PTCS DUCT SEALING SPECIFICATIONS - PowerPoint PPT Presentation

1 / 9
About This Presentation
Title:

PTCS DUCT SEALING SPECIFICATIONS

Description:

Require sealing of the supply plenum and take offs. One Last Challenge ... of qualifying path, the entire supply plenum and all take offs including the ... – PowerPoint PPT presentation

Number of Views:117
Avg rating:3.0/5.0
Slides: 10
Provided by: Andr732
Category:

less

Transcript and Presenter's Notes

Title: PTCS DUCT SEALING SPECIFICATIONS


1
PTCS DUCT SEALING SPECIFICATIONS
  • The Perfect Spec
  • Simple as possible
  • Achievable by the motivated, not just the true
    believer
  • Assure that energy savings have a probability of
    occurring
  • Produce measured, verifiable leakage reductions

2
The Challenges
  • Have the spec. recognize the differences between
  • New construction
  • Existing homes with new ducts
  • Duct repair
  • Manufactured housing

3
More Challenges
  • Have the Spec. recognize that all existing duct
    systems cannot be sealed to par bogeys and
    double bogeys are sometimes allowed
  • The 10 of floor area path
  • The 50 reduction path

4
Still More Challenges
  • Setting the eligibility threshold
  • Set it too high
  • Homes that might have received some duct sealing
    wont receive any
  • Set it too low
  • Contractors may only have to reduce the leakage a
    few cfm to qualify (10.5 to 9.5)
  • Require sealing of the supply plenum and take
    offs

5
One Last Challenge
  • How does PTCS verify the pre sealed leakage
    number?

6
  • Performance Tested Comfort System (PTCS)
  • Program Standards for Site Built Homes New
    Construction
  • New Construction Based on the protocol for
    Total Leakage Testing, or Leakage Testing to
    Exterior duct leakage in new construction shall
    not exceed 0.06 CFM50 x floor area served by the
    system (in square feet), or 75 CFM50 whichever is
    greater. In addition the following requirements
    must be met
  • All testing must be done by a PTCS Certified
    Technician or Inspector
  • Duct systems must be designed, sized and
    installed using recognized industry standards so
    that calculated heating and/or cooling loads are
    delivered to each zone (documentation may be
    required)
  • Based on the protocol for Combustion Appliance
    Zone Pressure Testing forced air system
    operation shall not de-pressurize a combustion
    appliance zone by more than 3 Pascals.
  • When combustion appliances are located within a
    conditioned space a UL listed carbon monoxide
    alarm, or equivalent must be installed.
  • Sealing Materials All duct sealing shall be done
    with mastics that meet the UlL181 AM or BM
    standard. Where taping is necessary (to provide
    service access), only UL-181 listed tape shall be
    used. Cloth duct tape is not acceptable.

7
  • Performance Tested Comfort System (PTCS)
  • Program Standards Existing Home, New Ducts
  • New Ducts existing homes Based on the protocol
    for Total Leakage Testing, or Leakage Testing
    to Exterior duct leakage for new systems in
    existing homes shall not exceed 0.10 CFM50 x
    floor area served by the system (in square feet),
    or 75 CFM50 whichever is greater. In addition the
    following requirements must be met
  • 1. All testing must be done by a PTCS Certified
    Technician or Inspector
  • 2.Duct systems must be designed, sized and
    installed using recognized industry standards so
    that calculated heating and/or cooling loads are
    delivered to each zone (documentation may be
    required)
  • 3.Based on the protocol for Combustion Appliance
    Zone Pressure Testing forced air system
    operation shall not de-pressurize a combustion
    appliance zone by more than 3 Pascals.
  • 4.When combustion appliances are located within a
    conditioned space a UL listed carbon monoxide
    alarm, or equivalent must be installed.
  • Sealing Materials All duct sealing shall be done
    with mastics that meet the UlL181 AM or BM
    standard. Where taping is necessary (to provide
    service access), only UL-181 listed tape shall be
    used. Cloth duct tape is not acceptable.

8
  • Performance Tested Comfort System (PTCS)
  • Program Standards for Site Built Homes Existing
    Homes, Existing Ducts
  • Existing Homes Based on the protocol for testing
    Duct Leakage to the Exterior, duct leakage in a
    retrofitted system shall
  • Be conducted by a Certified Technician or
    Inspector
  • 2. Required leakage reduction
  • A) Document a 50 reduction in leakage to
    the outside by
  • comparing duct leakage to the outside
    before and after
  • sealing
  • Or
  • C) In extreme cases where return ducts are
    inaccessible
  • compliance with 3A may be accomplished
  • by testing the supply side only.
  • 3 Regardless of qualifying path, the entire
    supply plenum and all take offs including the
    gores on flexible elbows shall be sealed
  • with approved materials.
  • 4.Based on the protocol for Combustion Appliance
    Zone Pressure Testing forced air system
    operation shall not de-pressurize a combustion
    appliance zone by more than 3 Pascals.
  • 5.When combustion appliances are located within a
    conditioned space a UL listed carbon monoxide
    alarm, or equivalent must be installed.
  • The leakage rate specified in 2 above is
    required for an existing system to be certified
    as meeting the PTCS standard. Some utilities may
    pay an incentive for test only or less than a
    50 reduction. Contact the sponsoring utility
    for specific program details.
  • Sealing Materials All duct sealing shall be done
    with mastics that meet the UlL181 AM or BM
    standard. Where taping is necessary (to provide
    service access), only UL-181 listed tape shall be
    used. Cloth duct tape is not acceptable

9
  • Performance Tested Comfort System (PTCS)
  • For Manufactured homes
  • Manufactured Homes Based on the protocol for
    Total Leakage Testing, or Leakage Testing to
    Exterior duct leakage in manufactured shall
  • 1 Be conducted by a Certified Technician or
    Inspector
  • 2 Have an existing tested leakage rate of 100
    CFM50 for single wide homes or 150 CFM50 leakage
    for double and triple wide homes
  • 3. Required leakage reduction Document a 50
    reduction in leakage to the outside by
  • comparing duct leakage to the outside before and
    after sealing
  • 4 Based on the protocol for Combustion
    Appliance Zone Pressure Testing forced air
    system operation shall not de-pressurize a
    combustion appliance zone by more than 3 Pascals.
  • 5When combustion appliances are located within a
    conditioned space a UL listed carbon monoxide
    alarm, or equivalent must be installed.
Write a Comment
User Comments (0)
About PowerShow.com