Title: Peerless PINNACLE
1(No Transcript)
2 3Peerless PINNACLE
- New Features
- P-125 Control
- PC Software
- Optional controls
4Target Markets
- Traditional boiler market
- Hydro-air market
- Combination space heat domestic hot water
market Canada and USA - Radiant market Typically upscale homes
- Commercial boiler market
- Combined triple integrated
- Traditional baseboard
- Snow melt (even with extremely low return water
temperatures)
5Wall Hung or Free Standing
6Ratings
7Features
- Floor-mounted/ Wall Mounted
- Zero clearance from combustibles
- Fully condensing / Low mass
- Thermal efficiency of 96
- AFUE of 92
- Environmentally Friendly Low Emissions
- Natural or LP
- High Altitude Models with Hot Surface Ignition
- Quiet
8Features
- Blocked vent switch
- Mesh Burner
- New Electrode
- Flame Rod
9Direct Vent
- Sealed Combustion
- Horizontal or Vertical venting
- PVC Venting up to 85 Feet (std)
- Termination options
- Standard Screened Tee Coupling
- Stainless Steel
- Concentric
10New P125 Control Board Features
- Improved Troubleshooting with LED display Module
- Status Menu / Installer Menu / Service Menu - Available PC software / Fault History Status
Screen/ Graphic display Screen - Optional Interface Module that will allow control
of the boiler with an 0-10 volt signal from an
external energy management controllerFeatures
like - A. Outdoor Reset
- B. Dual temperature set point. DHW priority
- C. Modulating Sequencing for multiple boilers
11(No Transcript)
12Packaged with System
- Electrical box with switch and cover
- 30 PSI Safety Relief Valve
- ¾ NPT Connection for gas hook up
- Combination temperature and pressure gauge
- Vent termination kit including tee and coupling
with screens (optional vent kits available) - Digital Display Module
13Optional Equipment
- 2 V500 Vent Termination Kit
- 3 V1000 Vent Termination Kit
- V2000 Vent Termination Kit
- 2 PVC Concentric Vent Kit
- 3 PVC Concentric Vent Kit
- Floor Mounted / Wall Mounted Stand
- Outdoor Reset Control (Tekmar 263)
- Adapter Interface Assembly
- P125 Software (requires pin type adapter cable)
14- Fully modulating pre-mix combustion, 31
turndown - PI-T50 50,000 BTU 18,000 BTU
- PI-T80 80,000BTU 19,000 BTU
- PI-800 180,000 BTU 27,000 BTU
- PI-140 140,000 BTU 46,000 BTU
- PI-199 199,000 BTU 66,000 BTU
- PI-399 399,000 BTU 100,000 BTU
- Gas Valve, Venting, Control Programming
allow for higher turndown - Low pressure drop through speciallyengineered
stainless steel manifolds - Integrated primary pump relay POWERED
- 316L Stainless Steel combustion chamber and
manifolds. - Heat exchanger is hydro-formed for maximum
surface area and efficiency
15(No Transcript)
16(No Transcript)
17(No Transcript)
18(No Transcript)
19- Comprehensive microprocessor control
- Greater voltage, fully automatic, spark ignition
system - Adjustable differential (5 30 in 1 degree
increments) - Adjustable aquastat 50 deg. F. 201 deg. F.
- Variable speed blower fan (31 modulation)
- Programmable Step Modulation
- External / Multiple Boiler Control (0-10 volt)
- Roto Cast ABS cabinet reduces operating noise and
weight - Approvals
- ITS
- IBR-GAMA
- CSA (Controls)
- UL and Energy Star
- ASME
- Low water pressure cut-out sensor (10 psi)
- High temperature cut-out sensor
- Blocked Vent Pressure Limit Switch
20How the P125 Controls Modulation
- Burner output based on actual system load
- Widest possible delta T across the heat exchanger
- Fan speed control regulates gas input
- Very accurate and instant variable burner output
- Input Modulation maintains low emissions and
reduces cycling - Modulation is monitored by
- analyzing the return water temperature
- supply water temperature
- set point temperature
- Pre-Mix gas valve and Venturi system
- Post purge state
- starts when the boiler reaches set point or
thermostat is satisfied - increase boiler efficiency
21P125 Controller and LED Display
- Pre-wired Display clearly shows fault codes and
can be placed inside or outside of Pinnacle. - Adjustable Settings
- 1. Supply temperature (Max 201F)
- 2. Differential
- 3. Temperature in F or C
- The display can be disconnected without effecting
system . However, the display is required to
reset any fault code. - Display will allow Dealers to program parameters
and view status of operation.
