notes

Title: Building Safety and Accommodation Requirements


1
(No Transcript)
2
Building Safety and Accommodation Requirements
  • Compliance with safety and health standards under
    the Buildings Ordinance
  • Enlisting the service of Authorized Persons
  • Formal submission of plans for approval
  • AP/RSE Directory (www.info.gov.hk/bd)
  • Viewing approved plans/documents
  • Land use and lease matters

3
Structural Design (1)
  • 2.0 kPa for dormitory areas
  • 2.5 kPa for living/recreational areas
  • RSEs structural justification for increased load
    such as raised screed and partition wall
  • Sound structural condition

4
Structural Design (2)
  • Additional solid
  • wall

5
Structural Design (3)
  • Raised screed

6
Fire Resisting Construction (1)
  • Compliance with
  • FRC Code

7
Fire Resisting Construction (2)
  • Some general requirements
  • 1 hour FRP compartmentation
  • 1 hour FRP wall and 1/2 hour FRP door for kitchen
  • AP/RSEs substantiation on fire resisting
    components

8
Fire Resisting Construction (3)
9
Means of Escape (1)
  • Compliance with
  • MOE Code 1996

10
Means of Escape (2)
  • Some general requirements
  • Discharge value
  • MOE provision in any particular floor
  • Clear width exit door
  • One 750mm exit door for rooms lt30 persons
  • Two exit doors (850mm each, total 1750mm) for
    rooms between 31-200 persons lines of direct
    distance gt30o open in the direction of exit not
    obstructing other exit route

11
Means of Escape (3)
XXXXXX
12
Means of Escape (4)
13
Means of Escape (5)
  • 2m headroom for exit routes
  • maximum 18m deadend
  • 30m to 45m (depending on the fire resisting
    construction) to staircase
  • 450mm solid separation from other accommodation
    at the discharge point of exit staircase

14
Means of Escape (6)
15
Means of Escape (7)
  • Occupancy factor 3 m2 usable floor area/person
  • Fire engineering approach

16
Lighting and Ventilation (1)
  • Habitable room (2.5m under floor slab, 2.3m under
    beam)
  • Windows of habitable rooms, offices and kitchens
    facing external air (glass area, openable area)
  • Windows of rooms containing sanitary fitments
    facing open air (glass area and openable area)

17
Lighting and Ventilation (2)
  • Artificial lighting and mechanical ventilation
    (gt5 air changes/hour) to the satisfaction of the
    BA
  • Adequate aperture for room-sealed gas water
    heater serving bathrooms

18
Sanitary Fitments
  • 1-8 residents 1 WC, 1 basin, 1 bath/shower
  • 9-20 residents 2 WCs, 2 basins, 2 baths/showers
  • Every additional 15 residents or part thereof, 1
    additional WC, basin and bath/shower

19
Unauthorized Building Works
  • similar to other types of licensed premises

20