22New P125 Controller
- Features of the New System
- Temperature displays in Fahrenheit or Celsius
- Improved troubleshooting by status display of
- a. Supply and Return Temperatures
- b. Flame Signal
- c. Fan Speed
- Service Mode allows installers to manually
control the firing rate for easy set up - Available Software that allows the installer to
interface with PC to access status information
and fault history
23New P125 Controller
Optional Interface Module that allows the boiler
to be operated with a 0-10 volt analog input
signal from a modulating controller (such as
Tekmar) for features such as a. Outdoor Reset
Control b. Dual temperature set points for space
heating and indirect hot water demands c.
Modulating Sequencing for Multiple Boilers
24Venting
25Side Wall Venting
26PI-399
27Venting Options
28Roof Venting Options
29Vent Length
- Lengths are combined added lengths of exhaust
vent and air inlet vent
30Multiple Venting Options
- 8 spacing in between air intake termination
- Stainless Concentric
31Venting options
- Vertical or side wall
- Concentric, V1000 V500 vent Kits
- Extended vent lengths with 4 pipe
- Choice of PVC, CPVC, or ABS solid schedule 40 or
80 pipe - 5/8 Condensate connection
32Wall Hung Units Accessibility Clearances
NOTE THE PINNACLE IS A ZERO CLEARANCE TO
COMBUSTIBLES APPLIANCE
Suggested clearances for ease of servicing only
33Free Standing Accessibility Clearances
NOTE THE PINNACLE IS A ZERO CLEARANCE TO
COMBUSTIBLES APPLIANCE
- 6 from right
- 10from left back
- 15 from top
- 24 from front
- Provide for inspection of vent condensate
Suggested clearances for ease of servicing only
34Free Standing Accessibility Clearances
NOTE THE PINNACLE IS A ZERO CLEARANCE TO
COMBUSTIBLES APPLIANCE
Suggested clearances for ease of servicing only
35Recommended CirculatorsPrimary Secondary Piping
with Boiler on secondary loop
36Circulator Sizing
37Change to Peerless Drawing
38(No Transcript)
39(No Transcript)
40(No Transcript)
41Water Capacity
- PI-T50 .50 Gallon
- PI-T80 and PI-80 .63 Gallon
- PI 140 .93 Gallon
- PI 199 1.13 Gallons
- PI 399 1.30 Gallons
Glycol / Antifreeze 50 Maximum Boiler BTU
output will be reduced Head against the
circulator will increase Use only inhibited
propylene glycol formulated for hydronic heating
42Gas Piping
- It is very important that the gas line is
properly purged. Failure to properly purge the
lines or improper line sizing, will result in
ignition failure. This problem is especially
noticeable in NEW LP installations and also in
empty tank situations.
43Natural LP Gas Pressure
- Minimum Gas Pressure 3.7 W.C.
- Maximum Gas Pressure 13.5 W.C.
- Minimum Gas piping size ¾ (boiler provided with
¾ x ½ pipe reducer) - Incoming Pressure drop should not exceed .5 W.C.
Nat or 2 W.C. on LP - Minimum distance of 10 feet between gas regulator
and boiler
44Honeywell Gas Valve
45Dungs Gas Valve
46Combustion SettingsHIGH FIRING RATES and LOW
FIRING RATES ON ALL MODELS
47Display Module
48P125 Control
- Shows the boiler supply (outlet) water
temperature on the LED Display as default. - Adjust the supply water set point, the set point
differential, and change the display mode
between Fahrenheit and Celsius. - Provides Error and Fault Codes on the LED
Display. - Shows the supply and return temperatures, fan
speed, flame signal (µA), boiler circulator
status, boiler set point, total power on hours,
boiler on hours, and the number of cycles. - Allows manual control of the firing rate using
the Service Mode.
49 Display ModuleProgram Functions
50Programming Supply Temperature set point
- To access the menu, press and hold the S3
"Program" key on the display module. - The control will enter the Supply Set Point
selection. - The display will alternately show "C" and then
the current set point temperature. - The set point may be adjusted by using the S1/-
(to decrease) or S2/ (to increase) keys on the
display module.
To Store settings Press S3 and continue
51Programming Set Point Differential
- The differential adjustment is the difference
between the temperature that the boiler shuts
down (high) and the temperature at which it
re-starts (low). - The differential may be set to values between 5F
(3C) and 30F (17C) in 1F increments. - The boiler will always shut down at a temperature
7F (4C) above the set point. - The differential temperature is then applied to
this value. - The set point differential may be adjusted by
using the S1/- (to decrease) or S2/ (to
increase) keys on the display module.
- To Store settings Press S4 to END !!!!!!!!
52Measurement Units
Finally, by pressing the S3 "Program" key again,
the display will advance to the Measurement Units
selection. The display will alternate between "t
and either "F" or "C" depending on the units
selected. This value may be changed by using the
S1/- or S2/ keys on the display module.
Pressing the S3 "Program" key once more will exit
the program mode and again display the supply
temperature.
53Status MenuAccess by press S4 and hold for 3
secondsPress S4 again to scroll through codes
Press S3 to Exit Menu
54Installer Menu
To enter the installer menu, press and hold the
S3 "Program" key and S4 "Reset" key
simultaneously for 3 seconds. The display will
show a blinking "000. Use the S1/- and S2/
keys to change the display to read 125. Press the
S3 "Program" key to enter the installer menu.
(The control will shut down the boiler if it is
in operation.) The display will alternate between
1 and a value of either 0 or 1.
The Pinnacle boiler can be programmed to be
controlled by an external 0-10 volt analog input
controlling set point temperature or fan speed.
In addition, it can be programmed for a 6 minute
step modulation sequence.
55Installer Menu
- External Control (OFF or ON)
- Reset Temperature Control or Modulation
- Step modulation option
56Fault Codes
57Fault Codes
58Error Codes
59(No Transcript)
60(No Transcript)
61(No Transcript)
62(No Transcript)
63Suggested Tool List
- 10 mm socket and ratchet
- Stubby flat screwdriver
- Multi fit screwdriver
- Long 4 mm t-handle allen wrench
- 2 mm allen wrench
- Needle nose pliers
- Basic multi-meter
- Combustion Analyzer (Reading CO levels)
- 25 torx driver
- Small (pocket) regular screwdriver
64Parts List
Red is LP Blue is to confirm data
65Parts List
Red is LP Blue is to confirm data
66Parts List
67P125 Upgrade Components
68Promotional Support Materials
- Catalog Literature
- FAB Sheet
- Warranty
- 1 year parts labor on complete Pinnacle boiler
- 3 years parts warranty on blowers
- 12 year warranty on heat exchanger
- Price Sheets
- Installation, Operation Maintenance Manuals
69Product Differentiation
- Sold by the Best Reps in the Industry
- ASME Certified All Boilers
- One-Year Labor Warranty
- Extended Warranties Available
- Steel Table
- Full-Color Literature Consumer and Contractor
Oriented - Complete, Easy to Use IOM Manual
- National Advertising in the Leading Contractor
Publications - Contractor Mailing
- Support on the Website
- Support at Peerless
70ASME Advantages
- Each Boiler is Tested and Certified by a Third
Party - Provides Credibility to the Product
- Many Municipalities Require ASME
- Most Insurance Companies Require ASME
- Many Other Agencies Require ASME
- MIL Specs Require ASME
- Litigation is Aided by ASME
- Its Not a Pressure Vessel Unless it is ASME
Certified!
71THE END THANK YOU
72Blower
- Disconnect the white, red, blue, and black
connection from the Molex to the combustion
blower at the control board. This will cause the
fan to run at 100. - This will then blow out any sediment that has
accumulated in the condensate line if we block
the vent termination.
73Gas Valve Conversions Honeywell gas valve for
natural gas has NO orifice between the valve and
the air intake venturi.
- Need a Torx T25 nut driver and a 2 Phillips
screw driver. - Kit numbers Natural to LP
- PI-80 90334 orifice 4.0mmLP
- PI-140 90335 orifice 5.3mmLP
- PI-199 90336 orifice 5.4mmLP
74Amps Draw.87 amps draw upon start up .37 amps
draw running
- Read the flame rod with a voltage meter to read
the flame current. If its less than 1 micro-amp,
change or clean the flame rod. (4.2 micro-amps on
high fire). - Check the Gas pressure while the unit is running
to determine if pressure is adequate.
75Failure while Running
- Check that the condensate drain is clear, and
that condensate can flow freely from the boiler.
Back ups create steam which suffocates the flame,
throws off rectification, or in the worst case,
soaks the refractory plates, causing the spark to
ground out instead of sparking. - The CO levels at the exhaust breach should be
less than 100 ppm on high fire on all units.
76Failure while Running
- If there is a concentric vent kit installed,
check that it has been properly assembled and
GLUED. Exhaust gas recirculation will cause the
unit to fire then fail almost immediately. - On a PI 80, check that the brass vent barb on the
rear of the gas valve is not blocked by the rear
of the boiler cabinet. If so, shift the boiler
slightly forward in the cabinet.
77Boiler is Short Cycling
- First Check for Proper Water Flow through the
system. - If the Boiler continually fires and shuts down,
check incoming gas supply. An interruption, or
insufficient supply of gas will allow the boiler
to fire only briefly before failing without a
fault code.
78Water Pressure Switch
- The water pressure switch is designed to fault
the boiler off in the event that the system
pressure falls below 10 psi. The maximum
pressure that is allowed to the switch is 87 psi. - If a water pressure switch is leaking internally
it can short out the 24 volt transformer in the
control board, showing an error code. - This is seen more often with systems filled with
anti-freeze. - Circulator location and piping should be as per
manual. P/S with pump on return to boiler.
79Resistance Tables for sensorsSupply/Return water
temperature Thermistor
80Starting the Burner